HomeMy WebLinkAboutPermit M19-0162 - KING COUNTY HOUSING AUTHORITY - DUCTWORK, DIFFUSERS, GRILLES, CONTROL SYSTEM UPGRADE ETCKING COUNTY HOUSING
AUTHORITY
600 ANDOVER PARK W
FINALED
O5h4/2O2O
M19-0162
Parcel No:
Address:
Project Name:
City of l7n�««m«^U
Department of Community Development
69DUSmuthcenterBoulevard, Suite #1OD
Tukwila, Washington 981OQ
Phone: 206-431'3670
Inspection Request Line: 286'4B8-935U
Web site: http///m/ww.7ukmi|oVVA.Rov
MECHANICAL PERMIT
2623049123
/ KING COUNTY HOUSING AUTHORITY
Permit Number: K419'016I
Issue Date: 12/3/2019
Permit Expires On: 5/31/2020
Owner:
Contact Person:
Name:
Contractor:
License No:
Lender:
Name:
KZHOUSING AUTHORITY
5OOANDOVERPARK VV,TUKVV|LA,
VVA,9O188
/
yW|CHAEL[UADRA Phone: (206)574'1219
70OANDOVERPARK VV'SUITE [,
REGENCY NVVCONSTRUCTION INC
pOBOX 6429,BELLEVUE,WA, 980O8
REGENNO042J5
|
Expiration Date: 3/2/2820
|
DESCRIPTION OFWORK:
DEMO EXISTING DIFFUSERS/GRILLES AND ALL DUCTWORK DOWNSTREAM FROM MOST OFTHE EXISTING FAN
P0VVEREDTERK4IN, ALS. RE-ROUTE AND INSTALL NEW DUCTWORK. INSTALL NEW SUPPLY/RETURN DIFFUSERS AND
GRILLES. BALANCING DAMPERS ADDED TO NEW BRANCHES. ZONE CONTROLS RELOCATED. CONTROL SYSTEM
UPGRADED TOACCOMMODATE NEAR ZONING CONFIGURATIONS.
J
Vn|uadonofVVom� $35,00000
Type ofWork: REPLACEK8ENT
Fuel type: ELECT
Fees Collected: $683.80
Electrical Service Provided by: PUGETSOUND ENERGY
Water District: TVKVV|LA
Sewer District: TUKVV|LA
/
Current Codes adopted 6ythe City ufTukwila:
international BuUdjnQCode Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform P|umbing,Code Edition:
International Fuel Gas Code:
National Electrical Code:
VVACities Electrical Code:
VVA[296-4G8:
Code:
ermit Center Authorized Signature:
/01
| heady certify that | have read and examined this permit and know the same to betrue and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate nrcancel the provisions ofany other
state orlocal laws regulating construction orthe performance ofwork. |amauthorized 0osign and obtain this
development permit and agree 0othe conditions attached tothis permit.
Sign atu \/ Date:
Print Name: V--�l-�-C����1. co r'04-or
This permit shall become null and void if the work isnot commenced within 18Odays for the date ofissuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
4: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
S: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City nfTukwila Building Department (2O6-4]1'367O).
G: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
7: VALIDITY OFPERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances ufthe City ofTukwila shall not bevalid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
8: `MECHANICAL PERMIT CONDITIONS'
9: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (2O6/431-367O).
10: Manufacturers installation instructions shall beavailable onthe job site atthe time ofinspection.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206)438-935u
1800 MECHANICAL FINAL
0701 ROUGH -IN MECHANICAL
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.Tukwi laW A.gov
Mechanical Permit No. Vfl - ORS -
Project No.
Date Application Accepted: q ` 9 5 - tci
Date Application Expires: ? 5)-CD
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
Site Address:
Tenant Name:
King Co Assessor's Tax No.:Pio Z3041 t
600 Andover Park West, Tukwila, WA 98188
King County Housing Authority
Suite Number:
PROPERTY OWNER
Name: King County Housing Authority
Address: 700 Andover Park W
City: Tukwila State: WA
Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: Michael Cuadra
Address: 700 Andover Park W, Suite C
City: Tukwila State: WA zip: 98188
Phone: (206) 574-1219 Fax:
Email: MichaelC@kcha.org
Floor: 1st
New Tenant: ❑ Yes ®..No
MECHANICAL CONTRACTOR INFORMATION
Company Name:
Address:
City:
State:
Zip:
Phone:
Fax:
Contr Reg No.:
Exp Date:
Tukwila Business License No.:
Valuation of project (contractor's bid price): $ 7,5I
Describe the scope of work in detail:
Demo existing diffusers/grilles and all ductwork downstream from most of the existing fan powered terminals. Re-route and
install new ductwork. Install new supply/return diffusers and grilles. Balancing dampers added to new branches. Zone controls
relocated. Control system upgraded to accommodate near zoning configurations.
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement Lin
Fuel Type: Electric Qf
Gas ❑
Other:
H:\Applications\Forrrs-Applications On Line\2016 Applications\Mechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Page I of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
27
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
Noise:
Mechanical units need to be in compliance with the Tukwila Noise Code. Maximum permissible sound levels are based on from where the sound is
created and where the sound is heard. Additionally, if sound can be heard from within a house at night in a residential zone it may not be allowed.
For more details, see TMC 8.22
District of Sound
Producing Source
District of Receiving Property
Residential, Daytime*
Residential, Nighttime
Commercial
Industrial
Residential
55 dB(A)
45 dB(A)
57 d13(A)
60 dB(A)
Commercial
57 dB(A)
47 dB(A)
60 dB(A)
65 dB(A)
Industrial
60 dB(A)
50 dB(A)
65 dB(A)
70 dB(A)
*Daytime means 7AM-10PM, Monday through Friday and 8AM-1OPM, Saturday, Sunday and State -recognized holidays.
A few sounds are exempt from the noise code, including:
• Warning devices;
• Construction and property maintenance during the daytime hours (lam-lOpm);
Testing of backup generators during the day.
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 Intemational Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER O UT RIZED AGENT:
Signature: `l �— —� Date: et • 2-''f
Print Name: ,l C ra C- CL ittaA Day Telephone:%(o ' i f 2-1q
Mailing AddressiC 1 s- f X ft/Z PpP(lk (. �•.�ie_—�1l 1 � Ar �l ' I O
City State Zip
H:\Applications'Fornts-Applications On Line\2016 Applications\ Mechanical Permit Application Revised 1-4-16.docx
Revised: January 2016
bh
Page 2 of 2
DESCRIPTIONS
ACCOUNT
QUANTITY
PAID
PermitTRAK
$552.30
M19-0162 Address: 600 ANDOVER PARK W
Apn: 2623049123
$552.30
Credit Card Fee
$16.09
Credit Card Fee
R000.369.908.00.00
0.00
$16.09
MECHANICAL
$510.68
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$33.15
PERMIT FEE
R000.322.100.00.00
0.00
$477.53
TECHNOLOGY FEE
$25.53
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R19197
R000.322.900.04.00
0.00
$25.53
$552.30
Date Paid: Tuesday, December 03, 2019
Paid By: MICHAEL CUADRA
Pay Method: CREDIT CARD 085075
Printed• Ti1Pcdav_ DPcemher 03. 2019 11:46 AM 1 of 1
COTUmWIL4 ETn4KIT
8280 S0UTH[ENTEK BLVD
TUKWILA, W4 98188
286-433'1870
CITY OF TUKWILA
0817340080802374404580
Date: 12/03/2019
VISA
CARD NUMBER:
TRAN AMOUNT:
APPROVAL [Q:
RECORD #/
CLERK ID:
X
11:46:07 AM
CREDIT CARD SALE
*******+**8721 K
$s52.]0
085075
000
frankie
{CARDHOLDER'S SIGNATURE}
I AGREE TO PAY THE ABOVE TOTAL AMOUNT
ACCORDING TO THE [ARV ISSUER AGREEMENT
(MERCHANT AGREEMENT IF CREDIT VOUCHER)
Thank you!
Merchant Copy
Cash Register Receipt
City of Tukwila
Receipt Number
DESCRIPTIONS
PermitTRAK
ACCOUNT
QUANTITY
PAID
$2,585.88
D19-0309 Address: 600 ANDOVER PARK W
Apn: 2623049123
$2,454.38
Credit Card Fee
$71.49
Credit Card Fee
R000.369.908.00.00
0.00
$71.49
DEVELOPMENT
$2,382.89
PLAN CHECK FEE
I
R000.345.830.00.00
0.00
$2,382.89
M19-0162 Address: 600 ANDOVER PARK W
Apn: 2623049123
$131.50
Credit Card Fee
$3.83
Credit Card Fee
R000.369.908.00.00
0.00
$3.83
MECHANICAL
$127.67
PLAN CHECK FEE
TOTAL FEES PAID BY RECEIPT: R18663
R000.322.102.00.00
0.00
$127.67
$2,585.88
Date Paid: Wednesday, September 25, 2019
Paid By: MICHAEL CUADRA
Pay Method: CREDIT CARD 063224
Printed: Wednesday, September 25, 2019 9:34 1 of 1
AM
CRWYSTEMS
0 4
CO TUKWILA ETRAKIT
6200 SOUTHCENTER BLVD
TUKWILA, WA 98188
206-433-1870
CITY OF TUKWILA
0017340000802374464500
Date: 09/25/2019
VISA
CARD NUMBER:
TRAN AMOUNT:
APPROVAL CD:
RECORD #:
CLERK ID:
09:34:27 AM
CREDIT CARD SALE
**********8721 K
$2,585.88
063224
000
kandace
{CARDHOLDER'S SIGNATURE}
I AGREE TO PAY THE ABOVE TOTAL AMOUNT
ACCORDING TO THE CARD ISSUER AGREEMENT
(MERCHANT AGREEMENT IF CREDIT VOUCHER)
Thank you!
