HomeMy WebLinkAboutPP - 18200 OLYMPIC AVE S - MULTIPLE BUSINESSES - PERMITS AND PLANS18200 OLYMPIC AVE S
ASSOCIATED PERMITS
D16-0077 D05-353
D13-0363 M05-163
D05-356 167-15
Date: 3/23/15
TUKWILA FIRE DEPARTMENT
OPERATIONAL PERMIT
167-15
By virtue of The Provisions of the International Fire Code adopted by City of Tukwila Ordinance,
Soaring Helmet Corporation located at 18200 Olympic Avenue South
having made application in due form, and as the conditions, surrounding, and arrangements are, in my
opinion, such that the intent of the Ordinance can be observed, authority is hereby given and the
PERMIT is granted *To use a building or portion thereof as a high -piled storage area exceeding 500
square feet (46m2) per Chapter 32 of International Fire Code 105.6.22.
This PERMIT is issued and accepted on condition that all Ordinance provisions now adopted, or that
may hereafter be adopted, shall be complied with.
THIS PERMIT IS VALID FOR -Eighteen Calendar Months -
Fire Marshal
THIS PERMIT MUST BE POSTED ON THE PREMISES MENTIONED ABOVE.
Operational Permit Long 2012.dotx Rev. 4/17/14 TFP #2
A-AMERICA
INSPECTION NUMBER
INSPECTItN RECORD
Retain a copy with permit
li6-c077
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
206-575-4407
Projecil- QiIC-4 t:
Sprinklers:
Typ of I spection:
Address: l3 ?00
Suite #:
o/ yam/ ' e_,
eS
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: prvviY te c----,
Date: 7/02
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip::
Word/Inspection Record Form.Doc
3/14/14
T.F.D. Form F.P. 113
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with peril it
AoSjF4
1/3- c363
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206-575-4407
Project:
V &4
,%J/AI C
Fire Alarm:
Type of Inspection:
- ,;./ ke._
Address: / s v
Suite #:
01 y,vyo, G
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
nCorrections required prior to approval.
COMMENTS:
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Inspector: &
cvi _5-0._,
Date:
3/VJ//
Hrs.:
1
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip::
Word/Inspection Record Form.Doc
6/11/10
T.F.D. Form F.P. 113
MERCHANT DU VIN
City of Tukwila
Fire Department
F 11
OCT 3 1 2005
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Project Name Al P v r
Permit No. DOS-- J
Address /3 >-o Y 11 ' Suite #
Retain current inspection schedule
Needs shift inspection
"'"4. Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Fec /
Authorized Signature Date
Final Approval Frm
Rev. 5/2/03 T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439.
City of Tukwila
Fire Department
GLE
NOV 4 ?005
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Permit No.
,"o J
Project Name M e k z k aw+ Ov V 1
Address A 1S Suite #
! 1
Retain current inspection schedule
X- Needs shift inspection
IX Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
FPo _5"if /o -c) -2 -0c -
Authorized Signature Date
Final Approval Frm
Rev. 5/2/03 T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
August 31, 2016
Ms. Nicole Callais
Operations Manager
A -America
18255 Segale Park Drive B
Tukwila, WA 98188
RE: High -Piled Storage Evaluation — Tukwila Washington
Fire Protection System Analysis
18200 Olympic Ave S, Tukwila, WA 98188
Dear Ms. Callais:
C
JENSEN HUGHES
Advancing the Science of Safety
RECEIVED
CITY OF TUKWILA
SEP 412016
PERMIT CENTER
JENSEN HUGHES has been retained to evaluate concerns expressed by the City of Tukwila Fire
Department as to whether the current method of fire sprinkler protection at the A -America storage
warehouse is code compliant. The building has rack storage throughout, arranged in both a Double Row
and a Multiple Row configurations. The concern is that the storage arrangement may need additional
fire sprinkler protection given the height and combustibility of commodities being stored at the facility.
