PLUMBING/GAS PIPING PERMIT
0923049066 Permit Number: PG18-0147
3215 S 116TH ST 109
Project Name: NATERA
Issue Date: 1/2/2019
Permit Expires On: 7/1/2019
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
EPROPERTY TAX INC DEPT 207
POBOX 49OU'S[OlTSDAUE,WA,
85261
AMANDA MOORE
11621 E MARGINAL WAY S , TUKWILA,
WA, 98168
P S F MECHANICAL INC
11G21EMARGINAL WAY SSUITE A'
TUKWILA, WA, 98168-1965
License No: PSFMEI*090NZ
Lender:
Name:
Address:
''^
Phone: (206) 812-7683
Phone: (206) 764-9663
Expiration Date: 10/5/2019
DESCRIPTION OF WORK:
INSTALLATION OF APPROXIMATELY 70 IF. OF VACUUM JACKETED LIQUID NITROGEN PIPING AND EQUAL AMOUNT
OF COPPER VENT PIPING WITH A VENT HEATER. SCOPE OF WORK DOES NOT INCLUDE LN2 STORAGE TANKS OR
CRYOFREEZERS (INSTALLATION AND MAINTENANCE BY OTHERS).
Valuation of Work: $0.00
Water District: TUKWILA
Sewer District: VALLEY VIEW
Fees Collected: $532J2
Current Codes adopted by the City of Tukwila:
International BuiIdng Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
International Fu& Gas Code:
Permit Center Authorized Signature:
2015
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
2017WA State Energy Code:
2017
2017
1
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature;
Print Name:
Date:1/1 Uvl`(
I' X4 \r\AA7O4-,
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: All permits, inspection records and applicable plans shall be maintained at the job and available to the
plumbing inspector.
2: All plumbing and gas piping systems shall be installed in compliance with the Uniform Plumbing Code and
the Fuel Gas Code.
3: No portion of any plumbing system or gas piping shall be concealed until inspected and approved.
4: All plumbing and gas piping systems shall be tested and approved as required by the Plumbing Code and
Fuel Gas Code. Tests shall be conducted in the presence of the Plumbing Inspector. It shall be the duty of
the holder of the permit to make sure that the work will stand the test prescribed before giving notification
that the work is ready for inspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
2000 GAS PIPING FINAL
8004 GROUNDWORK
1900 PLUMBING FINAL
9002 ROUGH -IN GAS PIPING
8005 ROUGH -IN PLUMBING
9001 UNDERGROUND
'4
I 1,
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
C
Plumbing/Gas Permit No. PA op -17
Project No.
Date Application Accepted: 1 — 1
Date Application Expires: 1 411 GI
(For office use only)
PLUMBING / GAS PIPING PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
King Co Assessor's Tax No.: 0923049066
Site Address: 3215 South 116th St Suite Number:
Natera
Tenant Name:
PROPERTY OWNER
Name: Amanda Moore
Name: E Property Tax Inc Dept
City: Seattle State: WA Zip: 98168
Address: PO Box 4900
Email: permits@psfmech.com
City: Scottsdale State: AZ
Zip: 85261
CONTACT PERSON — person receiving all project
communication
Name: Amanda Moore
Address: 11621 E Marginal Way S
City: Seattle State: WA Zip: 98168
Phone: (206) 812-7683 Fax:
Email: permits@psfmech.com
Floor:
New Tenant: D Yes ..No
PLUMBING CONTRACTOR INFORMATION
Company Name: PSF Mechanical, Inc.
Address: 11621 E Marginal Way S
City: Seattle State: WA Zip: 98168
Phone:
(206) 812-7683 Fax: (206) 762-8381
Contr Reg No.: PSFMEI*090NZ Exp Date: 10/05/2019
Tukwila Business License No.: BUS -0996384
Valuation of Project (contractor's bid price): $ 75,000
Scope of Work (please provide detailed information):
Installation of approximately 70 If. of vacuum jacketed liquid nitrogen piping and equal amount of copper vent piping with a vent
heater. Scope of work does not include LN2 storage tanks or cryofreezers (Installation and maintenance by others).
Building Use (per Int'l Building Code): Commercial
Occupancy (per Int'l Building Code): Group B
Utility Purveyor: Water: Tukwila Sewer: Tukwila Sewer Service
hi: \ Applications \ Forms -Applications On Line \ 2011 Applications,Plumbing Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
Fixture Type
Qty
Bathtub or combination
bath/shower
Dishwasher, domestic with
independent drain
Shower, single head trap
Sinks
Rain water system — per
drain (inside building)
Grease interceptor for
commercial kitchen (>750
gallon capacity)
11�
Each additional medical
gas inlets/outlets greater
than 5
f
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections (1-5)
Fixture Type
Qty
Bidet
Drinking fountain or water
cooler (per head)
Lavatory
Urinal
Water heater and/or vent
Repair or alteration of
water piping and/or water
treatment equipment
11�
Backflow protective device
other than atmospheric -
type vacuum breakers 2
inch (51 mm) diameter or
smaller
f
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections over 5
Fixture Type
Qty
Clothes washer,
domestic
Food -waste grinder,
commercial
Wash fountain
Water closet
Industrial waste
treatment interceptor,
including trap and vent,
except for kitchen type
grease interceptors
Repair or alteration of
drainage or vent piping
11�
Backflow protective
device other than
atmospheric -type
vacuum breakers over 2
inch (51 mm) diameter
f
Gas piping outlets
Fixture Type
Qty
Dental unit, cuspidor
Floor drain
Receptor, indirect waste
Building sewer and each
trailer park sewer
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity
Medical gas piping
system serving 1-5
11�
inlets/outlets fore specific
gas
f
Each lawn sprinkler
system on any one meter
including backflow
protection devices
Liquid Nitrogen
Piping
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 180 days. The extension shall be requested in writing
and justifiable cause demonstrated. Section 103.4.3 International Plumbing Code (current edition).
I HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND 1 AM AUTHORIZED TO APPLY FOR THIS PERMIT,
BUILDING OW/: OR AUTHO ZED AGENT:
Signatur : J/
Print Name: 11AKA1A.&( t AMe42-__
Mailing Address: 11621 E Marginal Way S, Suite A
H:\Apptications\Forms-Applications On Line\20t 1 Apptications`Plumbing Permit Application Revised 8-9-t t.docz
Revised: August 2011
bh
Date: 12/14/2018
Day Telephone: (206) 812-7683
Seattle WA 98168
City State Zip
Page 2 of 2
r 1,
DESCRIPTIONS
PermitTRAK
ACCOUNT
QUANTITY
PAID
$532.72
PG18-0147 Address: 3215 S 116TH ST 109 Apn: 0923049066
$532.72
Credit Card Fee
$15.52
Credit Card Fee
R000.369.908.00.00
0.00
$15.52
PLUMBING
$497.31
PERMIT FEE
R000.322.100.00.00
0.00
$364.70
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PLAN CHECK FEE
R000.322.103.00.00
0.00
$99.46
TECHNOLOGY FEE
$19.89
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R16067
R000.322.900.04.00
0.00
$19.89
$532.72
Date Paid: Friday, December 14, 2018
Paid By: AMANDA MOORE
Pay Method: CREDIT CARD 669707
Printed: Friday, December 14, 2018 1:23 PM 1 of 1
(7,
SYSTEMS
Page 2 of 2
CO TUKWILA ETRAKIT
6200 SOUTHCENTER BLVD
TUKWILA, WA 98188
206-433-1870
CITY OF TUKWILA
Date: 12/14/2018 01:23:27 PM
CREDIT CARD SALE
MASTERCARD
CARD NUMBER: **********5490 K
TRAN AMOUNT: $532.72
APPROVAL CD: 669707
RECORD #: 000
CLERK ID: Bill
Thank you!
Customer Copy
https://classic. convergepay.com/V irtualMerchant/transaction.do?dispatchMethod=printTr... 12/14/2018
12/3/2019
City of Tukwila
Department of Community Development
AMANDA MOORE
11621 E MARGINAL WAY S
TUKWILA, WA 98168
RE: Permit No. PG 18-0147
NATERA
3215 S 116TH ST 109
Dear Permit Holder:
("7
Allan Ekberg, Mayor
Jack Pace, Director
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric
Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null
and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 1/1/2020.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 1/1/2020, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
1:4 7-.1
Bill Rambo
Permit Technician
File No: PG18-0147
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
r�
City of Tukwila
Allan Ekberg, Mayor
Department of Community Development - Jack Pace, Director
June 20, 2019
Amanda Moore
11621 E marginal Way S
Tukwila, WA 98168
RE: Request for Extension #1
Permit Number PG18-0147
Dear Ms. Moore,
This letter is in response to your written request for an extension to Permit PGI8-0147. The Building
Official, Jerry Hight, has reviewed your letter and considered your request to extend the above
referenced permit. It has been determined that the City of Tukwila Building Division will be granting an
extension to the permit through January 1, 2020.
If you should have any questions, please contact our office at (206) 431-3670.
Sincerely,
Kandace Nichols
Permit Technician
File: Permit No. PG18-0147
Tukwila City Hall • 6200 Southcenter Boulevard • Tukwila, WA 98188 • 206-433-1800 • Website: TukwilaWA.gov
p 9 Building Relationships.
Creating Environment
June 14th, 2019
City of Tukwila
Department of Community Development
6300 Southcenter Blvd, Suite #100
Tukwila, WA 98188
ATTN: Kandace Nichols
0/ 47
RE: Permit No. PG18-04-74--
NATERA
3215 S 116 ST
To whom it may concem,
We would like to request a 180 day extension on the above mentioned permit. At this time work
is expected to begin in the next 3 months. Please contact me if there are any questions or
concerns,
Amanda Moore Permits and Licensing
PSF Mechanical, Inc.