Merchant Copy
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
-'', ' Al — .•c,
ca! Summary MECH-SUM
2 15 WashipplitscylrEatde Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
roject Information
i OCT 0 7 2019
City of Tukwila
BUILDING DIVISION
,Project Title: KCHA Building 600
Date 1 8/2 01 9
Applicant Information. Provide contact information for individual who can respond to
nquiries about compliance form information provided.
For Building Dept. Use9i
Name: Rice Fergus Miller
ompany
.—
'Company Address: 275 5th St *100
Applicant Name: Michael Cuadra
A
Applicant Phone: (206) 574-1219
Project Description
Briefly describe demechanical systems in
the text box provid
0 Total Bldg Perforrnance (TBP)
This path includes all mandatory
provisions per C401.2 Option 2.
MECH-SUM, MECH-CHK, and C407
Energy Analysis forms required.
0 New Building 0 Building Addition 0 Tenant Improvement E System Retrofit 2 No System Changes
Demo existing diffusers/grilles and all ductwork downstream from most of the existing fan powered
terminals. Re-route and install new ductwork. Install new supply/return diffusers and grilles.
Balancing dampers added to new branches. Zone controls relocated. Control system upgraded to
accommodate near zoning configurations.
Design Load Calculations
0 Load calculation summary 0 MECH-LOAD-CALC Forrn
Provide design load calculations for all mechanical systems and equipment serving the building heating, cooling or
ventilating needs. If a load calculation summary is provided with the permit documents that includes all applicable
compliance information then the MECH-LOAD-CALC form is not required.
Mechanical Schedules
2 Mechanical Plans 0 MECH-EQ Forms (TBD)
Indicate location of equipment compliance information. If provided on plans then MECH-EQ forms are not required,
however, include on plans all applicable compliance information listed in MECH-EQ tables.
Dedicated Outdoor Air
System Requirements and
High Efficiency VAV
Alternate
D DOAS Is required per C403.6 effective July 1, 2017 (office, retail, education, library and fire station occupancies)
All occupied, conditioned areas shall be served by a DOAS that delivers required ventilation air in a manner that does
not require space conditioning fan operation. Space conditioning fans cycled off when no heating or cooling is required.
0 Ventilation provided via natural ventilation per 2015 IMC in lieu of DOAS (C403.6, Exception 1)
0 Ventilation and space conditioning provided by a HEVAV system per C403.7 in lieu of DOAS (C403.6, Exception
2)
E] DOAS included in project, although not required (occupancy not office, retail, education, library or fire station)
0 DOAS related allowances Included in project:
0 Prescriptive vertical fenestration maximum area allowance increased to 40% per C402.4.1.4 with 100% of
conditioned floor area in building served by DOAS.
0 Exception to air economizer per C403.3 Exception 1, include MECH-ECONO form.
Fan Power
0 Project includes HVAC air distribution systems that provide heating and/or cooling
If yes, provide a MECH-FANSYS -SUM form.
0 For one or more systems, the total fan motor nameplate hp of all fans in HVAC system exceeds 5hp.
If yes, provide a seperate MECH-FANSYS form for each HVAC system exceeding the 5 horsepower threshold,
Refer to Section C403.2.11 and MECH-FANSYS-DOC for requirements and exceptions.
HVAC Hydronic Systems
0 Hydronic chilled water 0 Water -loop heat pump 0 No hydronic systems
0 Hydronic heating water 0 Geothermal
C406 Additional
Efficiency Options -
Mechanical
0 C406.2 More efficient HVAC equipment and fan systems
Requires 90% of heating and cooling capacity to be equipment listed in tables C403.2.3(1)-(9) or air -to -water heat
pumps and heat recovery chillers. All equipment listed in tables C403.2.3(1)-(7) must be 15%, more efficient than
minimum requirements. All stand alone supply, return, and exhaust fans over 1hp must have FEQ 71 and must be
selected within 10% of maximum .total or static pressure.
0 C406.6 Dedicated outdoor air system (DOAS)
Requires 90% of conditioned floor area to be served by a DOAS per C403.6 that delivers required ventilation air in a
manner that does not require space conditioning fan operation.
0 C406.7 Reduced energy in service water heating
Requires 90% of floor area be in occupancy types listed in C406.7.1 and that 60% of annual hot water energy use be
provided by heat pump, 15,stperlec/temor solar water -heating systems.
CITY OF TUKWILA
SEP 2 5 2099
PERMIT CENTER
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
Mechanical Summary, pg. 2 MECH-SUM
2015 Washington State Energy Code Compliance Forrns for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Service Water Heating
Systems
Equipment Type (s)
0 Hot water heating tank(s) 0 Instantaneous El No service water systems
0 Dedicated boiler 0 Heat exchange from space heat boiler or
central hot water/steam
Distribution Type (s)
0 Circulation System 0 On -demand
Commissioning
Commissioning is required for.
0 Mechanical systems per C408.2 0 Service water heating systems per C408.4
If required, commissioning shall be performed for all applicable systems regardless of individual equipment capacity.
Exceptions to commissioning requirements:
o Total output capacity of all mechanical space conditioning systems in the building do not exceed 240,000 Btu/h
cooling or 300,000 Btu/h heating. Mechanical systems commissioning not required.
Ei Capacity of largest service water heating system in building does not exceed 200,000 Btu/h. Service water heating
systems commissioning not required.
Low Energy and Semi -Heated Spaces (Note 6 and 7)
Space
Type
Location in Plan(s)
Space(s) Served
Area Served,
square feet
Heating
Capacity, Btu/h
(Note 4)
Cooling
Capacity, Btu/h
(Note 5)
Peak Space
Conditioning
Capacity,
Btufh-sf
Compliance
Check
Notes
Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh.
Note 5 - Provide total installed, cooling capacity of system serving Low Energy space(s) in Btu/h. Not allowed for semi -heated spaces. Enter 0 if no cooling.
Note 6 - Refer to Section C402.1.1 Low Energy Building. lntalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btu/test
Note 7 - Refer to Section C402,1.1.1 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 Btu/h"sf. Only systems without
electric resistance heating and no cooling are eligible for the wall insulation exception under semi -heated.
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 1 of 7
Mechanical Permit Plans Checklist
MECH-CHK
+2015 Washington State Energy Code Com fiance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: KCHA Building 600
Date 9/18/201 9
The following Information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(yes,no.nal,
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
Equipment - Sizing, Performance and Type
na
C403.1
Exempt process equipment
Identify equipment to be used in manufacturing, industrial or commercial processes that do not
provide space conditioning; identify provisions applicable to this equipment per C403.1
exception
yes
C403.2.1
Load calculations
Provide load calculations performed per ASHRAE Std 183 or equivalent, using design
parameters per C302 and Appendix C; include load adjustments to account for energy
recovery
Separate
Document
na
C403.2.2
Equipment and system
sizing
Indicate that output capacities of heating and cooling equipment and systems are no greater
than the smallest available equipment size that exceeds the calculated loads; note exceptions
taken
yes
C403.2.3
C403.2.3.2
C403.2.13.1
HVAC equipment
performance requirements
(efficiency)
Provide equipment schedules on plans or complete MECH-EQ forms indicating type, capacity,
rated and WSEC minimum efficiencies for all heating and cooling equipment; include supply
and OSA cfms and operating hours for all air systems; identify heating and cooling equipment
that does not have a corresponding WSEC minimum efficiency (manufacturer rated)
M00.01
C405.8
C403.2.14
Electric motor efficiency
List all motors a 1/12 hp (that are not integral to a rated piece of equipment) in the mechanical
or electrical equipment schedules on plans; indicate hp, rpm, number of poles and rated
efficiency. or exception applied
For fractional hp motors (1/12 - 1 hp), indicate whether they are an electronically commutated
motor, have rated efficiency of al least 70%, or exception taken
na
C403.2.11.1
Fan power limitation
For all HVAC fan systems that provide heating and / or cooling, provide system total na e
hp in MECH-FANSYS-SUM form
For all applicable HVAC systems with total fan motor hp > 5hp, verify fan system motor hp
bhp complies with fan power limits per equations in Table C403.2.11.1(1), provide MECH-
FANSYS form for each system
.