A previously completed analysis was performed on the sprinkler system at the facility, and JENSEN
HUGHES was asked to provide a more comprehensive overview of the fire sprinkler system and to
determine what system modifications, if necessary, are required to bring the sprinkler system up to
code. We utilized the following codes in the analysis of the system:
• International Fire Code (IFC), editions 2015 and 2012 as adopted by the State of Washington and
amended by the City of Tukwila
• NFPA 13, Standard for the installation of Sprinkler Systems, 2016 edition
ASSUMPTIONS
The first step for this analysis is to determine what commodity classification the IFC considers the
product being stored in the warehouse. Per discussions with A -America, the product at the facility
consists of wood dining room and bedroom furniture, which also contains small amounts of foam
padding (to prevent movement within the packaging), stored in cardboard boxes. From this description,
and applying Section 3203.4 of the IFC, we can ascertain that the stored product is of a Class III
commodity classification. NFPA 13 Table A.5.6.3.3 concurs with the IFC as to the classification of this
stored product.
Other parameters were also considered in the analysis. This information was culled from a variety of
sources, including City of Tukwila Fire Department, A -America personnel and submitted documentation.
We based our analysis on the following:
• From discussions with the City of Tukwila Fire Department, the existing WSRB sprinkler system
was designed with a design density of 0.39 gpm/ft2 over a design area of 5,600 ft2.
• The existing building has a ceiling height of 28' — 4".
• The Multiple Row Rack storage areas:
o Top of Storage (TOS) height of 13' — 4"
CORRECTION
LTR# 2-
O +1 720-441-6608
4445 Northpark Dr 1 Suite 204
Colorado Springs. CO 80907 USA
tfl(o 0011
jensenhughes.com
A -AMERICA HIGH -PILED STORAGE FIRE PROTECTION ANALYSIS PAGE 2 OF 4
o Rack depth of 19' — 2"
o Aisle width of 10'
• Double Row Rack storage areas:
o Top of Storage (TOS) height of 16' — 5"
o Rack depth of 9' — 1"
o Aisle width of 10'
• Storage arrangement that consists of wood pallets on wire mesh shelves on racks.
Multiple Row Rack Analysis
Using the information above to determine if the existing ceiling sprinkler system is adequate for
protection of this rack configuration we apply Table 16.2.1.3.3.2 of NFPA 13, "Multiple -Row Rack — Rack
Depth Over 16 ft or Aisles More Narrow Than 8 ft". Using a storage height of 13' — 4" and since the
product is not encapsulated, we use Figure 16.2.1.3.2(c), curves I and J to determine what the ceiling
sprinkler system should be designed to in order to adequately protect the multiple row racks in the
facility.
In addition, per Table 16.2.1.3.3.2, we are allowed to provide a reduced ceiling sprinkler density, per
Figure 16.2.1.3.4.1. This Table allows for the required ceiling sprinkler design density to be 60% of that
required in Figure 16.2.1.3.2(c) as the storage height is below 15 ft.
Per Table 16.2.1.3.2(c) curves 1 and J, the ceiling system must be designed to one of the following
protection scenarios for the multiple row rack areas:
• Curve I: If the existing ceiling system has High Temperature sprinklers installed, the ceiling
sprinkler density should be, at a minimum, 0.282 gpm/ft2 over a design area of 2,000 ft2. The
design density if 60% of that required by the Figure (0.47*0.6 = 0.282).
• Curve J: If the existing ceiling system has Ordinary Temperature sprinklers installed, the ceiling
sprinkler density should be between, 0.282 gpm/ft2 over a design area of 3,000 ft2 and 0.312
gpm/ft2 over a design area of 2,000 ft2. The design densities noted are 60% per that required by
the Figure.
Double Row Rack Analysis
Using the information for the double row rack arrangement, we follow the same methodology by
applying Table 16.2.1.3.2 of NFPA 13, "Single- or Double -Row Racks —Storage Height Over 12 ft Up to
and including 25 ft". Using a storage height of 16' — 5", non -encapsulated product, and an aisle width of
8 ft, we can apply Figure 16.2.1.3.2(c), curves E and F to determine what the ceiling sprinkler system
should be designed to. Curves G and H are eliminated from consideration as our aisle widths are greater
than 8 ft.
