HomeMy WebLinkAboutPermit EL19-0467 - THORNDYKE ELEMENTARY SCHOOL - REPLACE 49 HEAT PUMPSTHORNDYKE ELEMENTRY
SCHOOL
4415 S 150T" ST
ELI 9-0467
Parcel No:
Address:
City of Tukwila
a
ent of Community Development
63O0SouthcenterBoulevard, Suite #1OO
Tukwila, Washington 98188
Phone: 206431'3670
Inspection Request Line: Z06'438'9]5O
Web site: http://www.TukwilaWA.gov
0042000280
4415SI50TH5T
ELECTRICAL PERMIT
Project Name: THORNDYKE ELEMENTARY SCHOOL
Permit Number: EL19'0467
Issue Dat : 0/17/2019
Permit Expires On: 12/I4/2019
Owner:
Name:
Address:
Contact Person:
Name:
Address:
TUKWILA SCHOOL DISTRICT
4640 S 144TH ST , TUKWILA, WA
98168
MARK UNDSETH
5005 THIRD AVE S'5EA||LE, WA,
98134
Contractor:
Name: MO(|NSTR CO LLC(ELECTRICAL)
Address: P0BOX Z4567'SEATTLE, WA, 98I24
License No: MCKINCL942DN
Lender:
Name:
Address:
Phone: (206) 775-6561
Phone: (206) 762-3311
Expiration Date: 3/15/2020
DESCRIPTION OF WORK:
DISCONNECT (49) EXISTING 1-IEAT PUMPS, AND RECONNECT (49) NEW/REPLACEMENT HEAT PUMPS. REPLACE (2)
EXISTING 30 AMP 480 VOLT NON -FUSE DISCONNECT SWITCHES SERVING HEAT PUMPS IN TF-tE BOILER ROOM
WITH NEW FUSIBLETYPE.
Valuation of single family: $0.00
Valuation of mf/comm: $17,480.00
Type of Work: TENANT IMP
Fees Collected: $564.55
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: 125
Sewer District: VALLEY VIEW
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residental Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
2015International Fuel Gas Code:
Permit Center Authorized Signature:
2015
2015
2015
2015
National Electrical Code:
WA Cities Electrical Code:
WAC 296-46B:
WA State Energy Code:
2017
2017
2017
2015
I hearby certify that I have read and examined this permit and know the same to be true and correct, All
provisions of aw and ordinances governing ths work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work, am authorized to sign and obtain this
deve|upmenandag'ee to the conditions attached to this permit.
�
�
Print Name:
Da
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***ELECTRICAL PERMIT CONDITIONS***
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical
lnspector at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical
Inspector.
4: All electrical work shall be in accordance with NFPA 70 NEC, and requirements for electrical instaUations,
Chapter 295-469 WAC and the Washington Cities Electrical Code.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts
of the building, such equipment shall not be concealed until it has been inspected and approved by the
Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any
violation of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related
documentation that presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work
permits. Where approved plans have been issued, revisions to the plans and additional review may be
required.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line:: (206) 438-9350
2100 ELECTRICAL FINAL
7003 ROUGH -IN ELECTRICAL
7002 SERVICE
7001 UNDERGROUND/SLAB
(TITOFmTON;111?
comunity Developmen epartment
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Electrical Permit No.
Project No.
Date Application Accepted:
Date Application Expires: /
(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
King Co Assessor's Tax No.:
Site Address: 4415 s 150th St Suite Number:
Tenant Name: Tukwila SD/Thorndyke Elementary School New Tenant:
PROPERTY OWNER
,-.›.
Name: Mark Undseth
Name: Tukwila School
District
City: Seattle State:
WA Zip:
98134
Address:4640 s
144th
st
Phone: Fax:
City: Tukwila
Email: marku@mcKinstry. . com
State:
WA
Zip:98188
CONTACT PERSON — person receiving all project
communication
,-.›.