r 1----
118
C403.2.11.2
Motor nameplate hp
For all applicable HVAC systems with total fan motor hp > 5hp, Indicate fan motors specified
are the smallest available motor hp size treater than fan bhp, note exceptions taken
na
C403.2.11.3
Fan efficiency
For all applicable HVAC systems with total fan motor hp > 5hp, identify in equipment schedule
all fans required to comply with fan efficiency grade and indicate rated FEGIst 67, or
exception taken; indicate these fans are sized so total efficiency Is within 15% of the fan
maximum total efficiency
na
C403.2.11.4
Group R occupancy exhaust
fan efficacy
For all exhaust fans < 400 cfrn in Group R occupancies, Indicate in equipment schedule the fan
flow rate and efficacy (cfm/watt), or exception taken; refer to Table C403.2.11.4 (CE-57)
na
C403.2.13
Variable flow capacity -
fans
For fan motors a 7.5 hp, indicate method of variable flow control (VSD or equival
equipment schedule, or exception taken; for equivalent method for an HVAC sys refRtEEVci
HVAC System Controls for additional requirements
'—
It WE
FOR
na
C403.2.3
Maximum air cooled chiller
capacity
For chilled water plants and buildings with > 500 tons of cooling capacity, indi
chiller capacity Is s 100 tons, or exception taken
OMPLIANCE
no
C403.4
Large capacity cooling
systems
For buildings with a 300 tons of cooling capacity, Indicate method of multi -stag r variableAPpRovicry
capacity control (VSD, multiple staged compressors, or max capacity of any s unit < 66%
of the total)
na
C403.2.3.1
Non-standard water-cooled
centrifugal chillers
For water-cooled centrifugal chillers not designed for operation at standard itions, proveCI
calculations documenting maximum full load and part load rated equipment p ance
requirements
° 7 "`1119
na
C403.2.13.1
G403.4.3.2
Centrifugal fan open -circuit
cooling towers
For open -circuit centrifugal fan cooling towers with t 1,100 gpm capacity, indi cooling
towers comply with efficiency requirements for axial fan open circuit cooling e City
,
na
C403.4.2
C403.4.2.5
Large capacity boiler
systems
For single boilers with > 500,000 Btu/h capacity, indicate multi -stage or mod '
or Tu
Ha
For boiler system (single or multiple) with > 1,000,000 Btu/h capacity, indica NG
DIvIsiON
per Table C403.4.2.5 and method (multiple single Input boilers, modulating boliers, or
combination)
na
C403.2.13
Variable flow capacity -
pumps
For pump motors a 7.5 hp, indicate method of variable flow control (VSD or equivalent method)
in equipment schedule, or exception taken; for equivalent method for a hydronic system refer
to Hydronic System Controls for additional requirements
na
C403.2.3
Gas and oll-fired forced air
fumace and unit heaters
For forced air furnaces with capacity a 225,000 Btu/h and all untt heaters, indicate In equipment
schedule Intermittent ignition or IID, flue or draft damper, and rated jacket loss
na
C403.2.4.8
Combustion heating
equipment
For combustion heating equipment with output capacity > 225,000 Btufh, indicate modulating
or staged combustion control
no
C403.2.3.3
Packaged electric heating /
cooling equipment
Verify all packaged electric equipment with > 6,000 Btu/h cooling capacity and any amount of
heating Is a heat pump; include In equipment schedules
i- V.
CEIVED
na
G403.2.12
Heating outside a building
Indicate systems providing heating In non -enclosed outdoor occupied spaces are radiant
systems; refer to HVAC System Controls for additional requirements
Cr Y
F TUKWIL/
na
C403.2.7.1
Kitchen exhaust hoods
Indicate on plans the type, duty and exhaust air rate of each kitchen hood, refer to HVAC
System Controls for additional- requirements
c'cll
2 5 2n`n
na
C403.2.4.3
Outdoor supply air, exhaust
and relief dampers
Indicate locations of OSA intake, and exhaust and relief outlet dampers on plans; indicate
whether dampers are Class 1 motorized, or gravity and exception taken (include leakage
rating, cfm/sf); refer to FIVAC System Controls for additional requirements for OSA dampers
ur
{ C„ n—IT
,.....,
prkrffR
na
C403.2.4.3
Return air dampers
Indicate locations of return air dampers that are integral to economizer operation; verify
dampers are motorized; indicate whether dampers are Class 1, or within packaged equipment
eligible for leakage reline exception (include leakage rating, cfm/sfl
na
C403.2.4.3
Stairway and shaft vent
dampers
Indicate location of stairway and shaft vent dampers on plans; verify dampers are Class 1
motorized; refer to HVAC System Controls for additional requirements
na
C403.2.4.4
Zone isolation dampers
For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that
are expected to be occupied non -simultaneously; identify isolation zone areas on plans and
locations of associated isolation dampers in HVAC distribution system; refer to HVAC System
Controls for additional requirements
na
C403.2.3.4
Humidification
For cooling systems with humidification equipment that are also required to have air
economizer, Indicate humidifier is adiabatic (direct evaporative or fog atomization), or exception
taken . 411 Allk _Aft. - —
-
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 7
Mechanical Permit Plans Checklist
MECH-CHK
*2015 Washington State Energy Code Compliance Forms for Commercial Buildings includingR2 & R3 over 3 stories and all R1
Project Title: KCHA Building 600
Date 9/18/2019
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no,na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Buiiding Department
. Notes
Additional Efficiency Package Option, More Efficient HVAC Equipment & Fan Performance -
Must comply with all 3 provisions to be eligible
na
C406.2.1
C403.2.3
HVAC system selection
To comply with additional efficiency package option, calculate the percentage of heating and
cooling equipment In the project (based on output capacity) that do not have a corresponding
WSEC listed efficiency; shall be less than 10% to comply
na
C406.2.2
C403.2.3
Minimum equipment
efficiency
To comply with additional efficiency package option, indicate that all listed heating and cooling
equipment have a rated efficiency that exceeds WSEC listed efficiency by at least 15%
\._
na
C406.2.3
C403.2.11.3
Minimum fan efficiency
To comply with additional efficiency package option, indicate rated FEG of stand alone fans is
71; indicate these fans are sized so the fan efficiency at design conditions is within 10% of the
maximum total or static efficiency
HVAC System Controls
yes
C403.2.4.1
Thermostatic controls
(thermostats and
humidistats)
Indicate locations of thermostatic and humidity control devices and the zones they serve on
Plans. including perimeter system zones
M00.01,
M21.02
Where adjacent (neighboring) zones are controlled by separate thermostats (including
perimeter systems used to offset heat gain or loss), and are connected by permanent
openings > 10% of either zone sf area, indicate controls configured to prevent adjacent zones
from operating in conflicting modes (one in heat, other in cool); applies to adjacent perimeter
zones adiacent nonoerimeter zones and adiacent Perimeter and nortnerimeter zones
na
If applying Exception 2 to nonperimeter zones adjacent to perimeter zones, Indicate that
setpoints and deadband settings in these zones are coordinated so cooling in a nonperimeter
zone does not occur until the temperature in that zone is 5°F higher than the adjacent
perimeter zone temperature in heating
na
na
C403.2.4.1.1
Heat pump supplementary
heat
Indicate staged heating operation with compression as the first stage of heating and
supplemental heating controlled with outdoor lock -out temperature set to 40°F or less
na
C403.2.4.1.2
Deadband
Indicate zone thermostatic controls configured with 5°F minimum deadband for systems that
control both heating_and cooling
na
C403.2.4.1.3
Setpoint overlap restriction
(thermostats)
If separate heating and cooling systems with separate thermostatic control devices are used to
serve a zone, indicate locations of both thermostatic control devices and the zone they serve
on dans
Indicate a limit switch, mechanical stop or DDC control with programming to prevent
simultaneous heating and cooling
na
C403.2.4.2
C403.2.4.2.1
C403.2.4.2.2
Automatic setback and
shutdown
Indicate zone thermostatic controls configured with required automatic setback and manual
override functions, setback temperatures, and control method (automatic time clock or
programmable controls); note exceptions taken
na
C403.2.4.2.3
Automatic (optimum) start
Indicate system controls that adjust equipment start time required to bring each area served up
to design temperature just prior to scheduled occupancy
na
C403.2.4.3
Outdoor supply air dampers
Indicate automatic controls configured to close OSA damper during unoccupied equipment
operation; not including economizer cooling, night flush or IMC required OSA / exhaust
roe
C403.2.4.3
Stairway and shaft vent
dampers
Indicate method of activation of stairway and shaft vent dampers (fire alarm or interruption of
power)
na
C403.2.4.4
Zone isolation controls
For systems serving areas > 25,000 sf or spanning more than one floor, that include areas that
are expected to be occupied non -simultaneously; indicate controls that allow for independent
space conditioning of isolation zones; or exception taken
na
C403.2.12
Heating outside a building
Indicate occupancy sensing or timer switch controls configured to automatically shut off heating
system when area served is unoccupied
na
C403.2.4.5
Snow melt systems
Indicate automatic controls configured to shut off system when pavement temperature
exceeds 50°F and no precipitation is falling, and when outdoor air temperature exceeds 40°F
na
C403.2.4.6
Freeze protection system
controls
Indicate automatic controls to shut off system when outdoor temperature exceeds 40°F, or
conditions protect fluid from freezing
na
C403.2.4.9
Group R1 hotel / motel
guest rooms
For hotels and motels with over 50 guest rooms, indicate automatic controls serving guest
rooms that are capable of setback (heating) and set-up (cooling) of temperature setpoint by at
least 5°F; indicate control method - activated by room entry or occupancy sensor
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 3 of 7
Mechanical Permit Plans Checklist
MECH-CHK
Revised January2017
Washinaton State EnergyCode Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1
Project Tftle: KCHA Building 600
Date 9/18/201 9
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no.na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
na
C403.2.4.10
C403.2.4.11
Group R2 / R3 dwelling
units, Group R2 sleeping
units
For primary space conditioning system, indicate 5-2 programmable thermostats capable of two
setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or
both), required temperature range and at minimum a 10°F deadband; or exception taken
na
C403.2.6
C403.2.11.4
Ventilation
Indicate method of ventilation air delivery (natural or mechanical) for each zone
If mechanically delivered, indicate that systems are configured to provide not more than 150%
of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE
62.1 or other applicable code MAC. OSHA. etc): or exception taken
If delivered via natural ventilation, identify required elements per IMC including minimum
