HomeMy WebLinkAboutST - 10430 EAST MARGINAL WAY SOUTH - WYER CONSTRUCTION COMPANY / KING COUNTY METRO - STORAGE TANKSTANKS)
UNDERGROUND STORAGE TANKS (UST) 1 ABOVE GROUND STORAGE TANKS (AST)
10430 EAST MARGINAL WAY SOUTH
PARCEL NUMBER(S)
323049028
RELATED PERMIT NUMBER(S)
6-19
7-19
/ o e fl &-
Date: 2/26/19
Tukwila Fire Department
OPERATIONAL PERMIT
By virtue of the provisions of the International Fire Code adopted by City of Tukwila Ordinance,
Wyser Construction Company, Inc. located at 3301 South Norfolk Street
6-19
7-19
having made application in due form, and as the conditions, surrounding, and arrangements are, in my opinion, such that the intent of the Ordinance can
be observed, authority is hereby given and the PERMIT is granted to install, alter, remove, abandon or otherwise dispose of a flammable or combustible liquid tank
per 105.7.8 of the International Fire Code.
This PERMIT is issued and accepted on condition that all Ordinance provisions now adopted, or that may hereafter be adopted, shall be complied with.
THIS PERMIT IS VALID FOR -Ninety Days -
This permit does not take the place of any License
required by law and is not transferable. Any change in
use or occupancy of premises shall require a new permit.
Fire Marshal
THIS PERMIT MUST BE POSTED ON THE PREMISES MENTIONED ABOVE.
T.F.D./F.P. #2
., Marine Vacuum Service, Inc. P0. Box 24263 Seattle, Washington 98124
Telephone (206) 762-0240
CONTRACTORS LICENSE # MARI VS097JA FAX (206) 763-8084
1-800-540-7491
GENERAL CONTRACTOR
AST/UST STORAGE TANK PUMP & RINSE CERTIFICATE
Tank Size: i 0 PO //7;7
Last Contents
Tank Location:/
1r1,'
77:60 ri 6/7:+1
Marine Vacuum Service, Inc. certifies that the above mentioned tank(s) have been triple n sed in
accordance with the industry standard as outlined in 40 CFR PART 280.70, WAC 173-360.1
380(1), API 1604, API 2015 and that all residual product and rinSate has been disposed of in
accordance with Federal, State and Local regulations. Tanks listed above are NOT GAS FREE
or NOT SAFE FOR HOT WORK
Tank Owner:
Contractor:
M.V.S. Representative: bjel-rt.
Date: ?'
2 /y
f
/, - Jf'.
Notes:
_ J
a Orin
i ! ecC1 , ()\.'r)
DBE # D4M1302341
S
EPA # WAD980974521
A MINORITY BUSINESS ENTERPRISE ID # D4M1302341
SOUND TESTING, INC.
P.O. BOX 16204 SEATTLE, WA 98116
(206) 932-0206 FAX (206) 937-3848
WWW.SOUNDTESTINGINC.COM
ilemavtt---
ray
est
Survey R ed by
riol/f0 '- ' j Crrt)ii57 s
Vessel,
J
Di /) (aY)
Last Three (3) Loadings
MARINE CHEMIST CERTIFICATE
.... SERIAL N9 47276
e_i'-, 11-41 /Li 9
VessTOwner orAgent Date
Type of Vessel Specific Lo tion of Vessel
Tests Performed
Y/t$Z
Time Survey Completed
17`(75 .E 46 C ,z Ziff e 4":4 . . %�~m
e'es:;61,),
f 4 7 —/(,4 p f -7 f ',
)41.4%.. 7L'o' 5kr
i 4
X.71 -445-
e 2 /-!e /4, .-moi /5,row'' 014 A '.
7 },i/k 144111414-
2— s
In the event of changes adversely affecting conditions in the above spaces, or if in any doubt,
immediately stop all work and contact the undersigned Marine Chemist.
Qualifications: Manipulation of valves or devices tending to alter conditions in pipe lines or tanks noted above, unless specifically approved in this certificate, will
require re -inspection and a new Certificate for spaces so affected. All piping, heating coils, pumps and floating roof gaskets attached to or contained within spaces
listed above shall be considered "NOT SAFE" unless otherwise specifically designated.