Name: Mark Undseth
Address: 5005 3rd Ave S
Address: 5005 3rd Ave S
City: Seattle State:
WA Zip:
98134
City: Seattle State: WA
Zip:
98134
Phone: Fax:
Email: marku@mcKinstry. . com
Floor:
I: Yes Ej..No
ELECTRICAL CONTRACTOR INFORMATION
Company Name: McKinstry Co, LLC
Address: 5005 3rd Ave S
City: Seattle State:
WA Zip:
98134
Phone:206-762-3311 Fax:
Contr Reg No.: MCKINCL942DN Exp Date: 12 / 31 / 20
Tukwila Business License No.;
Valuation of Project (contractor's bid price): $ 17,480.00
Scope of Work (please provide detailed information):
Disconnect (49) existing heat pumps, and reconnect (49)
new/replacement heat pumps. Replace (2) existing 30 -amp 480 Volt Non-fused disconnect switches
serving Heat Pumps in the Boiler Room with new Fusible Type
Will service be altered? 11 Yes El No Adding more than 50 amps? El Yes CI No
Type of Use:
Type of work:
0 New 0 Addition 0 Service Change 12 Remodel 0 Tenant Improvement
0 Low Voltage 0 Generator 0 Fire Alarm 0 Telecommunication 0 Temporary Service
Property Served by:
Puget Sound Energy 0 Seattle City Light
W:\Permit Center\ Applications -Handouts\ Permit Applications \ PDF's\ Electrical Permit Application Revised I-17-19.docx
Page 1 of2
RESIDENTIAL
NEW RESIDENTIAL SERVICE
D New single family dwellings $180.00
(including an attached garage)
O Garages, pools, spas and outbuildings $120 00 ea
O Low voltage systems
(alarm) $60.00 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
O Service change or alteration $120.00
(no added/altered circuits)
0 Service change with added/altered circuits ........ .....-$100.00
number of added circuits $10.00 ea
0 Circuits added/altered without service change $60.00
(up to 5 circuits)
O Circuits added/altered without service change $60.00
(6 or more circuits)„ ..... .......... ....... ea
O Meter/mast repair $80.00
O Low voltage systems $60.00
(alarm, furnace thermostat)
MULTI -FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
O Temporary service (residential)$60 00
O Temporary service (generator) $90.00
O Manufactured/mobile home service $100.00
(excluding garage or outbuilding)
O Carnivals $100.00
Number of concessions $11.00 ea
Each ride and generator truck $11.00 ea
***EFFECTIVE JANUARY 1, 2014 EACH
PERMIT WILL BE ASSESSED A 5%
TECHNOLOGY FEE***
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value ofconstruction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
Print Name: Day Telephone:
Mailing Address: 5005 3rd
WAPerm it Center1Applications-Handouts \ Permit Applications PDF's \ Electrical Permit Application Revised I -1 7-19.does
Date:
DDia
Seattle WA
City Stat
Page 2 of 2
Cash Register Receipt
City of Tukwila
Receipt Number
DESCRIPTIONS
. CA COUNT
I QUANTITY
I PAID
PermitTRAK
$564.55
EL19-0467 Address: 4415 S 150TH ST
Apn: 0042000280
$564.55
Credit Card Fee
$16.44
Credit Card Fee
R000.369.908.00.00
0.00
$16.44
ELECTRICAL
$527.03
PERMIT FEE MULTI-FAM/COMM
R000,322.101.00.00
0.00
$421.62
PLAN CHECK FEE
R000.345.832.00.00
0.00
$105.41
TECHNOLOGY FEE
$21.08
TECHNOLOGY FEE
R000.322.900.04.00
0.00
$21.08
TOTAL FEES PAID BY RECEIPT: R17784
$564.55
Date Paid: Monday, June 03, 2019
Paid By: JULIA ALEXANDER
Pay Method: CREDIT CARD 060035
Printed: Monday, June 03, 2019 1:24 PM 1 of 1
5Y5TEN15
CO TUKWILA ETRAKIT
6200 SOUTHCENTER BLVD
TUKWILA, WA 98188
206-433-1870
CITY OF TUKWILA
Date: 06/03/2019 01:23:58 PM
CREDIT CARD SALE
VISA
CARD NUMBER: **********5604 K
TRAN AMOUNT: $564.55
APPROVAL CD: 060035
RECORD #: 000
CLERK ID: Bill
Thank you!
Customer Copy
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PE MIT
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
-Type of Inspection:
••-• V 1:
Address:
Date Called:
Special Instructions:
Date Wanted:
a.m.
P.m..
Requester:
Phone No:
42(e7
X-2 /2-72 ,
Approved per applicable codes.
COMMENTS:
Correction required prior to approval.
Inspector:
Date: 0 g
REINSPECTIO FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 S uthcenter Blvd.. Suite 100. Call to schedule reinspection.
•
INSPECTION RECORD
Retain a copy with permit
INSPECT ON NO.
T O.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 438-9350
Project:
Type of Inspe
on:
Address:
Date Called:
Special Ins
tions:
Date Wanted:
a.m.
p.m.
Requester:
Phone No:
�
QApproved per applicable codes.
Corrections required prior to approval.
ns pectora
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 outhcenter Blvd.. Suite 100. Call to schedule reinspection.
g'ERMIT COORD COPY o
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: EL19-0467 DATE: 06/03/19
PROJECT NAME: THORNDYKE ELELMENTARY SCHOOL
SITE ADDRESS: 4415 S 150 ST
X Original Plan Submittal
Response to Correction Letter # Revision # after Permit Issued
Revision # before Permit Issued
DEPARTMENTS:
Building ivision
Public Works
Fire Prevention
Structural
Planning Division
Permit Coordinotor
PRELIMINARY REVIEW:
Not Applicable
(no approval/review required)
REVIEWER'S INITIALS:
DATE: 06/04/19
Structural Review Required
DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
(corrections entered in Reviews)
DUE DATE: 07/02/19
Approved with Conditions fl
Denied
(ie: Zoning Issues)
n
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: I3ldg 1] Fire El Ping LIJ PW 1TJ Staff Initials:
12/18/2013
Howe Espailol Contact
Safety & Health Claims & Insurance
411111k/k Washington State Department of
Labor & Industries
Search L&I
A -Z ndex elp My
Workplace Rights Trades & Licensing
MCKINSTRY CO LLC
Owner or tradesperson
Principals
ALLEN, DEAN CHARLES, PARTNER/MEMBER
Hagar, Joseph D, PARTNER/MEMBER
Casey, Joy D, AGENT
MOORE, DOUGLAS J, PARTNER/MEMBER
(End: 03/09/2018)
ALLEN, DAVID, PARTNER/MEMBER
(End: 03/09/2018)
TEPLICKY, JOSEPH W
(BILL), PARTNER/MEMBER
(End: 03/09/2018)
BLACK, STEPHEN, AGENT
(End: 03/09/2018)
Doing business as
MCKINSTRY CO LLC
WA UBI No
602 569 922
PO BOX 24567
SEATTLE, WA 98124
206-762-3311
KING County
Business type
Limited Liability Company
Certifications & Endorsements
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Electrical Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
MCKINCL942DN
Effective — expiration
03/15/2006— 03/15/2020
Designated administrator
Gochis, Kenneth
License type
Electrical Administrator
Bond
Western Surety Co
Bond account no
929523050
Received by L8,1
02/25/2011
Active,
Meets current requirements.