openabte area to the outdoors or qualifying adjoining spaces
na
C403.2.6.2
Demand controlled
ventilation
Identify spaces > 500 sf with occupant load > 25 people/1,060 sf per IMC; for each space
indicate whether It Is served by an HVAC system with total design OSA > 3,000 cfm, and / or
the system has airside economizer or automatic modulating OSA damper; indicate OSA
controls are configured to provide.demand controlled ventilation or provide supporting
for applied exception
na
C403.2.6.3
Occupancy sensors
,documentation
For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based
OSA control when space is unoccupied and method (closes OSA damper or shuts -off
equipment); or alternate means provided to automatically reduce OSA when space is partially
occupied
03
C403.2.6.4
C403.2.6.4.1
Enclosed loading dock
ventilation
For enclosed loading docks, indicate ventilation / exhaust system method of activation (gas
detection system for CO and NO2, or occupancy sensors), and control method (staged or
modulating)
na
C403.2.6.4
G403.2.6.4.2
Enclosed parking garage
ventilation
For enclosed parking garages, indicate ventilation / exhaust system activated by gas detection
system for CO and NO2, and control method (staged or modulating); or exception taken
na
C403.2.7.1
Kitchen exhaust hoods
Provide calculations that show a balanced accounting of total kitchen exhaust (include all
hoods) with % of: supply air, transfer air from adjacent spaces, and make-up air, if applicable,
indicate that direct make-up air to each hood does not exceed 10% of hood exhaust
For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table
C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would
otherwise be exhausted)
na
C403.2.7.2
Laboratory exhaust systems
Refer to Systems Requiring Energy Recovery for requirements
no
C403.2.13
Variable flow capacity -
HVAC system fans
For HVAC fan motors 2 7.5 hp, indicate method of variable flow control (VSD, or equivalent
control method that reduces design air volume by 50% at 1/3 static design pressure); note
exception taken
na
C403.3.1
DX air handler variable
cooling control
(Under Integrated
Economizer)
For DX air handlers with economizer and cooling capacity t 65,000 Btu/h, indicate number of
cooling stages provided and method (multiple compressors and / or variable speed
compressors): indicate minimum displacement (capacity reduction) as % of full load
Indicate control method (cooling capacity controlled in response to space temperature, space
temperature controlled by modulating supply airflow, or both)
na
C403.2.11.5
Fan airflow control
For DX air handling units with cooling capacity t 65,000 Btu/h and evaporative and chilled
water air handling units with fan 2 0.25 hp, indicate whether system is single zone or multiple
zone and related control method (cooling capacity controlled in response to space
temoerature space temperature is controlled by modulating smell/ airflow or both)
For mechanical cooling systems (includes DX and chilled water coils) that control cooling
capacity in response to space temperature - Provide a minimum of W/0 stages of fan control;
indicate minimum fan speed is 5 66% of full speed drawing 5 40% of full speed fan power
during periods of low coolina or ventilation only
For other mechanical cooling systems (includes DX and chilled water coils) that control space
temperature by modulating airflow (in lieu of, or in addition to, controlling capacity in response
to space temperature) - Provide fan controls for modulating supply airflow; indicate minimum
fan speed Is 5 50% of full speed drawing 5 30% of full speed fan power during periods of low
cooling or ventilation only; or exception taken
na
C403.2.4.12
DDC system capabilities
Provide central and zone level DDC controls as required based on system application, capacity
or size threshold; and other Qualification per Table C403.2.4,12.1
Identify all DDC system input / output control points; Indicate capability for trending and
graphical display
Ducting Systems
yes
C403.2.8.1
C403.2.8.3
Dad construction
Indicate on plans that all ductwork is constructed and sealed per IMC
M00.01
For OSA ductWork, also indicate on plans that ductwork meets air leakage requirements per
C402.5 and vapor retarder requirements per the IBC
na
yes
C403.2.8.3
Duct pressure classifications
Identify location of low, medium and high pressure ductwork on plans
Specs
ii na
C403.2.8.3.3
High pressure duct leakage
test
Indicate high pressure duct leakage testing requirements on plans; provide test results to
jurisdiction when completed
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 4 of 7
Mechanical Permit Plans Checklist
MECH-CHK
'2015 Washington State Energy Code Compliance Forms for Commercial Buildings includingR2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: KCHA Building 600
Date 9/18/2019
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no.na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
yes
C403.2.8.1
C403.2.8.2
Duct insulation
For supply and retum ductwork located in unconditioned space or outdoors, indicate R-value of
insulation on ductwork on plans: identify climate zone: note exceptions taken
Specs
For supply ductwork located in conditioned space, identify if design supply temperature is <
55°F or > 105°F and indicate R-value of insulation on this ductwork on plans; note exception
taken
Specs
For OSA ductwork, shafts and plenums, indicate R-value of insulation on these elements on
olansjer Table C402.1.3 for steel -framed walls: note exception taken
Specs
Piping Systems
na
C403.2.9
Piping insulation
Indicate design temperature range of fluid conveyed in piping and thickness of insulation (in
inches) on hvdronic piping plans; or exception taken
ria
C403.2.9.1
Piping insulation exposed to
weather
Indicate method of protection of pipe Insulation from damage / degradation on hydronic piping
alans
Economizers
na
C403.3
Air economizer required
Identify in equipment schedules on plans or in MECH-EQ forms all cooling systems requiring
air economizer controls
Provide MECH-ECONO form indicating systems utilizing air economizer exceptions, including
those with water -side economizer in lieu of air economizer, indicate on plans eligible
exception(s) taken and measures to comply with exception(s)
na
C403.3.1
Integrated economizer
operation - air and water
Indicate air and water -side economizers are configured for partial cooling operation even
where additional mechanical cooling is required to meet the load
na
C403.3.2
Economizer heating system
impact - air and water
Verify control method of HVAC systems with economizers does not increase building heating
energy usage during normal operation
na
C403.3.3.1
Air economizer capacity
Indicate modulating OSA and retum air dampers are configured to provide up to 100% OSA for
cooling
na
C403.3.1
.3.3.
C4032
Integrated air economizer
Verify mechanical cooling controls are interlocked with air economizer controls so the outside
air damper remains in 100% open position when mechanical cooling is also required to meet
the coolino load. until the leaving air temperature is < 45°F
For systems with cooling capacity a 65,000 Btu/h, verify that control of economizer dampers is
not based only on mixed air temperature; or exception taken
na
C403.3.3.3
Air economizer high limit
controls
Indicate high limit shut-off control method and required high limit per Table C403.3.3.3
na
C403.3.4.1
Water economizer capacity
For eligible systems where water -side economizer may be provided in lieu of air economizer,
indicate system is capable of 100% design cooling capacity at 50°F db / 45°F wb OSA
temperatures
na
C403.3.4.2
Water economizer
maximum pressure drop
Indicate pressure drop across precooling coils and heat exchangers in water economizer
system do not exceedpressure drop limit
na
C403.3.1
DX air handling equipment
control
For DX air handlers with economizer and cooling capacity a 65,000 Btu/h, refer to HVAC
System Controls for requirements
na
C403.2.4.7
DX equipment economizer
fault detection and
diagnostics
For DX air handlers with economizer and cooling capacity 2 54,000 Btu/h, provide a fault
detection and diagnostics (FDD) system to monitor economizer system operation and report
faults
Systems Requiring Energy Recovery
na
C403.5.1
Energy recovery (ER) -
ventilation / exhaust
systems
For systems with design OSA > 5,000 cfm, or design supply air cfm and % OSA exceeding the
values in Tables C403.5.1(1) or (2), indicate exhaust alr ER method; or exception taken with
supoortina calculations
For rooms served by multiple systems with aggregate design OSA > 5,000 cfm, or aggregate
design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate
exhaust air ER method: or exception taken with supporting calculations
Indicate ER rated effectiveness that increases OSA enthalpy by a 50% based on delta
between OSA and retum air enthalpies at design conditions
na
C403.2.7.2
Laboratory exhaust systems
(energy recovery)
For buildings with total lab exhaust > 5,000 cfm, indicate method of energy recovery used to
•
pre -condition laboratory make-up air; ER effectiveness (min 25°F); or altemative method per
exception (VAV exhaust, semi -conditioned makeup, or CERM calculation)
na
C404.10.4
(under
C404.11)
Pools and permanent spas
exhaust systems
(energy recovery)
For buildings with pools or spas with water surface area > 200 sf, indicate exhaust air ER
method and use of waste heat (preheat ventilation air, pool water or service hot water); or
exceotion taken
Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air
temperature at design conditions by a 36°F
na
C403.5.2
Energy recovery -
steam condensate systems
For buildings with on-slte steam heating systems, indicate condensate water ER
For buildings that use off -site generated steam where condensate is not returned to the
source, indicate on -site condensate water ER
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 5 of 7
Mechanical Permit Plans Checklist
MECH-CHK
'2015 Washington State EnergyCode Compliance Forms for Commercial Buildings includingR2 & R3 over 3 stories and all R1
Revised January2017
Project Title: KCHA Building 600
Date 9/18/201 9
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no.nal
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
na
C403.5.3
Energy recovery -
cooler / freezer condensers
For buildings with food service, meat or deli departments that have a 500,000 Btu/h of remote
refrigeration capacity for coolers / freezers, indicate condenser ER and use of captured energy
(service water heating, space heating, or dehumidification reheating)
For buildings with a 40,000 sf conditioned floor area and with a 1,000,000 Btu/h of remote
refrigeration capacity for coolers / freezers, Indicate condenser ER and use of captured energy
for service water heating and also for space heating, or dehumidification reheating
na
C403.5.4
Energy recovery -
condenser systems
For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and
design service hot water load > 250,000 Btu/h, indicate condenser ER to pre -heat service
water; or exception taken. Provide calculations showing the amount of recovered heat that is
utilized (60% of oeak heatieiection load or ore -heat senAce_water to 85°F).