STANDARD SAFETY DESIGNATIONS
(These detail the..minimum conditions for Safe Entry and Hot Work.) The Marine Chemist may request additional measures if workplace conditions so dictate.
ATMOSPHERE SAFE FOR WORKERS means that in a space (a) the oxygen content is between 19.5% and 22% by volkme, and (b) combustible gas is less than 10% of the Lower
Explosive Limit, and (c) airborne toxic materials are within permissible concentrations as listed in OSHA's Subpart Z or in ACGIH's current list of Threshold Limit Values.
SAFE FOR HOT WORK means that (a) oxygen within the space is less than 22% by volume; and (b) the combustible gas is less than 10% of the Lower Explosive Limit; and (c) cargo
residues within the space will not combust during hot work; and (d) pipes that can deliver hazardous materials to the workspace have been separated, blanked, or locked out, and nearby
hazardous spaces have been evaluated and noted on the certificate.
NOT SAFE FOR HOT WORK: In the compartment or space so designated, hot work is not permitted.
"The undersigned acknowledges receipt of this Certificate and understands conditions and
limitations under which it was issttedt"
e".+1 Jn
Signed I ' + �/ 4. it
Name
li
CompKny
POSTING
This Certificate is based on conditions existing at the time the inspection herein set forth was completed
and is issued subject to compliance with all qualifications and instructjpns'�;?
Dat
pv4'ry\ Signed
50UND TESTING, INC.
P.O. BOX 16204 SEATTLE, WA 98116
(206) 932-0206 FAX (206) 937-3848
WWW.SOUNDTESTINGINC.COM
MARINE CHEMIST CERTIFICATE
SERIAL 47271
Survey Requested by
Vessel Owner or Agent
Date
Vessel
Type of Vessel
Specific Location of Vessel
Last Three (3) Loadings
Tests Performed
Time Survey Completed
In the event of changes adversely affecting conditions in the above spaces, or if in any doubt,
immediately stop all work and contact the undersigned Marine Chemist.
Qualifications: Manipulation of valves or devices tending to alter conditions in pipe lines or tanks noted above, unless specifically approved in this certificate, will
require reinspection and a new Certificate for spaces so affected. All piping, heating coils, pumps and floating roof gaskets attached to or contained within spaces
listed above shall be considered "NOT SAFE" unless otherwise specifically designated.
STANDARD SAFETY DESIGNATIONS
(These detail the minimum conditions for Safe Entry and Hot Work.) The Marine Chemist may request additional measures if workplace conditions so dictate.
ATMOSPHERE SAFE FOR WORKERS means that in a space (a) the oxygen content is between 19.5% and 22% by volume, and (b) combustible gas is less than 10% of the Lower
Explosive Limit. and (c) airborne toxic materials are within permissible concentrations as listed in OSHA's Subpart Z or in ACGIH's current list of Threshold Limit Values.
$AFE FOR HOT WORK means that (a) oxygen within the space is less than 22% by volume; and (b) the combustible gas is less than 10% of the Lower Explosive Limit; and (c) cargo
residues within the space will not combust during hot work; and (d) pipes that can deliver hazardous materials to the workspace have been separated, blanked, or locked out, and nearby
hazardous spaces have been evaluated and noted on the certificate.
NOT SAFE FOR HOT WORT( In the compartment or space so designated, hot work is not permitted.
"The undersigned acknowledges receipt of this Certificate and understands conditions and This Certificate is based on conditions existing at the time the inspection herein set forth was completed
limitations under which it was issued." and is issued subject to compliance with all qualifications and instructions.
Signed Signed
Name Company Date Marine Chemist Certificate No.