(206) 812-7683 1 permits@psfinech.com 1 license@pslmech.com
PSFIVec
Request for Extensior # J
Current Expiration Date: 7 -ict
Extension Request:
)(Approved for days
Denied (provide explanation)
Signature/ nitials
Corporate Office (206) 764-9663 Tacoma Office 53) 830-5978
C r 424
16/ „ Margns: '168
5/31/2019
City of Tukwila
Department of Community Development
AMANDA MOORE
11621 E MARGINAL WAY S
TUKWILA, WA 98168
RE: Permit No. PG 18-0147
NATERA
3215 S 116TH ST 109
Dear Permit Holder:
Allan Ekberg, Mayor
Jack Pace, Director
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National Electric
Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and become null
and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 7/1/2019.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 7/1/2019, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Kandace Nichols
Permit Technician
File No: PG18-0147
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
/ PERMIT COORD Cop'O
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: PG18-0147 DATE: 12/14/18
PROJECT NAME: NATERA
SITE ADDRESS: 3215 S 116 ST
X Original Plan Submittal
Response to Correction Letter #_ Revision # after Permit Issued
Revision # before Permit Issued
DEPARTMENTS:
(j
Building Division
blit Wo"rk�
Fire Prevention
Structural
n
Planning Division
Permit Coordinator in
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 12/18/18
Structural Review Required
REVIEWER'S INITIALS: DATE:
n
APPROVALS OR CORRECTIONS:
Approved
❑ Approved with Conditions
Corrections Required Denied
(corrections entered in Reviews) (ie: Zoning Issues)
DUE DATE: 1/15/19
n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW D Staff Initials:
12/18/2013
P S F MECHANICAL INC
Home Espanol Contact
Safety & Health Claims & Insurance
ill)Washington State Department of
Labor & Industries
Page 1 of 3
;Search L&I
AZ Index Help My L&I
Workplace Rights Trades & Licensing
P S F MECHANICAL INC
Owner or tradesperson
Principals
REYNOLDS, JAMES P, PRESIDENT
READ, ANDREW A, PRESIDENT
BEARDSLEY, WARREN
SCOTT, SECRETARY
CRITCHLOW, JAMES D
(End: 09/27/2011)
Doing business as
P S F MECHANICAL INC
WA UBI No.
601 318 369
11621 E Marginal Way S
Suite A
SEATTLE, WA 98168
206-764-9663
KING County
Business type
Corporation
Governing persons
WARREN
BEARDSLEY
JOHN P KING;
CHRISTOPHER J LAWSON;
DOUGLAS 0 LONG;
ANDREW AARON READ;
License
Verify the contractors active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
PSFMEI*090NZ
Effective — expiration
08/09/1991— 10/05/2019
Bond
Travelers Cas & Surety Co
Bond account no.
105975899q
$12,000.00
Received by L&I Effective date
03/13/2014 03/13/2014
Expiration date
Until Canceled
Bond history
Insurance
Liberty Mutual Fire Insurance
Policy no.
TB2Z91452741018
$1,000,000.00
Help us improve
httos://secure.lni.wa.gov/verify/Detail.aspx?UBI=601318369&LIC=PSFMEI*090NZ&SAW= 1/2/2019
P S F MECHANICAL INC
Received by L&I
09/28/2018
Effective date
10/01/2018
Expiration date
10/01/2019
\
Insurance history
Savings
No savings accounts during the previous 6 year period.
Lawsuits against the bond or savings
No lawsuits against the bond or savings accounts during the previous 6 year period.
L&I Tax debts
No L&I tax debts are recorded for this contractor license during the previous 6 year period, but some debts
may be recorded by other agencies.
License Violations
No license violations during the previous 6 year period.
Workers' comp
Do you know if the business has employees? If so, verify the business is up-to-date on workers' comp premiums.
This company has multiple workers' comp accounts.
Active accounts
L&I Account ID
848,535-00
Doing business as
PSF MECHANICAL INC
Estimated workers reported
Quarter 3 of Year 2018 "Greater than 100 Workers"
L&I account contact
T3 / KAYLENE MONIER (360)902-6627 - Email: BRKB235@lni.wa.gov
Track this contractor el
Account is current.
Public Works Strikes and Debarments
Verify the contractor is eligible to perform work on public works projects.
Contractor Strikes
No strikes have been issued against this contractor.
Contractors not allowed to bid
No debarments have been issued against this contractor.
Workplace safety and health
Check for any past safety and health violations found on jobsites this business was responsible for,
Inspection results date
09/10/2014
Inspection no.
317399160
Location
9322 14 Avenue S
Seattle, WA 98108
Inspection results date
04/01/2013
Inspection no.
316732031
Location
600 University
Seattle, WA 98101
Violations
No violations
Page 2 of 3
« Washington State Dept. of Labor & Industries. Use of this site is subject to the laws of the state of Washington.
Help us improve
https://secure.lni.wa.gov/verify/Detail.aspx?UB1=601318369&LIC=PSFMEI*090NZ&SAW= 1/2/2019
PIPING GE\
ERAL NOTES
LE
\_DS
1. BEFORE COMMENCEMENT OF WORK THE CONTRACTOR SHALL VERIFY THE
EXACT LOCATION, ELEVATIONS AND CHARACTERISTICS OF ALL UTILITIES
AND PIPING AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT OR ANY
DISCREPANCIES.