Hydronic System Controls
na
C403.2.13
C403.4.2.7
Variable flow control -
hydronic system pumps
For hydronic system pump motors a 7.5 hp, indicate method of variable flow control (VSD or
equivalent method that requires 2 30% design wattage at 50% design fluid flow); note
exception taken
Identify whether hydronic coils have DDC controls and associated manner of pump speed
control (differential pressure, zone hydronic demand, etc)
na
C403.2.5
C403.4.2.4
Hydronic system setback
and part load controls
For boilers that provide building heating, indicate controls that provide heating water
temperature setback based on outdoor temperature
For heating and chilled water systems a 300,000 Btu/h, indicate systems are configured to
automatically reset supply water temperature based upon demand; or exception taken.
If system DUMD motor ho 2 3 ho. also indicate controls automatically reduce flow by a 50%.
For chilled water systems (a 300,000 Btu/h, pump motor hp a 3 hp) that serve water-cooled
unitary air conditioners, indicate VSD or staged pumps in chilled water system and heat
rejection loop that reduce pump flow so that one control valve is nearly wide open, or to
maintain a minimum differential pressure; or exception taken
na
C403.4.2
Boiler sequencing
Indicate automatic controls that sequence operation of multiple boilers
na
C403.4.6
Hot gas bypass limitation
For cooling equipment with hot gas bypass, provide either multiple step unloading or
continuous capacity modulation; indicate bypass capacity per Table C403A.6
na
C403.4.2.2
Two -pipe changeover
systems
Indicate changeover deadband (min 15°F), heating / cooling mode scheduling and changeover
temperature range (limit 30°F)
na
C403.4.2.6
Chiller / boiler plant pump
isolation
Indicate controls are configured to automatically reduce overall plant flow and shut-off flow
through individual chillers and boilers when not in use
na
C403.2.13.1.1
C403.4.3.1.1
C403.4.3.1.2
Heat rejection equipment -
variable flow control
For cooling towers with fan motors a 7.5 hp, indicate VSD and method to adjust fan speed
(adjusted based on leaving fluid temperature or condenser temperature / pressure of heat
reiection device)
For multiple -cell heat rejection equipment with VSD, indicate controls that ramp all fans in
unison
na
C403.4,3.3
Heat rejection equipment -
cooling tower flow turndown
Indicate open -circuit cooling towers with multiple pumps or VSD control are designed so all
cells can be run in parallel
na
C403.4.2.3.1
Water loop heat pump -
deadband
Indicate capability of central equipment to provide minimum 20°F water supply temperature
deadband between heat rejection and heat addition modes*, or exception taken
na
C403.4.2.3.2.1
Water loop heat pump -
heat rejection equipment,
Zone 4
Indicate type of cooling tower (open- or closed-circuit) in equipment schedule; indicate method
used to limit system heat loss when heat rejection is not needed
na
C403.4.2.3.2.2
Water loop heat pump -
heat rejection equipment,
Zone 5
For open- or closed-circuit cooling towers, provide a heat exchanger that separates the cooling
tower and heat pump loop
na
C403.4.2.3.3
Water loop heat pump -
isolation valves
For hydronic heat pump systems with total system power > 10 hp, indicate 2-way isolation
valves on each heat DUMD - nd variable flow system control
Dedicated Outdoor Air Systems (DOAS) - Optional through 6/30/16, Prescriptive 7/1/2016
na
C403.6
C403.6.3
Dedicated outdoor air
systems
For buildings with office, retail, education, library and fire station spaces, identify these spaces
on plans; indicate that ventilation air in each occupied space is provided via a DOAS system;
or document compliance with C403.6.3 Impracticality; or exception taken (buildings complying
with C402.4.1.4 or C406.6 may not utilize exceptions)
na
C403.6.1
Energy recovery ventilation
with DOAS -
For all DOAS systems, indicate exhaust air ER method; or exception taken with supporting
calculations. Indicate ER rated effectiveness that increases OSA enthalpy by 2 50% based on
delta between OSA and retum air enthalpies at desian conditions.
na
C403.6.2
Heating / cooling system
controls with DOAS
Indicate equipment associated with the delivery of zone level heating and cooling (fans,
hydronic pumps, primary air dampers, etc) are configured to shut off, and central equipment is
confiaured to tum down. when there is no call for heatina or coolina in the zone they serve
If applying Exception to heating / cooling fans used for air mixing in the space during deadband
periods, include fan watts per cfm in equipment schedule
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 6 of 7
Mechanical Permit Plans Checklist
MECH-CHK
2015 Washington State EnergyCode Compliance Forms for Commercial Buildings Including R2 & R3 over 3 stories and all RI
Revised January2017
Project Title: KCHA Building 600
Date 9/18/2019
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no.na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
na
C402.4.1.4
C403.6
Increased prescriptive
maximum vertical
fenestration area with DOAS
Indicate that all occupied, conditioned spaces are served by a DOAS per C403.6
Additional Efficiency Package Option, Dedicated Outside Air Systems (DOAS)
na
C406.6
Building provided with
DOAS
To comply with additional efficiency package option, indicate that 90% or more of all occupied,
conditioned spaces are served bv a DOAS per C403.6
Multiple Zone Air Systems
na
C403.4.4
Air systems serving multiple
zones
Identify supply air systems serving multiple zones and the zones they serve on plans; indicate
whether system is VAV and method of primary air control; or provide supporting documentation
for applied exception to VAV
na
C403.4.4
VAV systems serving
multiple zones
Provide equipment schedules on plans or MECH-EQ form that list all VAV alr terminals and
tvoes
For each air terminal include: maximum airflow rates for primary supply air during zone peak
heating and zone peak cooling; maximum airflow during reheating, recooling or mixing;
minimum airflow rate to maintain required ventilation, and the basis for these values; if IMC or
ASHRAE 62.1 multiple zone equation is basis for minimum flow rates, provide calculation on
plans
na
C403.4.4.1
Single duct VAV terminal
units
Indicate single duct terminal units are configured to reduce primary supply air before reheating
or recooling
na
C403.4.4.2
Dual duct systems - terminal
units
For systems with separate warm air and cool air ducts, indicate terminal units are configured to
reduce the flow from one duct to minimum before mixing with air from the other duct
'
na
C403.4.1.1
C403.4.1.2
VAV system static
pressure sensors -
sensors and DDC set points
Indicate locations of duct static pressure sensors on plans; include at least one sensor per
maior duct branch: verify controller setpoint pressure at each sensor is 5 1.2 inch w.a.
For systems with zone level DDC, indicate controls are configured to monitor zone damper
positions and reset static pressure setpoint based on the zone requiring most pressure; include
control logic that automatically detects and generates an alarm If any zone excessively drives
reset logic. and allows building operators to exclude zones from reset JOCliC
na
C403.4.4.3
Multiple -zone VAV system
ventilation optimization
controls
For systems with zone level DDC controls, indicate controls are configured to automatically
reduce outdoor airflow in response to changes in system ventilation efficiency; or exception
taken
na
C403.4.4.4
VAV system supply air reset
Indicate controls automatically reset supply air temperature in response to building loads or
outdoor air temperature; or exception taken
Multiple Zone HVAC Systems, High Efficiency VAV - Required for systems utilizing C403.6 DOAS Exception 2, must comply with all 16 provisions
na
C403.7,
Item 1
Air economizer •
Indicate system is configured for 100% air economizer operation and complies with all related
economizer requirements per C403.3 (without economizer exceptions)
na
C403.7,
Item 2
Direct digital controls (DDC)
Provide DDC controls for all components of system; identify all DDC system input / output
control points; indicate capability for trending and graphical display
na
C403.7,
Item 3
Outdoor airflow
measurement and reduction
For systems with minimum OSA > 2,500 cfrn, indicate outdoor airflow monitoring station that
measures OSA intake under all load conditions; indicate control sequence that increases or
reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency (per
C403.4.4.3 without exceptions) or DCV (per C403.2.6.2)
na
C403.7,
Item 4
Supply airflow measurement
For systems with minimum OSA > 2,500 cfm, indicate supply airflow monitoring station capable
of measuring_supply air delivered to VAV terminals under all load conditions
na
C403.7,
Item 5
Zone isolation and
maximum area served
Verify maximum area served by a single HEVAV system is 5 50,000 sf, or one entire floor,
whichever is greater, in addition if a system serves > 25,000 sf, that includes areas that are
expected to be occupied non -simultaneously, indicate zone isolation controls per C403.2.4.4
na
C403.7,
Item 6
Interior / exterior zone
design supply air
temperature
Verify that VAV terminals serving interior cooling driven loads are sized per design supply air
temperature that is 5°F higher than VAV terminals serving exterior zones
na
C403.7,
Item 7
Maximum air terminal inlet
velocity
Identify air terminals with minimum primary airflow setpoints > 50% of maximum setpoint In
equipment schedule or MECH-EQ form; indicate air terminal inlet velocity does not exceed 900
fpm
na
C403.7,
Item 8
Sequence of operation
Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC
36
na
C403.7,
Item 9
Maximum allowable system
brake horsepower
Verify fan system bhp is 5 90% of the bhp limit per Option 2 equation in Table C403.2.11.1(1),
provide MECH-FANSYS forrn for each system
na
C403.7,
Item 10
Fan -powered terminal unit
motor and control
Indicate all series and parallel terminal fans have electronically commutated motors; indicate
DDC control system is configured to vary air terminal fan speed as a function of the load;
indicate fan speed during periods of low heating, low cooling, or ventilation only is 5 66% of
peak design air flow or provide supporting documentation for applied exception
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 7 of 7
Mechanical Permit Plans Checklist
MECH-CHK
• 2015 Washington State EnergyEnorgyCodo Compliance Forrns for Commercial Buildings includingR2 & R3 over 3 stories and all R1
Revised January 2017
Project Title: KCHA Building 600
Date 9/18/2019
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
(ves.no.na)
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Documents
Building Department
Notes
na
C403.7,
Item 11
Application of single duct
and fan -powered terminal
units
Indicate VAV terminal types on plans; verify fan -powered terminal units only serve perimeter
zones with envelope loads; verify all other zones are served by single duct terminal units
na
C403.7,
Item 12
Fan -powered terminal unit
primary air reset
Indicate DDC controls are configured to automatically reset the primary supply air cfm setpoirit
of all fan -powered terminal units to the minimum required to maintain ventilation during
occupied heating or deadband, based upon the VAV air handling unit OSA ventilation fraction
•
,
na
C403.7,
Item 13
High occupancy space
controls
For spaces > 150 sf with occupant density 2 25 people / 1000 sf, indicate space is served by a
dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint; also
indicate occupancy sensor control that automatically reduces minimum ventilation to zero and
sets back room heating and cooling setpoints by 2 5°F
na
C403.7,
Item 14
.