License no.
GOCHIK*841DU
$4,000.00
Effective date
03/06/2011
Expiration date
Help us improve
ELECTRICAL
ABBREVIATIONS
ABBRV
DESCRIPTION
ABBRV
DESCRIPTION
ABBRV
DESCRIPTION
ABBRV
DESCRIPTION
ABBRV
DESCRIPTION
A
AC
AF
AFF
AFG
AHU
AIC
AL
AT
ATS
AUTO
AUX
AWG
BATT
BFC
C
CAT
CB
CKT
CLG
CO
CPT
CT
CU
DC
DIA
DISC
DN
DSB
DWG
E
EF
EL
EMT
EOL
EPR
EQUIP
EWC
EWH
AMP, AMPERES
6" ABOVE COUNTER OR 3" ABOVE BACKSPLASH
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPS INTERRUPTING CURRENT
ALUMINUM
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAGE
BATTERY
BELOW FINISHED CEILING
CONDUIT or CENTIGRADE
CATALOG
CIRCUIT BREAKER
CIRCUIT
CEILING
CONDUIT ONLY - PROVIDE PULL STRING
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
COPPER
DIRECT CURRENT
DIAMETER
DISCONNECT
DOWN
DISTRIBUTION SWITCHBOARD
DRAWING
EMERGENCY DESIGNATION
EXHAUST FAN
ELEVATION (HEIGHT)
ELECTRICAL METALLIC TUBING
END -OF -LINE DEVICE
ETHYLENE PROPYLENE RUBBER
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXIST OR (E
F
FA
FACP
FBO
FC
FLA
FLEX
FS
FT
FV
FVNR
FVR
G or GND
GA
GEN
GFCI
GRS
HH
HID
HOA
HP
HPS
HTR
IBE
IBO
IC
ID
IN
INST
JB or J-BOX
K
KCMIL
KV
KVA
KVAR
KW
KWH
KWHD
EXISTING
FUSE OR FAHRENHEIT
FIRE ALARM
FIRE ALARM CONTROL PANEL
FURNISHED BY OTHERS
FOOTCANDLE
FULL LOAD AMPERES
FLEXIBLE CONDUIT
FLOW SWITCH
FOOT or FEET
FULL VOLTAGE
FULL VOLTAGE NON -REVERSING
FULL VOLTAGE REVERSING
GROUND
GAGE
GENERATOR
GROUND FAULT CIRCUIT INTERUPTER
GALVANIZED RIGID STEEL
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND -OFF -AUTO SELECTOR SWITCH
HORSEPOWER
HIGH PRESSURE SODIUM
HEATER
INSTALLED/CONNECTED BY ELECTRICAL
INSTALLED BY OTHERS
INTERRUPTING CURRENT
INSIDE DIAMETER
INCH or INCHES
INSTANTANEOUS
JUNCTION BOX
THOUSAND
THOUSAND CIRCULAR MILS
KILOVOLT
KILOVOLT -AMPERES
KILOVOLT -AMPERES REACTIVE
KILOWATTS
KILOWATT-HOURS
KILOWATT-HOUR DEMAND
LED
LS
LTG
LV
M or MTR
MAX
MCA
MC
MCB
MCC
MECH
MFR
MH
MIN
MISC
MLO
MOCP
MSB
MTD
MTG
MVA
N
NC
NEC
NEMA
NIC
NL
NO.