2. EXACT LOCATIONS AND MOUNTING HEIGHT OF PIPING SHALL
BE OBTAINED FROM DRAWINGS FOR ANY OTHER DATA, CONTACT OWNERS..
3. ALL PIPING SHALL BE INSTALLED SO AS TO AVOID INTERFERENCE
WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL
FRAMINGS.
4. ALL WORKS SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND
UNIFORM PLUMBING CODES. IN CASE OF CONFLICTS OF CODES AND
DRAWINGS AND SPECIFICATIONS, THE MOST STRINGENT SHALL PREVAIL.
5. EXTERIOR VENTS SHALL BE INSTALLED 10'-0" FROM/OR TERMINATED
3'-0" ABOVE ANY FRESH AIR INTAKES.
6. THE CONTRACTOR SHALL COORDINATE ALL ACCESS PANELS WITH
BUILDING REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING
PLAN.
7. THE CONTRACTOR SHALL MAKE ALL ARRANGEMENTS WITH UTILITY
PIPING AND INSURE THE NEW PIPING WILL NOT HINDER OTHER
APPUCATION FOR SERVICES. ROUTING OF PIPING MUST BE PREPLANNED
AND MUST BE FULLY AGREED UPON BEFORE INSTALLATION. FIELD VERIFY
BEFORE BID.
8. THE CONTRACTOR SHALL FULLY STUDY THE PLANS AND WITH THOROUGH
EVALUATION OF SITE, WILL INSURE THE JOB WILL BE INSTALLED WITHIN
BID QUOTED. CONTRACTOR WILL BE RESPONSIBLE FOR FULL AGREEMENT
AND SATISFACTION OF OWNER. INSTALLATION WILL BE COMPLETE WITH
ALL SEISMIC AMENITIES AND SUPPORTS, EVEN IF NOT DETAILED ON PLANS.
9. CONNECTIONS BETWEEN INCOMPATIBLE MATERIALS ABOVE GROUND AND
INSIDE BUILDINGS SHALL BE BE MADE WITH FULL AND COMPLETE
ISOLATION WITH NEOPRENE SHEETS.
10. CONTRACTOR SHALL COORDINATE ALL PATHWAYS, THE TYPE OF STRUCTURE,
AND MATCH THE UBRARY OF DETAILS PRODUCED. ADDITIONAL SUPPORTS CAN
BE ADDED UNDER THE ORIGINAL CONTRACT. NO AD SERVICES PERMITTED.
11. NOT USED.
12. ALL MATERIALS AND EQUIPMENT USED SHALL BE NEW AND UNUSED. THE
CONTRACTOR SHALL ONLY USE QUAUFIED LABOR FOR THE PROPER
INSTALLATION OF SUCH MATERIAL/EQUIPMENT PER APPLICABLE STANDARDS.
13.
14.
15.
16.
NOT USED.
NOT USED.
NOT USED.
NOT USED.
17. THE PLUMBER SHALL VERIFY ALL PENETRATIONS THROUGH THE BUILDING
STRUCTURES WITH OWNERS. THE PLUMBER TO SEAL ALL FIRE RATED
PIPING PENTERATIONS WITH FOAM SEALANTS OF EQUAL FIRE RATING.
18. ALL VALVES ARE TO BE LOCATED
IN PROPER AND ACCESSIBLE SPACES.
19. NOT USED.
20. CONTRACTOR IS TO SECURE THE PIPING TO THE PROPER
LOCATIONS IN THE BUILDING STRUCTURES (VERIFY WITH THE
STRUCTURE AND CORRESPONDING DETAIL)
21. PROVIDE 4" PER 100 FEET MINIMUM SLOPE UP TO CRYOVENT.
22. CONTRACTOR SHALL MAKE REASONABLE ALLOWANCE FOR VALVES, FITTINGS,
PIPING, AND SUPPORTS NOT SHOWN ON PLANS.
23. DRAWINGS ARE OF SCHEMATIC FORM AND CHANGES MAY BE
NECESSARY FOR CONVENIENCE, OBSTRUCTIONS, OR EFFICIENCY. THE
CONTRACTOR SHALL BE REQUESTED TO PROVIDE VAUD REASONS FOR ANY
CHANGES.
PLUMBING
LEGEND
SYMBOL
DESCRIPTION
41
PRESSURE RELIEF PER ELDEC STNDRD
CHECK VALVE PER ELDEC STANDARD
D I
CAPPED PIPE FOR FUTURE USE
[
FLEXIBLE PIPE
SOIL VENT
-
SOFT WATER
SW
-AIR-OR-A-
COMPRESSED AIR
A HB
HOSE BIBB
A KHB
KEYED HOSE BIBB
A RH8
RECESSED HOSE BIBB
BALL VALVE
-1><- SOV
SHUT OFF/GATE VALVE
if-
GAS COCK (VALVE)
KI
CHECK VALVE
WALL CLEAN OUT
I WCO
FCO
FLOOR CLEAN OUT
CLEAN -OUT TO GROUND
COTG
100 r.