Dedicated HVAC systems
For server, electronic equipment, telecom or similar spaces with cooling loads > 5 W/sf,
indicate spaces are served by independent HVAC systems that are separate from HPVAV
systems serving rest of building; indicate dedicated HVAC systems have air economizer
controls or energy recovery per C403.3 Exception 9
na
C403'7'
Item 15
Central plant efficiency
Indicate whether systems are served by a high efficiency heating water plant, or a high
efficiency chilled water plant
If complying via high efficiency heating water plant Indicate all VAV terminals have hydronic
heating coils served by heating water system with either gas -fired boiler(s) with thermal
efficiency k 90%, air -to -water heat DUMPS. or heat recovery chillers
If complying via high efficiency chilled water plant: Indicate all VAV air handlers have cooling
coils served by chillers with rated IPLV efficiency that exceeds WSEC listed IPLV by at least
25% per Table C403.2.3(7) (note water-cooled IPLV is max, all others are min); indicate
smallest chiller or compressor in plant is s 20% of total plant capacity, or provide thermal
storage sized for s 20% of total plant capacity
na
C403.7,
Item 16
Fault detection and
diagnostics
Indicate DDC system includes a fault detection and diagnostics (FDD) system configured to
monitor operation and provide fault reporting of required parameters for all VAV air handlers
and VAV air terminal units in thei-IPVAV system
HVAC Equipment Energy Use Metering
na
C409.3.1
HVAC equipment energy
use metering
For new buildings > 50,000 sf and building additions > 25,000 sf, verify energy use metering of
all equipment used to provide space heating and cooling, dehumidification and ventilation will
_be Provided Der C409:indicate eauioment eligible for exception
Documentation and System Specific Requirement To Support Commissioning
yes
C408.2
Scope of mechanical
systems commissioning
Indicate that all mechanical systems, equipment, and controls for which the WSEC requires
control functions and / or configuration to perform specific functions are required to be
commissioned:
M00.01
For buildings with 2 240,000 Btu/h total output cooling capacity or 2 300,000 Btu/h total output
heating capacity, indicate that all mechanical systems regardless of individual capacity are
required to be commissioned; or provide building heating / cooling capacity calculation
demonstrating eligibility for exception
na
yes
C403.2.10
C408.1.1
C408.1.2
C408.1.4.2
C103.6
Commissioning
requirements in construction
documents
.prior
Indicate in plans and specifications that Cx per C408 is required for all applicable mechanical
systems:
M00.01
Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2
including: narrative description of activities, responsibilities of the Cx team, schedule of
activities including verification of project close out documentation per C103.6, and conflict of
interest Dlan (if reauiredl:
M00.01
Include in general summary that a Cx project report or Compliance Checklist (Figure
C408.1.4.2) shall be completed by the Certified Cx Professional and provided to the owner
to the final mechanical inspection.
M00.01
yes
C408.2.2
Air system and hydronic
system balancing
Indicate in plans that air and fluid flow rates shall be tested and balanced within the tolerances
defined in the specifications; indicate systems shall be balanced in a manner to first minimize
throttling losses, then adiusted to meet design flow conditions
M00.01,
Specs
yes
C408.2.2.1
Air system balancing
devices
Indicate devices that provide the capability to balance all supply air outlets, zone terminals and
air handling equipment requiring system balancing
MU0.01,
Specs
na
C408.2.2.2
Hydronic system balancing
devices ,
Indicate devices that provide the capability to isolate, balance and measure flow across all
hydronic equipment requiring system balancing including heating and cooling coils and pumps
na
yes
C408.2.3
Functional performance
testing criteria
Identify in plans and specifications the intended operation of all equipment and controls during
all modes of operation, including interfacing between new and existing -to -remain systems
mOu.ui,
Specs
Project Close Out Documentation
yes
C103.6
Documentation and project
close out submittal
requirements
Indicate in plans that project close out documentation and training of building operations
personnel is required for all mechanical components, equipment and systems govemed by this
code; indicate close out documentation shall include: record documents, O&M manuals,
applicable WSEC compliance forms and calculations
M00.01
" .ERMIT COO r) COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M19-0162
DATE: 09/25/2019
PROJECT NAME: KING COUNTY HOUSING AUTHORITY
SITE ADDRESS: 600 ANDOVER PARK W
X Original Plan Submittal Revision # before Permit Issued
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS:
AttAki, 441
Building Division s
Public Works
hl\A
Fire Prevention
Structural
Planning Division
r
Permit Coordinator II
PRELIMINARY REVIEW:
Not Applicable
(no approval/review required)
DATE: 09/26/19
Structural Review Required
REVIEWER'S INITIALS: DATE:
n
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
(corrections entered in Reviews
DUE DATE: 10/24/2019
Approved with Conditions n
Denied
(ie: Zoning Issues
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg 0 Fire 0 Ping 0 PW
Staff initials:
12/18/2013
Wa+.t:i��GLr ii.,,IFl�.iitnw ,t n,
9 Labor & Industries (httos://ini.wa.gov)
(0)
rttractors
REGENCY NW CONSTRUCTION INC
Owner or tradesperson
Principals
FOOTE, BRIAN LEE, PRESIDENT
Doing business as
REGENCY NW CONSTRUCTION INC
WA UBI No.
601 696 917
PO BOX 6429
BELLEVUE, WA 98008
425-883-1301
KING County
Business type
Corporation
Governing persons
BRIAN
L
FOOTE
BRIAN FOOTE;
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active
Meets current requirements.
License specialties
GENERAL
License no.
REGENNC041J5
Effective — expiration
04/25/1996-- 03/02/2020
Bond
. North American Spec Ins Co
Bond account no.
2281442
Received by L&I
01/24/2019
$12,000.00
Effective date
02/20/2019
Expiration date
Until Canceled
Ohio Cas Ins Co $12,000.00
Bond account no.
023031132
Received by L&I Effective date
01/12/2016 02/20/2016
Expiration date
Until Canceled
Bond history
Insurance
Underwriters at Lloyds $1,000,000.00
Policy no.
WCISCGL000298801
Received by L&I Effective date
02/20/2019 02/20/2019
Expiration date
02/19/2020
Insurance history
MECHANICAL SYSTEMS
COMMISSIONING NOTES
1. IN ACCORDANCE WITH THE 2015 SEATTLE ENERGY CODE (SEC) SECTION
C408 BUILDING COMMISSIONING SHALL BE COMPLETED FOR MECHANICAL
SYSTEMS- (C403), SERVICE WATER HEATING SYSTEMS (C404),
CONTROLLED RECEPTACLES AND LIGHTING SYSTEMS (C405), ENERGY
METERING (C409), AND REFRIGERATION (C410).
a. *EXCEPTION (C408.2) MECHANICAL SYSTEMS ARE EXEMPT FROM
COMMISSIONING PROCESS WHERE THE BUILDING'S TOTAL
MECHANICAL EQUIPMENT CAPACITY IS LESS THAN 240,000 BTU/H
COOLING CAPACITY AND LESS THAN 300,000 BTU/H HEATING
CAPACITY
b. CONTRACTORS ARE REQUIRED TO PERFORM PRE -FUNCTIONAL
PERFORMANCE TESTING OF ALL EQUIPMENT PRIOR TO
FUNCTIONAL PERFORMANCE TESTING BY THE COMMISSIONING
AGENT (C408.2.3). CONTRACTORS SHALL PROVIDE THE NECESSARY
ASSISTANCE TO THE COMMISSIONING AGENT TO PERFORM
COMMISSIONING DUTIES. CONTRACTORS SHALL BE RESPONSIBLE
FOR TAKING CORRECTIVE ACTION IF ANY DEFICIENCIES ARE
FOUND DURING COMMISSIONING.