NO
NTS
OC
OCPD
OD
OFCI
OL
OS
PA
PB
PC
LIGHT EMITTING DIODE
LIMIT SWITCH
LIGHTING
LOW VOLTAGE
MOTOR
MAXIMUM
MINIMUM CIRCUIT AMPACITY
METAL CLAD CABLE
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MECHANICAL
MANUFACTURER
MANHOLE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
MAIN SWITCHBOARD - SERVICE ENTRANCE RATED
MOUNTED
MOUNTING
MILLION VOLT AMPERES
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE - JURISDICTION CURRENT
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NUMBER
NORMALLY OPEN
NOT TO SCALE
ON -CENTER
OVERCURRENT PROTECTIVE DEVICE
OUTSIDE DIAMETER
OWNER FURNISHED CONTRACTOR INSTALLED
OVERLOADS
OCCUPANCY SENSOR - ADJUSTABLE
PUBLIC ADDRESS
PULLBOX
PHOTOCELL - MOUNT FACING NORTH
PF
PH OR
PNL
PRI
PSE
PT
PVC
PWR
QTY
R
REC
REQD
REV
RPM
RS
RVAT
SCL
SEC
SECT
SF
SHLD
SHT
SK
SPEC
SQ
SS
ST
STD
STL
STRUCT
SUB
SV
SVC
SW
SWBD
SYM
SYNC
SYS
TB
POWER FACTOR
PHASE
PANEL
PRIMARY
PUGET SOUND ENERGY
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
POWER
QUANTITY
RESISTANCE or RADIUS
CONVENIENCE RECEPTACLE
REQUIRED
REVISION
REVOLUTIONS PER MINUTE
RAPID START
REDUCED VOLTAGE AUTOTRANSFORMER
SEATTLE CITY LIGHT
SECONDARY
SECTION
SUPPLY FAN or SQUARE FEET
SHIELD or SHIELDED
SHEET
SKETCH
SPECIFICATIONS
SQUARE
STAINLESS STEEL
SHUNT TRIP or STREET
STANDARD
STEEL
STRUCTURAL
SUBSTITUTE
SOLENOID VALVE
SERVICE
SWITCH
SWITCHBOARD
SYMMETRICAL
SYNCHRONOUS
SYSTEM
TERMINAL BLOCK
TD
TC
TEMP
TERM
THHN
THWN
TOS
TS
TSP
TTB
TTC
TYP
UC
OF
UG
UH
UL
UON
UPS
UTP
V
VM
W
W/
WH
WHSE
WM
W/O
WP
X
XFMR
XHHW
XLP
XP
Z
TIME DELAY
TELECOMMUNICATIONS OUTLET (PHONE/DATA)
TEMPERATURE or TEMPORARY
TERMINAL.
HEAT -RESISTANT THERMOPLASTIC
MOISTURE AND HEAT RESISTANT THERMOPLASTIC
TOP OF SUPPORT or STEEL or SLAB
TAMPER SWITCH
TWISTED SHIELDED PAIR
TELEPHONE TERMINAL BOARD
TELEPHONE TERMINAL CABINET
TYPICAL
UNDER -COUNTER
UNDER -FLOOR
UNDERGROUND
UNIT HEATER
UNDERWRITER LABORATORIES
UNLESS OTHERWISE NOTED
UNINTERRUPTABLE POWER SUPPLY
UNSHIELDED TWISTED PAIR
VOLTS
VOLTMETER
WATTS or WIRE
WITH
WATT-HOUR
WAREHOUSE
WIREMOLD
WITHOUT
WEATHERPROOF/NEMA 3R MINIMUM
REACTANCE
TRANSFORMER
MOISTURE AND HEAT RESISTANT
CROSS -LINKED SYNTHETIC POLYMER
CROSS -LINKED POLYETHYLENE
EXPLOSION -PROOF
IMPEDANCE
LIGHTING
SYMBOL
DESCRIPTION
(NOTE
(NOTE
1)
2)
REFERENCE LUMINAIRE SCHEDULE FOR DETAILS ON
LUMINAIRES INCLUDING MOUNTING TYPE, HEIGHT,
LAMPING, VOLTAGE, MANUFACTURER, ETC.
VARIOUS LIGHTING SYMBOLS ARE USED TO GENERALIZE
SHAPE/STYLE OF LUMINAIRE. REFERENCE LUMINAIRE •
SCHEDULE FOR DETAILS.
LUMINAIRE DESIGNATION
iGF1-•
2a,b CIRCUIT & SWITCHING
SF1
SF3
BF1 T
SF2
SOLID LINETYPE INDICATES SURFACE, CEILING OR WALL
0>
MOUNTING. ARROW INDICATES DIRECTION OF WALL WASH.
1----1
WF1
1-O
WF2
SF1
SF3
ill
r
SF2
O
DOUBLE LINETYPE INDICATES RECESSED OR PARTIALLY
RECESSED MOUNTING
SF1
SF3
tl/IIII
LUMINARE ON EMERGENCY SOURCE (TYPICAL)
SF2
EX1 fel EX2
AL1 AL2
0-4 ❑-.
EXIT SIGN ON EMERGENCY SOURCE
ARROW INDICATES DIRECTION OF EGRESS
SHADING INDICATES FACE (SINGLE OR DOUBLE)
POLE MOUNTED AREA LUMINAIRE
Li.
BATTERY POWERED EMERGENCY LIGHT
U
COMBINATION BATTERY POWERED EGRESS LIGHT AND
®
i V
EXIT
LIGHTING FIXTURE, WALL WASHER
TRACK LIGHT
i
LLCPJ
LC � 20/6
S
S S
ET]
(fa
OS
LIGHTING CONTROL PANEL
LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE, 120V COIL,
ELECTRICALLY HELD, NO/NC AUXILIARY CONTACTS A/P A
INDICATES CONTACT AMP RATING P INDICATES NUMBER OF
POLES (NO)
SWITCH, TYPE AS INDICATED
2 2-POLE D DIMMER
3 3-WAY LV LOW VOLTAGE
4 4-WAY P PILOT LIGHT
K KEY SWITCH OC OCCUPANCY SENSOR
M MOTER RATED, SIZE OL PER MOTOR SIZE
T DIGITAL TIME SWITCH - INTERMATIC E1400 SERIES OR EQUAL
SWITCHES TO BE SUBMITTED AS PART OF LIGHTING CONTROL
PACKAGE
DUAL LEVEL SWITCHING, INSIDE AND OUTSIDE LAMPS OF
LUMINAIRE TO BE SWITCHED SEPARATELY
SWITCHBANK
LOW VOLTAGE TRANSFORMER
TIME CLOCK
SENSOR, TYPE AS INDICATED
IR INFRARED
DT DUAL TECHNOLOGY
PC PHOTO CELL
LS INTERIOR LIGHT SENSOR
EQUIPMENT
74
FSD
SPD
SM
XIY/Z
D
X/Y
®X
W/X/Y/Z
qHU..l
�EPOl
PB
BRANCH CIRCUIT PANELBOARD. VOLTAGE, AMPACITY
AS INDICATED.