LENGTH/ONE-FT DROP
PLUGGED OR CAPPED PIPE
L
GAS LINE
G
e OR POC
POINT OF CONNECTION
ROOF DRAIN do OVERFLOW
Di;
®
FLOOR DRAIN
'�'
FLOOR SINK
AIKX
ROOF DRAIN W/ OVERFLOW
THRU WALL
CONDENSATE DRAIN PIPE
CD
MATERIALS LEGEND
SERVICE
NITROGEN
INSIDE
OUTSIDE _
O
REMARKS/
NOTES
SECTION 4302 2S- VACUUM INSULATED PIPE
PART 1 -GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and all
provisions as mandated by Owner, Owners' represehtatwe, Standards, and rreniadurers stringent gudellnes.
B AN nodes, standard, manufactures installation are applicable.
1.02 SUMMARY
A. Perform all work required to provide and install vacuum Insulated pipe and accessories for dshib lion of liquid
nitrogen from outside tank to indoor facilities, with supplementary terns necessary for proper attribution to final
point of use including valves, Stings and vacuum ports, all amenities required for complete and functional system,
even if not detailed.
1.03 REFERENCE STANDARDS
A. The latest puttered edition of a reference stall be applicable to this Project unless identied by a specific edition
date
B. All reference amendments adopted prior to the effective date of this Contract WWI be applicable to this Project.
C All materials, installation and workmanship shell comply with the applicable requirements and standards
addressed within tie following references.
1. ANSI 1331.3 -Chemical Plant and Petroleum Refiring Piping
2 ASTM A312-Welded Pipe.
1.94 QUALITY ASSURANCE
A. Valves: Manufacturers lame and pressure rating marked on valve body.
B. Welding Materials and Procediroe: Conform to ASME Code and applicable state labor regulations.
C. Manufacturer Quakfications: Company specializing in manufacturing the products specified in this section with
minimum three years documented experience.
D. Installer Qualifications: Company specializing In performing the walk of this section with mrimum three years
documented experience.
1.05 DATA
A. Product Data: Provide data on pipe materials, pipe fittings, valves and accessories. Provide manufacturers
catalog information.
B. Record Documents: Record actual locations of valves. Mc
C. Operation and Maintenance Data:
1.06 DELIVERY, STORAGE AND HANDLING
A. Accept valves on site in shipping containers with labeling in place Inspect for damage.
B. Provide temporary end caps and closures on piping and fittings Maintain in place untl mstaSatlon.
C Protect piping systems from entry of foreign materials by temporary covers, compk4ing sections of the work and
isolating pens of completed system.
PART 2-PRODUCTS
2.01 GENERAL
A. All materials shall meet or exceed all applicable referenced standards, federal, state and local requirements, and
conform to codes and ordinances of aut hondes having jurisdiction.
2.02 VACUUM INSULATED PIPE
A. Manufactures:
1. Chart Industries, Inc.; Techntab Products, Inc.; Quality Cryogenics, Approved Equal per owners' request
B. The vacuum insulated piping system shall be composed of prefabricated sections of the static vacuum design
with a chemical getering system The sections must have bayonet end connections for assembly in the fled
without welding. The manufacturer shall have design bayonet locations and provide a piping dewing for customer
approval.
C. The Inter carrier shall be INVAR 36 with 36% nickel alloy for minimal contraction between atmospheric and
cryogenic temperatures or 304 stainless with bellows. Pipe ends shall be bayonet joints for joining spools and as
use points.. Male bayonet shall be INVAR 3&
D. The vacuum jacket shell be 304 stainless steel in accordance with the ASME Code for Unfired Pressure Vessel,
Section VIII for an internal vacuum and external atmospheric pressure with the assembly at ambient temperature.
Expansion joins shall not be necessary
• After liquid begins to flow from the farthest use point, you can lest any additional legs of the
system that may be required.
• For systems with a gas vent, make sure the gas vent is operating correctly.
4. The bulk tank valve may now be Idly opened. The use point velvets) may now be closed or left open as desired.
E Note: The cool down process involves rapid pressure changes and metal contractions. You may see or hear
evidence of these changes such as pipe vibrations and/or popping souses. As these changes subside, showy
throttle open the tank outlet valve to push liquid further Into the system
Additional Guideline%
(a) All welding shall be performed by quieted welders using approved welding procedures per ASME B31.3
(b) Welds will he exam ned in accordance with requirements of ASME B31.3- Norval Fluid Service Per
section 341.4. 1 In -Process Examination in accordance with section 344.7 may be substituted for all or
part of the radiographic examination
(c) All VP should be cormercialty cleaned for cryogenic service. Piping service shall be Oxygen cleaned
(d) All welds and the entire spool shall be leak tested with a helium mass spectrometer calibrated to a
serstvlly of tx1OE standard cc/sec.
(e) Heat shall be applied during the evacuation of the spool sections to accelerate out gassing. The
minimum temperature shell be 2e0°F. Means shall be employed on the vacuum pumping system to
prevent oil from beck streemng etc the spcol vacuum space. Spools shell be sealed off at less then 10
microns
(f) The installer shall perform a field pneumatic leak test on the completed piping system at 110% of the
design pressure per ASME B31.3
E. The vacuum annulus inner carrier shall be supported within the jacket by a support system designed to absorb
thermal loads on the Inner pipe when partially or completely lined with product minimize heat leakage, withstand
loadings 1, 2, are 3, listed below during shipping and loading 4 during and after 'retaliation.