In addition, per Table 16.2.1.3.3.2, we are allowed to provide a reduced ceiling sprinkler density, per
Figure 16.2.1.3.4.1. This Table allows for the required ceiling sprinkler design density to be 65% of that
required in Figure 16.2.1.3.2(c) as the storage height is 16'-5".
Per Table 16.2.1.3.2(c) curves E and F, the ceiling system must be designed to one of the following
protection scenarios for the double row rack area:
• Curve E: If the existing ceiling system has High Temperature sprinklers installed, the ceiling
sprinkler density should be between, 0.21 gpm/ft2 over a design area of 3,000 ft2 and 0.24
JENSEN HUGHES
A • -AMERICA HIGH -PILED STORAGE FIRE PROTECTION ANALYSIS PAGE 3 OF 4
gpm/ft2 over a design area of 2,000 ft2. The design densities noted are 65% per that required by
the Figure.
• Curve F: If the existing ceiling system has Ordinary Temperature sprinklers installed, the ceiling
sprinkler density should be between, 0.25 gpm/ft2 over a design area of 3,000 ft2 and 0.27
gpm/ft2 over a design area of 2,000 ft2. The design densities noted are 65% per that required by
the Figure.
Summary of Findings
We compared the existing fire sprinkler system design to what is required by both the Multiple Row and
Double Row rack scenarios. To do this we utilized the design curve from the 2002 edition of NFPA 13,
Figure 12.3.2.1.2(c). The reason for using this table is that although the figure from the 2016 edition of
NFPA 13 is the same, the 2002 edition has an expanded graph of sprinkler design curves needed in this
analysis.
Design area of sprinkler operation (ft2)
6.1
6000
5000
4000
3000
2000
1000
8.2
A BC
Ceiling sprinkler density (mm/min) Existing Ceil.ng System
10.2
D
E
12.2
FG
•
14.3
H
16.3
•
1.6.3 20.4
1
Curve F. 65%
reduction Double Row
11111111111
Curve J. 60% reduction
Multiple Row
J
557
N
E
c
465 2
a)
0
372
0.
279 re
0
co
a2
co
186 c
", Singe point 'c
design only o
" 1 1 93
0.15 /b.20 0.25 0.30 0.35 0.40 0.45 0.50
Ceihn• sprinkler density (gpm/ft2)
Curve I, 60% reduction
Multiple Row
FIGURE 12.3.2.1.2(c) Sprinkler System Design Curves — 2O -ft (6.1-m) I -
Class III Nonencapsulated Commodities — Conventional Pallets.
Curve E. 65%
reduction Double Row
From the figures above we can clearly identify that the existing system was designed in such a manner
that it can supply a more than adequate amount of fire protection to both rack scenarios throughout the
facility.
JENSEN HUGHES
. A -AMERICA HIGH -PILED STORAGE FIRE PROTECTION ANALYSIS PAGE 4 OF 4
This analysis is based on storage heights provided to us by the Owner. They have indicated that
although the rack structures in place can handle more storage height in the facility, they would like to
have the system reviewed before considering more shelving. Any future rack storage additions should
be reviewed by a sprinkler contractor and designed accordingly.
JENSEN HUGHES appreciates the opportunity to be of assistance. If you have any questions please
contact me directly at 720.441.6620.
Sincerely,
JENSEN HUGHES
Carl W. Chappell
Senior Fire Protection Engineer
JENSEN HUGHES
Fire Sprinklers ■
WA CL#FIRESI.988RJ
1524 45th Street E, Suite 102, Sumner, WA 98390.253-826-0099 • Fax 253-826-1033 • www.firesprinklersinc.com
Friday, July 15, 2016
Raymond Handling Concepts Corporation
Attn: David Norris
3500 West Valley Hwy N, Suite 101
Auburn, WA 98001
Re: A -AMERICA
18200 Olympic Ave S.
Tukwila, WA 98188
Mr. Norris,
Based on my inspection of the existing fire sprinkler system I determined that the existing fire
sprinkler system resembles a typical Washington Survey and Rating Bureau (WSRB) sprinkler
system. The identifying WSRB characteristics seen were 8" looped mains, oversized riser
nipples, and large orifice sprinklers. With this information I conclude that the existing fire
sprinkler system has a design density of .395 gpm with a remote area of 5,600 square feet
(.395/5,600).