TRANSFORMER
MOTOR CONNECTION. MOTOR BY OTHERS. SIZE AS INDICATED BY
MECHANICAL CALLOUT SYMBOL.
FIRE SMOKE DAMPER
SURGE PROTECTION DEVICE
EQUIPMENT CONNECTION
MOTOR DISCONNECT SWITCH
FUSED DISCONNECT, TYPE AS INDICATED, 3-POLE UON
X DISCONNECT RATING
Y NEMA RATING
Z FUSE SIZE
NON -FUSED DISCONNECT, TYPE AS INDICATED, 3-POLE UON
X DISCONNECT RATING
Y NEMA RATING
MOTOR STARTER IN NEMA 1 ENCLOSURE, SIZE AS
INDICATED, 3-POLE UON
COMBINATION MOTOR STARTER AND DISCONNECT TYPE AS
INDICATED, 3-POLE UON
W STARTER SIZE
X DISCONNECT RATING
Y NEMA RATING
Z FUSE SIZE
VARIABLE FREQUENCY DRIVE
ENCLOSED CIRCUIT BREAKER
THERMOSTAT - PROVIDE 120V INTERCONNECTION TO HVAC
EQUIPMENT INDICATED
RELAY - CONTROL TYPE
EMERGENCY POWER OFF SWITCH, see detail
PULLBOX
GROUNDING ROD CONNECTION
GROUNDING ROD CONNECTION WITH TEST WELL
BOX
RECEPTACLES
(NOTE 3)
ALL RECEPTACLES TO BE GROUNDING TYPE UON.
TYPE AS INDICATED
WP WEATHERPROOF
GFCI GROUND FAULT CIRCUIT INTERRUPTER
XP EXPLOSION PROOF
T TAMPER -RESISTANT
IG ISOLATED GROUND
0
6
O
!O
//111/11
LTV
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, EMERGENCY CIRCUIT
DOUBLE DUPLEX RECEPTACLE, EMERGENCY CIRCUIT
SPLIT WIRED RECEPTACLE,
DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER TYPE
SPECIAL RECEPTACLE, SEE PLANS FOR ADDITIONAL INFORMATION
FLUSH FLOOR OUTLET (DEVICES AS INDICATED)
FLOOR OUTLET - POKE THROUGH (DEVICES AS INDICATED)
DEDICATED CIRCUIT RECEPTACLE
DATA / POWER POLE
MULTI -OUTLET ASSEMBLY - LENGTH PER PLAN, DEVICE(S) AS INDICATED
COMBINATION OUTLET (DEVICES AS INDICATED)
ELECTRICAL ROUGH -IN FOR COMMUNICATION OUTLET
(# INDICATES NUMBER OF PORTS)
CIRCUIT SYMBOLS
UNMARKED CIRCUIT IS CONCEALED
IN CEILING OR WALL
BRANCH CIRCUIT "20/1" (UON)
BEGINNING OF
INDIVIDUAL CIRCUIT
CONDUIT, STUBBED, CAPPED AND
MARKED, WITH PULL STRING
CONDUIT DOWN CONDUIT UP
EXISTING
GF1
4a,b
CIRCUIT
_ 2
CONCEALED IN FLOOR
OR UNDER GROUND
JUNCTION BOX
SIZED PER CODE
CONDUCTORS -CONNECTED
— (— CONDUCTORS - NOT CONNECTED
LN1A-2,4,6
PANEL HOMERUN
3/4"-3#12,1#12G
SIZE
QUANTITY
RACEWAY
RACEWAY UP
RACEWAY DOWN
c CIRCUIT CONTINUATION
ELECTRICAL
EQUIPMENT
NAMING
CONVENTION
LEGEND
EXAMPLES / LEGEND
VOLTAGE
EQUIPMENT TYPE
POWER SYSTEM
FLOOR DESIG.
SEQUENCE DESIG.
4 ATS X B A
4 MSB N 1 A
2 PNL N 2 B
4 — 480Y/277 30, 4W+G
2 — 208Y/120 30, 4W+G
MV — MEDIUM VOLTAGE
SUB — UNIT SUBSTATION
SBD — SWITCHBOARD
SGR — SWITCHGEAR
DPL — DISTRIBUTION PANEL
PNL — BRANCH PANEL
ATS — AUTOMATIC TRANSFER SWITCH
MSB — MAIN SWITCHBOARD
MTS — MANUAL TRANSFER SWITCH
T — TRANSFORMER - DRY TYPE
UTX —UTILITY MAIN TRANSFORMER
MCC — MOTOR CONTROL CENTER
ECB — ENCLOSED CIRCUIT BREAKER
FSW — FUSED DISCONNECT SWITCH
DSW — NON -FUSED DISCONNECT SW.