1. Three it bad applied vertical downward
2. Three '9' load applied vertical upward
3. Two "g' load applied horizontally, longitudinally, or laterally combined with one'g' load vertically downward.
4. Mel Uniform Building Code for Zone 3 seismic requirements when inner line is filed with TritNorethylene.
F. The laminar radiation shielding inner Ilne shall De "super insulated' with a Mrirrxirn of twenty alternate Myers of
aluminum foil and cryogenic paper
Each section of the chemical getting system shall have molecular sieve and a hydrogen converter installed in
the vacuum annuls for the purpose of removing the majority of vacuum contaminants, The quantity of sorption
pumping materials required for each section shall be determined by the manufacturer.
H. Each section shall be equipped with a combination evactatior/relief valve port complete with a Hosting DV -SR
Vacuum Transducer for montoring the vacuum level without breaking into the vacuum annulus.
I. Heat shall be applied during pumping to accelerate outgassing Minimum temperature shall be 200 degrees
Fahrenheit. Sections to be sealed at less than 10 microns
J. All manufacturing shall be accomplished through the use of certified welders. Testing of welds lnclldes leek -
testing with helium nets spectrometer calibrated to a sensitivity of 1 x 10.9 standard colseoord. A two-day
vacuum retention test to verify leak testing and seal off.
K. Three fool and six loot flexible vacuum jacketed sections to offset horizontally around walls.
L. All ngld end flexile piping shall be rated for 150 peg maximum.
M. All points of tee drops shell be provided with internal traps.
203 VALVES
A. Valves shall be provided for point of use isolation. Each valve shall be WI vacuum insulated extended stem valve.
Valve shall accormhodate operating temperatures between -320 degrees to +165 degrees a a maximum operating
pressure a 600 PSI CWP.
204 CRYOVENTS
A. Heated cryovertts shall be provided at the end of each main and at other locations as recommended by the
manufacturer.
205 FILL STATION
A Manufacturer Shall provide one le station assembly with manually actuated dead -man switch solenoid valve
controlled dispensingsystem whereitr rewired in protect drawings
2.06 FITTINGS
A. Each point of use outlet stall be provided with male connector to receive freezer hose. Intermediate piping and
fittings ghat be stainless (304). Each drop may serve from one to four freezers
PART 3 - EXECUTION
3.01 PREPARATION
A. Visually inspect all components for damage prior to installation. If deep dents are noted, do rot install pipe.
Contact manufacturer for aeeieMnce.
B. Clean bayonet couplings and 0-ring using clean lint tree cloth and solvent approved by the manufacturer.
C. Read vacwm on each section ofpipe, usingHastingsVacuum Gauge. Rep
ort any vacuum pipe reeding higher
than 35 microns.
3.02 INSTALLATION
A. Installation shall meet or exceed all applicable federal, state and local requirements, referenced standards and
conform to codes and ordirences of authorities having jurisdiction
B. Installation shall be in accordance with manufacturer's published recommendations.
G Provide non -conducting dielectric connections wherever joining dissimilar metals.
D Rost piping in orderly manner and maintain gradient.
E. Install piping to conserve boding space.
F. Group piping whenever practical at cannon elevations
G. Install piping to allow for expansion and contraction without stressing pipe, lints, or connected equipment
H. Provide clearance for access to vanes and fittings.
I Refer to manufacturer's Installation instructions for complete installation
J Slope shall be 1" per 50' span for gas bubbles to naturally nse up to cryovent
K Flexible pipe minimum bend radius per inner flex size: 1' inner pipe with 16" bend radius, 1 W inner pipe with 20'
bend radius, 2' inner pipe with 20' bend radius.
L All torque values for tightening nuts shall be per manufacturers' values
M. All Bayonet piping sizes and installations must be per manufacturer's guideli nes
N All pipes in axial direction must be Bose to allow slight pipe m overrents. Every 5" support must be a roller.
O. Trap End: Skgle &op use points require trap end.
P All safety bulletins from all manufacturersto be followed are the installers must have Installed this system with ten
years of experience with manufacturer's training programs.
3.03 APPLICATION
A Install hangers and supports at intervals of 6 to B feet and all large in direction poins Use split damp hanger
type supports with appropriate isolation. Piping shall not be able to sway. Refer to specification 20 05 29 Supports
and Sleeves.
B Point of use drops shall be attached to architectural pipe column or attached to wall with strut charnel. Coordinete
spacing requirements of electrical raceway.
3.04 TESTING - DRY NITROGEN
A. Alter installation of all conponerits, the installer shall pressurize the entire system with dry nitrogen gas to
maximize operating pressure. Presetre stall not exceed 1.25 times vacuum insulated pressure rating. There should
be no pressure decrease in a four host period. If the pressure drops in a four hour period, bubble test entire system,
darting at supply tank until the leaks located and repaired. Repeat until the pressure told test is successful.