POSTING
A
B
METRO FURNISHED
SUBMERSIBLE PUMP
FOR INSTALLATION BY
CONTRACTOR
METRO FURNISHED
12,000 GAL DIKE TANK
FOR TEMPORARY INSTALLATION
BY CONTRACTOR, SEE DWG G!03
POWER CONDUIT FROM
PANEL VIA NEW
CONTACTOR, SEE DWG E406
1
ISOLATION
VALVE
4
C
SOLENOID VALVE (TYP 2 PLACES)
SEE DWG E406
INSTALL METRO FURNISHED METER
(VEEDEDRIVER RIVER(TOKOHEIM,8DEL 1
MODEL400/15/SP/2),
FILTERS, HOSE COUPUNG, HOSE
AND NOZZLE (TYP 2 PLACES)
3" DOS
METER PEDESTAL W/ NOZZLE
CRADLE, FABRICATE FROM
It 1/4" AND TS 3x3x1/4
ANCHOR TO PAVEMENT (4 PLACES
SEE DWG E406 FOR ELECTRICAL
CONTROLS (TYP 2 PLACES)
,
DIKE TANK PIPING SCHEMATIC
(FIRST LOCATION FOR TEMPORARY INSTALLATION)
EL 18 14
L
/-6" OUTLET a
TO SD
1E 13 55
EL. 10 39
3'-0" INSIDE
SECTION LOOKING EAST
i
6" INLET
0
M
ISOLATION VALVE W/ LEVER
(TYP 2 PLACES)
EMERGENCY IMPACT VALVE
EMCO WHEATON MODEL A60-002
OR EQUAL (TYP 2 PLACES)
1 1/2" DOS TO METER (TYP)
COVER M-20 LOADING
WITH 2 EACH 12" X 12"
AND 1 EACH 24" X 24"
ACCESS MANWAYS —�
A
3" DOS FROM
SUBMERSIBLE
PUMP (SEE M403
b DET U/M404
FOR CONT )
D
1
E
F
G
H
DIKE VENT, EXTEND
2' ABOVE PARAPET
�+---2" PRIMARY TANK VENT,
EXTEND 2' ABOVE PARAPET
POWER CONDUIT FROM
PANEL VIA NEW
CONTACTOR, ROUTE
12'-6"± ABOVE GRADE
PROVIDE TEMPORARY
PIPE SUPPORT (TYP )
FUEL AND WASH BLDG
LINE OF PARAPET
METRO FURNISHED
SUBMERSIBLE PUMP
FOR INSTALLATION BY
CONTRACTOR
METRO FURNISHED
12,000 GAL DIKE TANK
FOR TEMPORARY INSTALLATION
BY CONTRACTOR, SEE DWG G103
u
IE 14 05 h'�
5'-0" INSIDE
SECTION LOOKING NORTH
EXISTING OIL WATER SEPARATOR
(FOR REFERENCE ONLY)
D E TALI L
SCALE T 1/2"=I'-0"
No
REVISION
T
4
BY
B
DATE
BAFFLE (TYP)
PAVEMENT
EXTENSION
SECTIONS
DIKE TANK PIPING SCHEMATIC
(SECOND LOCATION FOR TEMPORARY INSTALLATION)
ADJUSTABLE DRAW OFF THREADED
2" EL, 2" X 1-1/2" P -TRAP
ADAPTOR (SCREWED X SUP JOINT)
WITH NUT, 1-1/2" X 6" 17 GA
BRASS TUBE
2" FRP PIPE TO WASTE
OIL TANK PITCH DOWN
1/4"/FT
PRECAST CONCRETE VAULT
EXTENSION SECTIONS
DETAIL
SCALE - NONE
1 EMBED TOP EDGE OF FILTER FABRIC
24" IN LEAN CONC MIX (TYP. ALL
AROUND EXCAVATION)
lI PAVEMENT, SEE CIVIL DWG'S
1
EXIST SOIL
(TYP)
LIMIT OF EXCAVATION
(TYP)
TYPE A FILL MATL
1
INDICATES WALL PENETRATION
(TYP OF 2)
CONNECT TO EXIST
2" DOS 0 THIS POINT
SEE DET B/ M403
FUEL AND WASH BUILDING