2. THE BUILDING COMMISSIONING PROCESS DELIVERABLES ARE AS
FOLLOWS:
a. COMMISSIONING PLAN (C408.1.2) SHALL BE DEVELOPED BY THE
PROJECT'S CERTIFIED COMMISSIONING PROFESSIONAL AND
INCLUDED WITH THE CONSTRUCTION DOCUMENTS
b. TESTING AND BALANCING (C408.22) ALL HVAC SYSTEMS SHALL
BE BALANCED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH
GENERALLY ACCEPTED ENGINEERING STANDARDS AND
SPECIFICATIONS PRIOR TO COMMISSIONING.
c. FINAL COMMISSIONING REPORT (C408.1.3) A FINAL
COMMISSIONING REPORT SHALL BE COMPLETED AND CERTIFIED
BY THE CERTIFIED COMMISSIONING PROFESSIONAL AND
DELIVERED TO THE BUILDING OWNER OR OWNER'S AUTHORIZED
AGENT.
3. BUILDING DOCUMENTATION AND CLOSE OUT SUBMITTAL
REQUIREMENTS (Cl 03.6) OWNER TRAINING BY CONTRACTORS FOR EACH
PIECE OF EQUIPMENT OR SYSTEM SHALL INCLUDE:
a. SYSTEM/EQUIPMENT OVERVIEW (WHAT IT IS, WHAT IT DOES, AND
WHICH OTHER SYSTEMS OR EQUIPMENT DOES IT INTERFACE
WITH).
b. REVIEW OF AVAILABLE O&M MATERIALS. REVIEW OF THE
RECORD DRAWINGS ON THE SUBJECT SYSTEM/EQUIPMENT.
c. HANDS-ON DEMONSTRATION OF ALL NORMAL MAINTENANCE
PROCEDURES, NORMAL OPERATING MODES, AND ALL EMERGENCY
SHUTDOWN AND START-UP PROCEDURES.
ENERGY CODE NOTES
1. SEE MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT TYPE,
CAPACITY AND EFFICIENCY.
2. PROVIDE THERMOSTAT CONTROLS CAPABLE OF A FIVE (5) DEGREE
DEADBAND BETWEEN HEATING AND COOLING.
3. PROVIDE AUTOMATIC SETBACK CONTROLS WITH NIGHT SETBACK AND
SEVEN (7) DIFFERENT DAY TYPES.
4. PROVIDE DAMPERS FOR OUTSIDE AIR INTAKES AND EXHAUST FANS WHICH
CLOSE AUTOMATICALLY WHEN THE SYSTEM IS OFF, EXCEPT FOR THOSE
SYSTEMS WHICH OPERATE CONTINUOUSLY WITH LESS THAN 20 CFM/SF
LEAKAGE FOR BAROMETRIC DAMPERS, AND LESS THAN 10 CFM/SF LEAKAGE
FOR MOTORIZED DAMPERS.
5. PROVIDE MICROPROCESSOR -BASED THERMOSTAT FOR HEAT PUMP
CONTROLS.
6. PROVIDE A MEANS OF BALANCING EVERY AIR SUPPLY OUTLET AND AIR OR
WATER TERMINAL DEVICE.
7. SIMULTANEOUS HEATING AND COOLING IN A ZONE IS NOT PERMITTED.
8. SEAL TRANSVERSE SEAMS OF ALL DUCTWORK.
9. SEALING TO CONTROL BUILDING ENVELOPE AIR LEAKAGE AND AIR
TIGHTNESS TESTING IS REQUIRED PER 2015 SEC SECTIONS C402.5.1
THROUGH C402.5.8.
10. DUCTWORK AND PLENUMS SHALL BE THERMALLY INSULATED IN
ACCORDANCE WITH 2015 SEC SECTION C403.2.8.
11. ALL PIPING SHALL BE THERMALLY INSULATED TO MEET SPECIFICATIONS
SET IN PIPE INSULATION TABLE ON SHEET P0.01 PLUMBING SCHEDULE AND
GENERAL NOTES.
12. ALL ELECTRIC MOTORS GREATER THAN 1.0 HP SHALL MEET THE
REQUIREMENTS OF 2015 SEC SECTION C403.2.14.
13. WATER HEATING EQUIPMENT AND STORAGE TANKS SHALL MEET THE
MINIMUM REQUIREMENTS OF TABLE C404.2 OF THE 2015 SEC.
GENERAL NOTES
1. THESE PLANS ARE SCHEMATIC AND DO NOT SHOW EXACT ROUTING OR
EVERY OFFSET WHICH MAY BE REQUIRED. THE HVAC CONTRACTOR IS TO
COORDINATE WITH ALL OTHER TRADES AND IS TO VERIFY ALL CLEARANCES
BEFORE COMMENCING WORK.
2. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE
PROVISIONS OF THE LATEST EDITION OF THE WASHINGTON STATE ENERGY
CODE (WSEC), INTERNATIONAL MECHANICAL CODE (IMC) WITH
WASHINGTON STATE AMENDMENTS, INTERNATIONAL BUILDING CODE (IBC)
WITH WASHINGTON STATE AMENDMENTS, INTERNATIONAL FIRE CODE (IFC)
AND OTHER APPLICABLE STATE AND LOCAL CODES AND ORDINANCES.
3. DUCT CONSTRUCTION AND HANGINGS SHALL COMPLY WITH THE LATEST
IMC AND WITH CURRENT SMACNA STANDARDS.
4. JOINTS OF DUCT SYSTEM SHALL BE SEALED WITH DUCT MASTIC.
5. DUCTS SHALL BE INSULATED AS INDICATED ON PLANS TO MEET THE
REQUIREMENTS OF CURRENT CODES AND SPECIFICATIONS.
6. FLEXIBLE DUCTS SHALL ONLY BE USED WHERE SHOWN AND SHALL NOT
EXCEED 6 FT IN LENGTH UNLESS NOTED OTHERWISE.
7. PROVIDE EARTHQUAKE RESTRAINT FOR HVAC EQUIPMENT IN
ACCORDANCE WITH THE CURRENT IBC.
8. PIPING PENETRATIONS OF FIRE RATED WALLS OR FLOOR SHALL BE
SLEEVED AND FIRE STOPPED WITH LISTED MATERIALS SO AS TO MAINTAIN
THE INTEGRITY AND RATING OF THE FLOOR OR WALL.
9. HVAC EQUIPMENT, VALVES, AND DAMPERS SHALL BE LOCATED IN EASILY
ACCESSIBLE LOCATIONS, UNLESS SHOWN ON ARCHITECTURAL DRAWINGS.
REQUIRED ACCESS PANELS SHALL BE PROVIDED BY THE HVAC
CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR.
10. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF EXPOSED
DUCTWORK AND GRILLES.
11. ALL DUCT DIMENSIONS INDICATE FREE AREA. BOUND LINING AND
EXTERIOR INSULATION ARE LABELED AS SUCH.
MECHANICAL LEGEND
SYMBOL DESCRIPTION
SECTION/ELEVATION VIEW
DETAIL VIEW
EQUIPMENT TAG
OSHEET NOTE TAG
iQ REVISION TAG
I SIZE DIFFUSER/GRILLE TAG
FLOW
RECTANGULAR FREE AREA DUCT
DIMENSIONS (S" WIDTH x 10" DEPTH)
ROUND DUCT FREE AREA
DIMENSIONS (6" DIAMETER)
FLEX DUCT
� AIR DIRECTION
SUPPLY DUCT IN/OUT OF PAGE
O EXHAUST/RETURN DUCT IN/OUT OF PAGE
THERMOSTAT
(CO2) CO2SENSOR
u
> ENVELOPE PENETRATION
PUMP
SUPPLY/EXHAUST FAN
PRESSURE GAGE
O TEMPERATURE GAGE
TURNING VANES
KCHA Building 600 is undergoing an interior renovation on the northern half of the first floor. VAV
boxes currently installed in the space will remain in place and the ductwork will be re-routed as
necessary to supply the new office layout with heating/cooling and ventilation. All new diffusers and
grilles shall be coordinated with the Architect. Ductwork is to be added and/or replaced when
necessary. Balancing dampers are to be added to all diffuser/grille branches. Zone control
sensors relocated as shown. Control system shall be upgraded to accomodate new zoning
configurations.
GENERAL NOTES
Drawings show general routing and are schematic in nature
Include at least one elbow on all branches connecting to supply/retum diffusers in offices to
reduce cross -talk
Supply diffusers to be located centrally in space
All information collected for "Existing" drawing including equipment locations and ductwork routing
were collected with a closed ceiling. All information to be verified in field.
Diffuser type to be coordinated with Architect
Include balancing dampers on all branches
1" soundlining to be included on all trunk ductwork downstream of VAV
Include R-S insulation on all branch duct supplies to diffusers
DEMOLITION
Demo all ductwork downstream of VAV units: 1-7, 1-8, 1-9, 1-10, 1.12
Demo all return ductwork serving zones supplied by VAV units: 1.7 and 1.12
Demo all supply/return diffusers and grilles
MECHANICAL SUMMARY ROOM -BY -ROOM
- Work Room 100 - New addition - Add new supply/return diffuser, add new ductwork between
diffuser and VAV 1 -9
- File Storage 101 - New addition - Add new supply/return diffuser, add new ductwork between
diffuser and VAV 1-9
- Office 102 - New addition - Add new supply/return diffuser, add new ductwork between diffuser
and VAV 1-8
- Open Office 103:
- Workstations on west side - Add 2 new supply diffusers, add new ductwork
between diffuser and VAV 1-8
- Central workstations - Add 2 new supply diffusers, add new ductwork between
diffusers and VAV 1-10
- Office 104 - Supply diffuser replaced and moved to central location. Remain connected to VAV
1-13. Install new return grille. Add ductwork as need.