3.04 TESTING - LIQUID NITROGEN
A. Alter dry nitrogen lest the manufacturer shall introduce liquid nitrogen into the piping system from a supply tank.
The closest point of use valve shall be opened first, unit liquid nitrogen begins to issue. Repeat sequence for all
points of use through to far point.
B. The system shall be visually inspected for condernsatkxh on vacuum insulated pipe. The manufacturer shall make
adjustr ants as needed to ehmirate abnormal frost formation or condensation
C It is recommended that connection of the system to a liquid cryogen bulk tank or supply be performed by
customer's liquid cryogen supplier. Starting Up a Cryogenic System When inklating flow into a VJP system it is
necessary to gradually cool down the pipe from ambient temperature to cryogenic temperature.
D. Procedure: Note: If Field Joints are installed, the Owner or the Owner's Representative may specify Inspection
requirements. Be sure to verify Inspections are complete prior to proceeding.
1. Visually ireped the VJP system to ensure all connections are joined and the installation meets the
requirererts listed previously. This includes but is not limited to:
• ❑ All bayonet clamps are installed and tightened.
• 0 Piping clamps and hangers are correctly installed and tightened
• 0 Safely relief valves have been installed and are in the proper locations. Verify liquid can not
be trapped anywhere in the system.
2. Next charge the system with cryogen to look for leaks:
• ❑ Make sure the use point valves and valves in portions you do not want to test are closed.
You will need to remove any valve lookout devices before opening.
• D Slowly crack open the cryogen supply valve on the bulk storage tank and allow the
pressure to equalize between the system and the tank. Note On systems with a gas vent the
pressure will not equalize until the line is full
• L' Inspect the system once the bulk tank valve has been cracked open
3.Orbe the system has been pressurized, cool down the system and check for system operation.
• On systems with a gas vent, gas will expel from the vent unfit system is cooled.
• Go to the farthest end point open the use point valve, and let the system fill up with cryogen
to cool the system down.
• Continue to watch for leaks, which can indicate an assembly problem, and frost on insulated
connectors that could indicate an MpropeM assembled o-ring.
.d' dUF'anZv'' I:'t
Jrcmar.ce
l cn5 s
Date
REVISIONS
=cope
Dian r
SEPARATE PERMIT
REQUIRED FOR:
Ly Mechanical
mr Electrical
Plumbing
MU Gas Piping
City of Tukwila
BUILDING DIVISION
EXPiREl
JAM 01 2020
VJ
PIPE
FRONT
WALL MOUNT -ANGLE BRACKET
ANGLE
BRACKET
WALL
STRUT
CUSHION
CLAMP
UNISTRUT
ANGLE
BRACKET
TOP SIDE
SCALE: 1' =
WALL
VJ
PIPE
WALL MOUNT - SURFACE
StRfr
C U5IION
CLAMP
FRONT
SCALE'. 1' = I' -a
SIDE
WALL
FLOOR MOUNT - SURFACE
VJ PIPE
UNISTRUT
CONCRETE
ANCHORS B POST
BASE
SIDE
SCALE: 1' = 1'-m
END
CEILING
CEILING MOUNT- Be5 FLEXIBLE
ALL -THREAD --
t
SS HOSE CLAMP
6' OC
SIDE END
CELNG
CEILING MOUNT - R50 RIGID
CEILING
---
ALL -THREAD
VJ PIPE
SIDE
END
CEILING
REVVElieLD 3iZ
CODE COMPLIANCE
APPROVED
DEC 13 2018
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
DEC 1 4 2018
PERMiT CENTER
CLIENT
U.S. CRYOGENICS, INC
12609 NE 95th Street
Unit B-101 Vancouver,
Washington 98682
>-
g J
0
a°
U.
O J
O 0
< 0
-I W
I.
co
zQ
THESE PLANS WERE DEVELOPED RESTRICTNELY
FOR USE ON THE STRUCTURES AND BY PERSONS/
COMPANY AS SPECIFIED IN THE TRLE BLOCK.
ANY OTHER USE (INCLUDING, BUT NOT UMfaED
TO, DISSEMINATION AND COPYING) OF THESE
PLANS AND ANY PORTION THEREOF, AS WELL
AS ANY USE OF THE PLANS BY ANY PARTY OR
PARTIES OTHER THAN THE ONES SPECIFIED IN
THE TITLE BLOCK. ARE STRICTLY PROHIBITED
UNLESS UNDER A WRITTEN PERMISSION BY SGE.
KHOSROW 11SAUMrt
NOURMOHAMMADI
2515 BAMBOO
Newport Beach, CA 92660
Tel.(949) 852-8700 ' Fox (949) 852-1918
--t-2tre
ts
Ise LS,
vi; S3677
0.
b'CrectNAL. tie
[EXPIRES
JOB No. 181438
PLUMIBNG SHEET-R
REV
DATE
REVISIONS
DESCRIPTION
BY
P'd
DATE: DECEMBER 5, 2018
DESIGNED BY
RA
APPROVED BY
KN
GENERAL
NOTES,
DETAILS
SCALE. 1-=
SCALE- f1'4*
P1.0
ter r c.