2'-0" MIN OR AS
RECOMMANDED BY TANK
MANUFACTURER (TYP )
12'-0" (TYP)
INDICATES PIPING INTO
CONC SLAB (TYP )
ROUTE TO EMER GENERATOR
AND STANDBY BOILER
FROM DIKE TANK
(SEE DET T/M404)
EXIST METERING DISPENSERS
INDOOR FUEL ISLANDS (RIGHT
SIDE FUELING, 4 TYP)
EXIST METERING DISPENSER
OUTDOOR 0 NON -REV
FUEL APRON
CONNECT TO EXIST
2" DOS 0 THIS POINT
3" DOS FROM VALVE BOX
SEE M401 FOR CONTINUATION
- DIESEL FUEL DISPENSING SCHEMATIC
1
TYPE "A" FILL
4'-0"
—1,-0"
TYPE D FILL MATERIAL (PEA GRAVEL MINUS
CONFORMING TO SPECIFIED GRADATION (TYP))
6" LEAN CONCRETE MIX (CONTROLLED
DENSITY FILL) SEE NOTE 1
• /2•/,/\
'ENVELOPE PEA GRAVEL BACKFILL
1 AROUND ENTIRE TANK EXCAVATION
WITH FILTER FABRIC AS SHOWN,
'SEE NOTE 1
EMBED FILTER FABRIC 24" IN CONCRETE OR
HOLD BOTTOM OF FABRIC AS RECOMMENDED BY
FABRIC MANUFACTURER
TANK HOLD DOWN
BALLAST, SEE DET A/M501
1).1','jt. kl�1r
4! Ci <:` '•' 1 CAW
,
;ft,ii
.1121
^'' PPROVED
OW;nye :4, 4 i 757L-.
SECTION
1'-0 ; BEDDING
SCALE I /8'= I '•-0"
t
HOLD DOWN HARDWARE
(SEEDET A/M501,
tYP )
NOTES:
_,_1'_O»
95% COMPACTION
BELOW SLAB
1 LEAN CONCRETE AND FILTER FABRIC ARE REQUIRED
IN AREAS OF VEHICLE CIRCULATION
2 SEE DWG M101 FOR MECHANICAL SYMBOLS
RAVEN
Cf
��/fff
SCALE.
NOTED
7
C
E
F
CONTRACT NO
T/M 11-93
T
U
z
LAI
z
0
Wy
o0
`` 0
z�
Li.. V
Lai
N Lai
NQ
J �Nj
J
1i =
Q?
1100 c 5 129891
Municipality of Me tropolitan Seattle
SOUTH BASE / UNIT REPAIR
UNDERGROUND TANK REPLACEMENT
AREA 4
DETAILS AND PIPING SCHEMATICS
G
7
DATE.
MARCH 1993
ALE Na
X14
DRAWING NO-
M404
P
M404
SHEET NO.44 63
H
A
HAZARDOUS STORAGE
SHED
EXISTING PANEL "P9"
SEE DET B/E406
FIRST LOCATION FOR
TEMPORARY DIESEL FUEL
TANK INSTALLATION
SUBMERSIBLE PUMP
FURNISHED BY METRO
12OVAC FROM
UNE STARTER
B
3/4"RGS POWER
WIRING CONDUIT
METRO FURNISHED
SUBMERSIBLE PUMP
FOR INSTALLATION BY
CONTRACTOR
A
D
METRO FURNISHED
12,000 GAL. DIKE TANK
FOR TEMPORARY INSTALLATION
BY CONTRACTOR, SEE DWG G103
POWER CONDUIT FROM
PANEL VIA NEW CONTACTOR
SEE CONTROL DIAGRAMS THIS
DWG
SOLENOID VALVE
(TYP 2 PLACES)
METRO FURNISHED METER
(TYP 2 PLACES)
,-
TEMPORARY PUMP
7—
STARTER & TIMER
RELAY PANEL INSTL
SEE DET C/E406
PLAN -- TEMPORARY DIKE TANK! INSTALLATION
r
t
0
DISPENSER
CRADLE SW #1
f
s
CONTRACTOR TO PROVIDE
PROTECTIVE RAMP FOR