N — NORMAL
X — LIFE SAFETY (NEC517/NEC700)
Y — LEGALLY REQUIRED (NEC701)
Z — OPTIONAL (NEC702)
U — UNINTERRUPTABLE POWER (UPS)
C — CRITICAL BRANCH (NEC517/NEC700)
Q — EQUIPMENT BRANCH (NEC 517/NEC700)
W — OTHERS (AS DEFINED)
B — BASEMENT/PIT
1 — FIRST FLOOR
M — MEZZANINE
R - ROOF
UTILIZE SEQUENCE
DESIGNATOR TO INDICATE
MULTIPLE EQUIPMENT
TYPES IN SAME AREA
A — 1ST SEQUENCE
B — 2ND SEQUENCE
C — 3RD SEQUENCE
VOLTAGE
T
EQUIP
TYPE
POWER
SYSTEM
FLOOR
T
SEQUENCE
DESIGNATOR
STEP DOWN TRANSFORMER
STEP DOWN TRANSFORMERS ARE ALWAYS LABELED T PROCEEDED BY PANEL NAME SERVED
TRANSFORMER SERVING PANEL '2PNLN1A' WOULD BE 'T2PNLN1A'
ELECTRICAL RISER
1 ST
LSIG
J 30AF
30AT
>>
(A600/A)
480V, 301
A
480/277V, 30, K11
75KVA
CP1-ATS06
125A/3P
65kAIC
GENERATOR. 39(14,45NVA4e0277. 38}W d G
A 30A
—(J)
R:U8T5A,%MRSRTA9 1I
PANEL
LXP2N
208Y/120
100A MCB
CIRCUIT BREAKER, NUMBER INDICATES SIZE(A) AND
POLES
ST SHUNT TRIP
CL CURRENT LIMITING
L LONG TIME ADJUSTABILITY
S SHORT TIME ADJUSTABILITY
I INSTANTANEOUS ADJUSTABILITY
G GROUND FAULT ADJUSTABILITY
MEDIUM VOLTAGE CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
FUSED SWITCH
NON -FUSED SWITCH
SPACE
FUSE OR CURRENT LIMITER. SIZE(A) AS INDICATED
IDENTIFICATION SYMBOL FOR FEEDER SIZES
MOTOR THERMAL OVERLOADS, SIZE PER MOTOR, (3)
UON
GROUND CONNECTION
DELTA-WYE, DRY TYPE TRANSFORMER. VOLTAGE, KVA RATING AS
INDICATED ON PLANS, 150°C RISE, 220°C INSULATION CLASS
STANDARD
TENANT METER
UTILITY METER
TRANSFER SWITCH
ENGINE -GENERATOR, DIESEUNATURAL GAS. SOUND ATTENUATED
ENCLOSURE, IF APPLICABLE.
BRANCH CIRCUIT PANELBOARD. VOLTAGE, AMPACITY
AS INDICATED.
GROUND FAULT SENSOR AND INDICATING LIGHT
OUTLET
MOUNTING
HEIGHT
(TYPICAL)
SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE
ARCHITECTURAL DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR REQUIRED,
THEN LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE
FINISHED FLOOR TO THE UPPER OR LOWER EDGE OF THE BOX AS NOTED BELOW.
RECEPTACLES
15" AFF TO BOTTOM OF BOX
LIGHT SWITCHES .
48" AFF TO TOP OF BOX
PANELBOARDS
72" AFF TO TOP OF PANELBOARD
TELEPHONE OUTLET - DESK
15" AFF TO BOTTOM OF BOX
TELEPHONE OUTLET - WALL
48" AFF TO TOP OF BOX
COMPUTER OUTLET - DESK
15" AFF TO BOTTOM OF BOX
LUMINAIRE
NAMING
CONVENTION
EXAMPLES / LEGEND
MOUNTING TYPES
SHAPE / STYLE
DESIGNATOR
P L 1 A
R R 1 B
X T 3 C
Z 1 A
P — SUSPENDED
R — RECESSED
S — SURFACE/CEILING
W — WALL
XP — EXTERIOR - POLE
XB — EXTERIOR - BLDG
Y — LANDSCAPE
Z — EXIT
C — CUSTOM / OTHER
L — LINEAR
P — PERIMETER
R — ROUND
S — SQUARE
T — TAPE /RIBBON
W — WALL WASH
PRIMARY AND SECONDARY
DESIGNATORS MAY BE UTILIZED TO
INDICATE THE SAME LUMINAIRE UTILIZED
WITH DIFFERENT OPTIONS (LUMEN
OUTPUT, REFLECTOR COLOR, ETC.)
EXIT SIGNS
MTG.
TYPE
SHAPE
STYLE
T
/
PRIMARY
DESIG.
T
SECONDARY
DESIG.