- Office 105 - Supply diffuser replaced and moved to central location. Remain connected to VAV
1-13. Install new return grille. Add ductwork as needed.
- Office 106 - Supply diffuser replaced and moved to central location. Remain connected to VAV
1-11. Install new return grille. Add ductwork as needed.
- Office 107 - Supply diffuser replaced and moved to central location. Remain connected to VAV
1-11. Install new return grille. Add ductwork as needed.
- Office 108 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-7
Office 109 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-7
Office 110 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-7
Office 111 - Add new supply/retum diffuser, add new ductwork between diffuser and VAV 1-7
Office 112 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-7
Office 113 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-12
Office 114 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1-12
Open Office 115 - Add 2 new supply diffusers, add new ductwork between diffuser and VAV 1-12
Storage 116 -Add new supply diffuser, add new ductwork between diffuser and VAV 1-12.
Undercut door 3/4"
-Break Room 118 -Add new supply diffuser in central location. Remain connected to VAV 1-15.
Add ductwork as needed.
Office 119 - Add new supply/return diffuser, add new ductwork between diffuser and VAV 1 -11
Office 120 - Add new supply/retum diffuser, add new ductwork between diffuser and VAV 1-14
Office 121 - Add new supply diffuser, add new ductwork between diffuser and VAV 1-13.
Undercut door 3/4"
CONTROLS SUMMARY
Create/change GUI on controls computerto reflect new zones shown on M0.01
Thermostats:
VAV 1-7 - Keep thermostat in same area
VAV 1 -8 - Move thermostat to south wall of workstations
VAV 1 -9 - Move thermostat to Work Room 100
VAV 1.10 - Move thermostat to north wall in space
VAV 1 -11 - No change
VAV 1-12 - Move thermostat to Office 114
VAV 1-13 - No change
VAV 1-14 - No change
VAV 1-15 - Move thermostat to entrance walkway
MECH - EXISTING VAV BOXES Rc�ergumLLER
HEATER ARCHITECTURE INTERIORS PLANNING VIZLAB
TAG MANUFACTURER MODEL SIZE FLOW (CFM) VOLTS/ PHASE MCA MOCP kW NOTES 275 FIFTH STREET, SUITE 100
1-7 TITUS DESV 012 1500 CFM 480VAC/ 3PH 13.5 15 9.00 kW
1-8- TITUS DESV 08 800 CFM 277VAC/ 1 PH 18.1 20 4.00 kW BREMERTON, WA 98337
1-9 TITUS DESV 06 230 CFM - 0.00 kW NO HEATING COIL 360-377-8773
1-10 TITUS DESV 08 500 CFM 0.00 kW NO HEATING COIL RFMARCH.COM
1-11 TITUS DESV 08 600 CFM - 0.00 kW NOHEATINGCOIL
1-12 TITUS DESV 2_1 2 j0O1CFM 41 111 3 9 15 6.00 kW1-13 TITUS DESV CFM 277VAC/ 1 PH 18.1 1 20 1 4.00 kW
1-14 TITUS DESV 06 250 CFM 277VAC/1PH 13.5 1 15 1 3.00 kW
1-15 TITUS DESV 08 530 CFM 277VAC/1PH 13.5 15 3.00 kW
ECOTOPE
MECH - DIFFUSERS, LOUVERS, GRILLES
TAG MANUFACTURER MODEL NOTES
1 TITUS OMNI COORDINATE WITH ARCHITECT
2 TITUS PAR COORDINATE WITH ARCHITECT
0
8
T
0910N , t
EXPIREZ79�104/21I
Z
0
>
F_
LLJ co
arIX!KC" It LU
00
80
ry 00
ch 0 < <
a_
Of Cf
Uj > ED <
_j
= z 0zY
-
::D
<
C)
C)
C-0
V 21 cc:
_V3
...........
j'f---
4'
C-0
!$ECT # 2017036.20
PERMIT SET
ISSUE DATE SEPTEMBER 12,2019
REVISION SCHEDULE
V"RMIT
FOR:
Q OD E
Fiectrical
T_
FlUmbing
Gas Piping
i City ofTukwila
CUILDING DIVISION
. ..........
i City of Tuk`t6la
01 `"v
Elf
_T
WI!
Vj
V
0 0
GENERAL NOTES AND
MECHANICAL
M19-0162 SCHEDULE
fn►q•DlvzMoo.o1
3
4
1 Mechanical - Level 1 Demo
1/8" = 1'-0" —
M 19-0162
275 FIFTH STREET, SUITE 100
BREMERTON, WA 98337
360-377-8773
RFMARCH.COM
ECOTOPE
0 of Wa:.;ryi�;
Z
'O ,9 42877 p ��
is FGISTV
FgS/ p hs AL ENC'
EXPIRES 0924
I Z
H _0
O<
■ O
aZ
ww
c� � 00
z ��
�0 <
pww<
z Y
= Z
O 0
C.) =5
0 m
zo
PROJECT# 2017036.20
PERMIT SET
ISSUE DATE SEPTEMBER 12, 2019
REVISION SCHEDULE
APr^ —R�;
rr _-07-211--1
—`£sty-of -T ma-- 4- —
MECHANICAL DEMO
PLAN
SHEET #
m 11001
2
0
4
5
1-15�
+- OUT OF SCOPE
A B C D E F G d
Mechanical - Level 1 Epsting
fig, = 1'-0"
Ml 9-0162
275 FIFTH STREET, SUITE 100
BREMERTON, WA 98337
360-377-8773
RFMARCH.COM
ECOTOPE
Z
O
O
aZ
WW 00
0
in Q
ry
O W wJ
= Z oz�
�- — �
Q�
Z Z o0
= 0 co
O J
tC.)
w W
Z p
PROJECT # 2017036.20
PERMIT SET —]
ISSUE DATE SEPTEMBER 12, 2019
REVISION SCHEDULE
41
MECHANICAL LEVEL 1
FLOOR PLAN -
EXISTING
SHEET #
M21 mOl
;L��
275 FIFTH STREET, SUITE 100
BREMERTON, WA 98337
360-377-8773
RFMARCH.COM
ECOTOPE
A B u E F G H
1 g g 1 718"a 1 8.,a 1- 8. a r' 8..a 1 8.,a 8 g 1 8, a ` Z
- 200 CFM 200 CFM 200 CFM 200 CFM 150 CFM 200 CFM 1 200 CFM 1 8" 0 215 CFM
- r 250 CFM � 1
\\wo- \
,aa
Cw e^e 10 e 10^e � !
«F, _._.
ofri 1nq 121 J 2 T
10,2[11,i1 r SREAK M
2
�._ 200 CFM "-------- 1 8 0 ! I
120
—= -- PRIMARY RETURN DUCT,,",�_-.' a250CFMa� r _. .._._-_---
(TYP-2) - - __ .. ____._ --- - I. i
elf 00
2 I 14'e 8 0---- —--__t.-
50 CFM - - - _ 4- - — 2 1 - 1 i ctn� I - t CO
610 5�50 CFM 150 CFM T�-
- C LL
1 6"e!L(TYP-2) 0 12"e7
�_50 CFM
---Aw__ ,--r0 2s...�. :\\.. '_ v _- -�` 3E#'f10E- --- - 450 CFM♦^
719
V♦
^� ' 1 �1 .,. PRIMARY SUPPLY �8' 0 ! -� -- -1 1 -- ( Af� j 8 �1 _ r - "' =
____
-N� T
I
180 CFM _ 8"m 5 FM
2 1 8"6 m i 1 °Fi i. + 1 2 UNDERCUT 14"0 Q
OC '
T�■
180 CFM a^e 12 e - -- . ' JL,e _. _ 200 CFl
FM ; DOOR 3/4" i.
_.... 600 CFM t1 _ z
P
Q
I \\\ I 1 50 ~
i' FM � V
;',. � ST9 F2A j -
I�jl ' ..
�--� - 4
16^e ,a^e ern oF'v ce
r� O
- �_.�� -
110 9
_ 4 Co
_ !M _
i 1 10 a 2 8' m 1 8"0 9 2 8..e 1 10"m I
300 CFM 200 CFM 200 CFM �I 200 CFM 275 CFM
(TYP-5) (TYP-4) (TYP-2) (TYP-3) (TYP-2)
A B C p E F H
PROJECT # 2017036.20
PERMIT SET
ISSUE DATE SEPTEMBER 12, 2019
� REVISION SCHEDULE
Mechanical - Level 1 New r
��-- T--
s !
MECHANICAL LEVEL 1
FLOOR PLAN - NEW
M 19-0162
SHEET #
M21 m02
•
275 FIFTH STREET, SUITE 100
BREMERTON, WA 98337
360-377-8773
RFMARCH.COM
ECOTOPE
z
I-- o
0
� O
1 -
2 �'
IJ • _ • _
az
wu)
00
0
F71
� n A EZ U O F
®
ct
O W W Q
~
_
O
r L
LA
C-0
U
pi
oz
C L1 (e�
j
Z
PROJECT # 2017036.20
PERMIT SET
D
E
F
G !
ISSUE DATE SEPTEMBER 12, 2019
REVISION SCHEDULE
n Reflected Ceiling Plan - Level 1 New
°
CY3 i --4 -�
REFLECTED CEILING
PLAN - LEVEL 1 - NEW
M 19-0162
-
2>>
SHEET #
M22m01