CONDUIT CROSSING, ANCHOR
ANCHOR TO EXISTING PAVING
SOL #1
DISPENSER
CRADLE SW #2
1
DIKE TANK PIPING SCHEMATIC
(FIRST LOCATION FOR TEMPORARY INSTALLATION)
CONCEPTUAL DIAGRAM
SOL #2
b
DIESEL OIL SUPPLY PIPING
TIMER RELAY PANEL
DETAIL
SCALD _ NONE
FUEL NOZZLE
230VAC
L2 Li N
20A,3P
BREAKER
3/4"RGS POWER
& CONTROL WIRING
CONDUIT TO TIMER
RELAY PANEL, SEE a
DET C/E406
1 1/2" DOS TO METER (TYP)
•
•
ex
GROUND WIRE, SAME
SIZE AS CURRENT
CARRYING CONDUCTORS
f
-do-- PANEL "P9"
3PST
TOGGLE
SWITCH
r-- LINE
STARTER
•
i
1TR�'
ZTR'
0,4
.7
DISPENSER
CRADLE SW #1
oho
DISPENSER
CRADLE SW #2
SOL #1
SOL #2
DIESEL OIL PUMP CONTROL DIAGRAM
(1ST LOCATION - TEMPORARY DIESEL FUEL TANK)
OPERATION
E
F
1
4
A
G
3/4"RGS CONDUIT TO DIESEL
OIL PUMP LINE STARTER 1
0
00
0
EXISTING PANEL "P9"
SEE NOTE 1
1 WHEN NOZZLE IS REMOVED FROM
CRADLE SWITCH IS CLOSED ENERGIZING
TIMING RELAY WHICH CLOSES CONTACT
ENERGIZING PUMP MOTOR, AND OPENS SOL
2 WHEN NOZZLE IS REPLACED ON CRADLE,
CRADLE SWITCH OPENS DE -ENERGIZING
TIMING RELAY WHICH STARTS PRESET
TIME DELAY AT COMPLETION OF TIME
DELAY CONTACT OPENS DE-ENERG1Zt,j4G
PUMP MOTOR
HAZARDOUS STORAGE SHED — OUTSIDE PANELS
DIESEL OIL PUMP
-LINE -STARTER..,
3/4"RGS POWER & CONTROL
WIRING CONDUIT TO PANEL
"P9" 0 HAZARDOUS STORAGE
SHED
•
A
J
0
H
A
NOTES:
1 CONTRACTOR SHALL DE -ENERGIZE PANEL
"P9" BEFORE REMOVING COVER TQ INSTALL
PUMP POWER WIRING AFTER NEW WIRING
IS COMPLETED REINSTALL COVER WITH NEW
GASKET AND TORQUE COVER BOLTS PER
MANUFACTURERS SPECIFICATION
TIMER RELAY PANEL
TEMPORARY PLYWOOD
BACKBOARD AND POSTS
3/4"GRS POWER & #CONTROL
WIRING CONDUIT TO DIESEL
OIL TANK _
i
STARTER AND TIMER RELAY PANEL -- TEMPORARY INSTALLATION
DETAIL -
SCALE NONE
V
z
W
z
0
No.
REVISION
BY
APP D
DATE
fiAi21"
14
91,
DRAWN CHECKED
A.,
RECOMMENDED
t
„meTwo
SCALE.
NONE
APPROVED
CONTRACT NO
T/M 11-93
Municipality of Metropolitan Seattle
SOUTHBASE/UNIT REPAIR
UNDERGROUND TANK REPLACEMENT
AREA 4-FUEL/WASH BLDG.
ELEC. DIAGRAM & MISC. T DETAILS
129910
DATE
MARCH 1993
FILE NO
X14
DRAWING N0
E406
SHEET NO OF
63 -- 63
B
C
7
F
IfL
G t
_ f — ra
.a. .mm3 3a.�
3
- - -
H
r -w
A B
C
D
E
F
G
H
5
ONLY TANKS WHICH HAVE BEEN IDENTIFIED FOR REMOVAL
ARE SHOWN ON THIS DRAWING OTHER EXISTING
UNDERGROUND TANKS ARE NOT SHOWN FOR CLARITY.