PRIMARY DESIGNATOR (1) FOR SINGLE
FACE, (2) FOR DOUBLE FACE
GENERAL INFORMATION SYMBOLS
(J)
__, i+',J;
E
I I
L_ J
X
X
KEY NOTE
REVISION SYMBOL
LIGHT LINE INDICATES EXISTING DEVICES
LIGHT LINE INDICATES FUTURE DEVICES
REMOVE EXISTING ELECTRICAL EQUIPMENT
NEC CODE REQUIRED CLEAR WORKING SPACE
EQUIPMENT DESIGNATION
ELECTRICAL VOLTAGE AND PHASE
ELECTRICAL LOAD
KITCHEN EQUIPMENT NUMBER
REF. KITCHEN EQUIPMENT SCHEDULE
DETAIL OR DIAGRAM NUMBER
SHEET NUMBER
WHERE DETAIUDIAGRAM SHOWN
SECTION LETTER
SHEET NUMBER WHERE SECTION SHOWN
REVISION NUMBER - DENOTES NUMBER
AND DATE WHEN REVISION OR ISSUE
OCCURED
REVISION CLOUD - DENOTES AREA OF
CHANGE
DETAIL REFERENCE OUTLINE
WITH NUMBER AND SHEET LOCATION
SCOPE OF WORK:
ELECTRICAL SCOPE ASSOCIATED WITH THE REPLACEMENT OF (49) HEAT PUMPS. THIS PROJECT
WILL RESULT IN A NET LOAD ADDITION. WORK INCLUDES RELOCATION OF THE ELECTRICAL
CONNECTIONS FOR 4 DUCT SMOKE DETECTORS.
DRAWING
INDEX
SHEET NO.
SHEET NAME
E-001
ELECTRICAL - COVER SHEET
E-002
ELECTRICAL SHEET SPECIFICATION
E-013
ELECTRICAL PANEL SCHEDULES
E-014
ELECTRICAL PANEL SCHEDULES
E-040
ELECTRICAL ONE LINE
ED-121
ELECTRICAL DEMO PLAN MECH RM & PLATFORM
ED-122
ELECTRICAL DEMO PLAN ATTIC EAST & WEST
EP-121
ELECTRICAL PLAN - MECH RM & PLATFORM
EP-122
ELECTRICAL PLAN ATTIC EAST & WEST
REVISIONS
No changes shall be made to the scope
of work wltnout prior approval of the
Tukwila Building Division.
NOTE: Revisions will require a new plan
submittal and may Include additional plan review.
SEPARATE PERMIT
RE URED FOR:
Mechanical
❑ Electrical
Plumbing
GE Gas Piping
City of Tukwila
BUILDING DIVISION
qv
Permit NoL Fell kY0
Plan review approval is subject to errors ana
omissions Approval of construction documents does
VT auth:►rize ine violation of any adopted code or
ordinance. Receipt of apDrpved Field Copy and
�ikl{/lea
`) f
By.
Date:
City ofuKwiia
BUILDING DIVISION
REVI WED FOF4;
GONFP 70 NE WITH
3 JJUUN 12 01
City of Tukwil
EUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN 03 2019
PERMIT CENTER
le Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED:
DRAWN:
CHECKED:
SWS
SWS
DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL
COVER SHEET
SHEET NUMBER:
-001
DIVISION 26 - ELECTRICAL
SUBMITTAL REQUIRED
YES NO NA
MEDIUM VOLTAGE WIRES AND CABLES
LOW VOLTAGE WIRES AND CABLES
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
RACEWAY AND BOXES
IDENTIFICATION ELECTRICAL SYSTEMS
PANELBOARDS
SWITCHBOARDS
WIRING DEVICES
LOW VOLTAGE CIRCUIT PROTECTIVE DEVICES
MOTOR CONTROLLERS
VARIABLE FREQUENCY AC DRIVES
x
x
x
x
x
x
x
x
x
x
x
x
SECTION 26 00 00 - ELECTRICAL WORK
1. ALL PROVISIONS OF THE CONTRACT APPLY TO THIS WORK. THIS DIVISION CONSISTS OF THE ELECTRICAL
WORK FOR THIS PROJECT. COORDINATE ALL WORK WITH OTHER TRADES AND CRAFTS FOR PROPER
INSTALLATION AND TIMELY EXECUTION OF CONSTRUCTION.
2. BEFORE THE SUBMITTING A PROPOSAL OR BID FOR THIS WORK, CONTRACTOR SHALL EXAMINE THE
COMPLETE SET OF PROJECT DOCUMENTATION FOR ALL TRADES AND SHALL VISIT THE JOB SITE TO
DETERMINE EXISTING CONDITIONS.
3. SUBMITTING A PROPOSAL OR BID ACKNOWLEDGES THE CONTRACTOR IS FULLY AWARE OF THE SCOPE, THE
EXISTING CONDITIONS AND IS ABLE TO COMPLETE ALL WORK IDENTIFIED. CONTRACTOR SHALL NOT BE
ENTITLED TO ADDITIONAL COMPENSATION FOR FAILURE TO ALLOW FOR ALL EXISTING CONDITIONS PRESENT
AT INSPECTION.
4. ALL MATERIALS, APPLIANCES, EQUIPMENT, TOOLS AND APPARATUS NECESSARY TO CONSTRUCT A
COMPLETE WORKING SYSTEM SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR.