As the plans dictate, the proposed storage arrangements are Multiple -Row Racks which exceed
16' in depth with a storage height over 12' up to and including 15' and a Double Row Rack
consisting of (2) Single Row Back -to -Back Racks not exceeding 12' in depth and a storage height
over 12' up to and including 20' with a 12" longitudinal flue space.
Additionally, the commodity stored in racks is on wood pallets, non -encapsulated, cartoned,
unassembled wood product consisting of various wood compositions i.e. pressboards
(fiberboard), wood and plywood's. Expanded plastic protective inserts are located in the corners
of the cartoned unassembled wood product commodity. The amount of expanded plastics present
consist of less than 1% by weight and less than 10% by volume therefore it is allowed to be
recognized by IFC as a Class II commodity.
NFPA #13 2013 Edition, Table 16.2.1.3.3.2 dictates that a Multiple -Row Rack which has a depth
exceeding 16' and a storage height of 12' up to and including 15' in height, with a non -
encapsulated Class II commodity (unassembled wood product) shall be protected per Figure
16.2.1.3.2(b) Curve J (ordinary temperature sprinklers) requiring a 0.420 density over a 3,000
square foot remote area (0.420/3,000) requiring no in -rack sprinklers. Applying Figure
16.2.1.3.4.1 the design density shall be adjusted by 60% for 15' top of stored commodity.
Therefore, the required density will be
0.420 x 60% = 0.252 gpm.
CORRECTION
LTR#
bi 0017
RECEIVED
CITY OF TUKWILA
JUL 18 2016
Call FSI for all of your Fire Sprinkler Installation, Service, Inspection and Design needs-,ERMl•l, CENTER
ti
NFPA #13 2013 Edition, Table 16.2.1.3.2 dictates that a Double -Row Rack with a storage height
of 12' up to and including 20' in height and aisles greater than 8' per 16.2.1.3.2.1(B) with a non -
encapsulated Class II commodity (unassembled wood product) shall be protected per Figure
16.2.1.3.2(b) Curve F (ordinary temperature sprinklers) requiring a 0.330 density over a 3,000
square foot remote area (0.330/3,000) requiring no in -rack sprinklers. Applying Figure
16.2.1.3.4.1 the design density shall be adjusted by 60% for 15' top of stored commodity.
Therefore, the required density will be
0.330 x 60% = 0.198 gpm.
In conclusion, the planned storage of a class II non -encapsulated cartoned commodity
(unassembled wood product) in the proposed Multi -Row Racks with a storage height of 15' or
less and the Double Row Rack consisting of (2) Single Row Back -to -Back Racks not exceeding a
storage height greater than 20' will not require modifications.
Sincerely,
53'tett Atowd4en
Brett Morrison
President
losimmeammumesimainammommenumem
WASHINGTON WATS
CNRTIFISAT! Or COIMRTlNOT
FMB PROTECTION ASID N ISR OTITZINI
Brett A. Morrison
90471001 -CG Level
Fire : 'dere Incorporated
1
Call FSI for all of your Fire Sprinkler Installation, Service, Inspection and Design needs.
Norita Deckard
From: Don Tomaso
Sent: Wednesday, May 25, 2016 2:25 PM
To: Norita Deckard
Subject: Business Change
Main Actions IRouting Status _pouting History
Activity # 00025735
Code Napo 'Bus Lic Application
Activity date 05/19/2016
Organization a License
Name A AMERICA INC
Address 18200 OLYMPIC AVE S
Apt/Suite
City TUKWILA.
Label (Value
Fee effective date 05/19/2016
State WA 1"
Status pendnc
Type Opp
Pending
Application
Due date 05/19/2016 Expected issue date 05/19/2016
Phone (206) 575-3044
Lic type buslic Business License
Lic #
•
Zip 9 1 -4721
Initials
Email notification sent
nwil" 47-tm-
4 • 4;40.457.01.,!:q
'
#PIT Owner/Employees
FTE/Annual Hours
3840
Don Tomaso
Battalion Chief
1