B M ELEVATION ESTABLISHED FROM SOUTH BASE BUILDING
AND PAVING CONTRACT, METRO NO T3B74-13, DRAWING G2.
R R SPIKE ON NORTH SIDE OF POWER POLE N OF S
ENTRANCE TO SOUTH BASE DATUM IS U S C AND
G S 1929, ADJUSTED 1947 AND PUBUSHED BY N S G
(USC AND G S) IN 1972
5
REMOVE:
(1) 6.000 GAL. DIESEL OIL TANK
INSTALL NEW METRO FURNISHED -
6.000 GAL DIESEL OIL TANK
1 3.000 GAL ENGINE OIL TANK
1 3,000 GAL. DUAL PRODUCT AUTOMATIC
TRANSMISSION FLUID TANK
SEE DETAIL A/G107 AND A/M301
STAFF PARKING
REMOVE AND INSTALL NEW METRO FURNISHED
(1) 2,000 GAL WASTE OIL TANK
SEE DET. B/G105 AND B/M202
HAZARDOUS
STORAGE
SHE
REMOVE
(1)6,000 GAL DIESEL FUEL TANK
1) 2,000 GAL WASTE OIL TANK
INSTALL NEW METRO FURNISHED.
(1) 6,000 GAL. DIESEL FUEL TANK
SEE DET B/G107 AND B/M301
FIRST LOCATION FOR
TEMPORARY DIESEL FUEL TANK
FURNISHED BY METRO
FOR INSTALLATION BY
THE CONTRACTOR
SEE DET S/M404
STORAGE
SHED
RETENTION POND
MAINTENANCE BLDG
AREA 2
GAL. TRANSMISSION FLUID TANKS
GAL LUBE OIL TANK
GAL WASTE OIL TANK
METRO FURNISHED:
GAL. TRANSMISSION FLUID TANK
GAL ENGINE OIL TANK
GAL ANTI—FRFT7F CONCENTRATE TANK
A/G106 AND A f M202
COACH PARKING
REMOVE.
1 550 GAL DIESEL FUEL TANK
1 1,000 GAL DIESEL FUEL TANK
3 12,000 GAL DIESEL FUEL TANKS
1 10.000 GAL. DIESEL FUEL TANK
1 2.000 GAL. WASTE OIL TANK
1 6,000 GAL ANTI—FREEZE CONCENTRATE TANK
1 8.000 GAL LUBE OIL TANK
1 12,000 GAL UNLEADED GASOUNE TANK
INSTALL NEW METRO FURNISHED -
(3) 12,000 GAL DIESEL FUEL TANKS
2,000 GAL WASTE OIL TANK
1 6.000 GAL ANTI—FREEZE CONCENTRATE TANK
1 6 000 GAL ENGINE OIL TANK
1 12,000 GAL UNLEADED GASOUNE TANK
SEE DET A/G108 AND DWG M401
REMOVE.
1 6,000 GAL. DIESEL FUEL TANK
1) 550 GAL DIESEL FUEL TANK
INSTALL NEW METRO FURNISHED
(1) 6.000 GAL. DIESEL FUEL TANK
SEE DET A/G105 AND A/M201
STAFF PARKING
SECOND LOCATION FOR
TEMPORARY DIESEL FUEL TANK
FURNISHED BY METRO
FOR INSTALLATION BY
THE CONTRACTOR
SEE DET T/M404
3
4
1
CONTRACTOR TO PROVIDE
TANK PROTECTION, JERSEY
BARRIER, ECOLOGY BLOCKS
OR OTHER APPROVED
METHOD
2
OPERATIONS BLDG
FUEL AND WASH BLDG
1 AREA 4
CONTRACTOR'S GATE
(SEE DWG C101)
EXIST POWER
POLE
EAST MAGINAL WAY
Municipality of Metropolitan Seattle
SOUTH BASE / UNIT REPAIR
UNDERGROUND TANK REPLACEMENT
129850
DAZE
MARCH 1993
RENO
X14
DRAWING NO.
REVISION
CONTRACT NO
TAA 11-93
SITE PLAN
A
B
C
0
E
V
F
V
G
V
H
3