0 o 0 ��Ian 1 0 0 0 0
(7)
_T EXPI'.' D
JAN O 1 ZOZB
ovn
DEC 1 '.': 232
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
DEC I42018
PERMIT CENTER
PROPRIETARY AND CONFIDENTIAL THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF US CRYOGENICS.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT "HE WRITTEN PERMISSION OF US CRYOGENICS IS PROHIBITED.
S
0
LL
I
CLIENT
U.S. CRYOGENICS, INC
12609 NE 95th Street
Unit B-101 Vancouver,
Washington 98682
2a
> N
0
Z W
0 o-
J 0
uj
Z
3215 S. 116TH STREET TUKWILA, WA 98168
THESE PLANS WERE DEVELOPED RESTRICTIVELY
FOR USE ON THE STRUCTURES AND BY PERSONS/
COMPANY AS SPECIFIED IN THE TITLE BLOCK.
ANY OTHER USE TO. DISSEMINATION AND INCLUDICOPYYIING OF NOT TREESE
PLANS AND ANY PORTION THEREOF, AS WELL
AS ANY USE OF THE PLANS BY ANY PARTY OR
PARTIES OTHER THAN THE ONES SPECIFIED IN
THE TITLE BLOCK, ARE STRICTLY PROHIBITED
UNLESS UNDER A WRITTEN PERMISSION BY SCE.
REV
KHOSROW "SAUM"
NOURMOHAMMADI
2515 BAMBOO
Newport Beach, CA 92660
Tel(949) 852-8700 ' Fax (949) 852-1918
DATE
JOB No. 181438
PLUMIBNG SHEET-R
REVISIONS
DESCRIPTION
DATE: DECEMBER 5, 2018
DESIGNED BY
RA
APPROVED BY KN
PLUMBING
PLAN
P2.0
(A)
CLIENT
U.S. CRYOGENICS, INC
HEATER H
WAL
63'-3"
DROP CEILING
(USING
r CRYOVENT
VENT LINE 1/2" IPS VJ PIPE 6 1/2"
111-6 1/2"
`
_
(PIPE SLOPE NOT REQUIRED)
r
8 1/4 js
6'
7-6• SLOPE PIPE UP 1" IPS VJ SUPPLY PIPE
7,
BOX
-
6" PER 100 FEET
ki
\ \
=
\
9��
4;
IPS VJ PIPE
o
/2" VJ
NAL�As�
�/2"
kr
co
zn
9
L
LIQUID NITROGEN (LN2) CRYOGENIC STORAGE
STORAGE TANKS BY OTHERS FREEZER BY OTHERS
1
3
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
1
DROP CEILING
6'-0 1/4"
r
CRYOVENT
ID
1
..
r..
( ,
"
LIQUID NITROGEN (LN2)
CRYOGENIC STORAGE STORAGE TANKS BY OTHERS
FREEZER BY OTHERS
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
6'-6 1/2'' 11'-2"
r r
PNEUMATIC
SAFETv
6'-0" D (2) PLCS
r
VALVE
RELIEF VALVE
N
I
r
kr
\
\
CO
5 7'
5'-7"
1-1/4'
ID FLEX i1/44
M
1
1'�`—
_
JF
I
11-2"
\
o
-
`s
1 •• 1
l�
I 1 J I Y- I
\,
ELEVATION VIEW
LIQUID NITROGEN (LN2)
STORAGE TANKS BY OTHERS
SCALE: 1/4" = 1'-0"
L 1
L0
VENT HEATER
0 —�
WALL
BOXES
T
ELEVATION VIEW
EXPIRED
JAIL 0 a. 2020
PGl8eoH7
CODE CC:,';'L A E
APPROVED
DEC 1?2018
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
DEC 142018
PEi-trMTl f CENTER
12609 NE 95th Street
Unit B-101 Vancouver,
Washington 98682
LOCATION
3215 S. 116TH STREET TUKWILA, WA 98168
THESE PLANS WERE DEVELOPED RESTRICTIVELY
FOR USE ON THE STRUCTURES AND BY PERSONS/
COMPANY AS SPECIFIED IN THE TITLE BLOCK.
ANY OTHER USE (INCLUDING. BUT NOT UNITED
TO, DISSEMINATION AND COPYING) OF THESE
PLANS AND ANY PORTION THEREOF, AS WELL
AS ANY USE OF THE PLANS BY ANY PARTY OR
PARTIES OTHER THAN THE ONES SPECIFIED IN
THE TITLE BLOCK. ARE STRICTLY PROHIBITED
UNLESS UNDER A WRITTEN PERMISSION BY SOE.
KHOSROW "SAUM"
NOURMOHAMMADI
2515 BAMBOO
Newport Beach, CA 92660
Tel.(949) 852-8700 $ Fax (949) 852-1918
JOB No. 18143E
PLUMIBNG SHEET-R
REVISIONS
REV
DATE
DESCRIPTION
DATE: DECEMBER 5, 2018
DESIGNED BY
RA
APPROVED BY
KN
ELEVATIONS
PROPRIETARY AND CONFIDENTIAL THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF US CRYOGENICS.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF US CRYOGENICS IS PROHIBITED.
P3.0