5. EQUIPMENT AND DEVICES FURNISHED AND INSTALLED BY OTHER DIVISIONS (OR BY OWNER) THAT REQUIRE
ELECTRIC POWER (50V OR GREATER) SHALL BE CONNECTED BY THIS DIVISION. OBTAIN AND REVIEW ALL
SUBMITTALS AND SHOP DRAWINGS OF THIS EQUIPMENT.
6. ALL WORK SHALL COMPLY WITH THE LATEST ADOPTED ELECTRICAL CODE. CONTRACTOR SHALL NOTIFY
ENGINEER IMMEDIATELY IF PROJECT DOCUMENTATION OR EXISTING CONDITIONS IMPLIES OR REQUIRES
DEVIATION FROM APPLICABLE BUILDING CODES.
7. UNLESS INSTRUCTED OTHERWISE, CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY LICENSES,
PERMITS AND FEES REQUIRED. COORDINATE INSPECTIONS AS REQUIRED WITH THE AUTHORITY HAVING
JURISDICTION (AHJ). PROVIDE WRITTEN EVIDENCE OF FINAL ACCEPTANCE BY THE AHJ UPON PROJECT
COMPLETION.
8. RECORD DRAWINGS SHALL BE CONTINUOUSLY MAINTAINED IN THE FIELD, SUBJECT TO REVIEW BY THE
OWNER AND THE ENGINEER ON A REGULAR BASIS. AT COMPLETION OF WORK, CLEAN, CLEARLY MARKED
REPRODUCIBLE COPIES OF CONSTRUCTION DRAWINGS WILL BE PROVIDED TO THE ENGINEER.
SECTION 26 0010 - BASIC ELECTRICAL REQUIREMENTS
1. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL FEATURES OF WORK. INSTALL AS NECESSARY TO
AVOID INTERFERENCES, EASE INSTALLATION AND PROVIDE MAINTENANCE ACCESS AS REQUIRED AND IN
ACCORDANCE WITH CODE.
2. VERIFY LOCATION OF ALL EQUIPMENT PRIOR TO ROUGH IN. LOCATION OF ELECTRICAL DEVICES SHOWN ON
MECHANICAL DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.
3. DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY AND WHAT IS REQUIRED IN EITHER IS REQUIRED AS
IF CALLED FOR IN BOTH. DRAWING SYMBOLS AND/OR SPECIFICATION SECTIONS INCLUDED IN THE
CONTRACT DOCUMENTS MAY INCLUDE ITEMS NOT REQUIRED IN THE SCOPE OF WORK.
4. CIRCUITING IS DIAGRAMMATIC AND DOES NOT REPRESENT RACEWAY ROUTING. EXPOSED RACEWAY SHALL
BE RUN PARALLEL OR AT RIGHT ANGLES TO WALLS. CONTRACTOR IS RESPONSIBLE FOR CIRCUITING AND
CONNECTIONS PER INDUSTRY BEST PRACTICES.
5. LOAD HORSEPOWER AND/OR WATTAGES INDICATED ON THE PLANS ARE ESTIMATED REQUIREMENTS; VERIFY
WITH MECHANICAL SUBMITTAL DRAWINGS BEFORE ROUGH -IN. ADVISE ENGINEER OF EQUIPMENT CIRCUIT
REQUIREMENTS THAT DEVIATE FROM SUBMITTALS.
6. NOTIFY ENGINEER OF ANY CONFLICTS OR ISSUES IN THE DRAWINGS OR SPECIFICATIONS.
SECTION 26 00 40 - EXISTING SYSTEMS
1. DEMOLISH EXISTING ELECTRICAL AS REQUIRED. PROTECT EXISTING SYSTEMS TO REMAIN OR BE REUSED.
2. NO ELECTRIC SYSTEM OPERATION SHALL BE INTERRUPTED UNLESS SCHEDULED WITH THE OWNER IN
ADVANCE. CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR UNSCHEDULED INTERRUPTIONS AND EXPEDITE
REPAIR.
3. MATERIALS REMOVED AS REQUIRED BY THIS CONTRACT SHALL REMAIN THE PROPERTY OF THE OWNER.
MATERIALS SUITABLE FOR REUSE SHALL BE MADE AVAILABLE FOR OWNER'S INSPECTION. MATERIAL NOT
SELECTED FOR RETENTION BY THE OWNER AND ALL DEBRIS SHALL BE DISPOSED OF BY THE GENERAL
CONTRACTOR.
SECTION 26 00 50 - BASIC ELECTRICAL MATERIALS AND METHODS
1. PROVIDE ALL ELECTRICAL COMPONENTS, PARTS AND MATERIALS SHOWN AND REQUIRED BY CODE FOR
EQUIPMENT FURNISHED UNDER THIS AND OTHER DIVISIONS OF THESE SPECIFICATIONS TO FORM A
COMPLETE AND OPERABLE SYSTEM.
2. MATERIALS SHALL BE NEW, OF THE BEST QUALITY AND FREE FROM DEFECTS AND DESIGNED TO ENSURE
SATISFACTORY OPERATION IN ENVIRONMENTAL CONDITIONS WHICH PREVAIL. ALL ELECTRICAL
COMPONENTS SHALL BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
3. SUBMITTALS REQUIRED ONLY WHERE SPECIFIED BELOW. WHERE SUBMITTALS ARE REQUIRED, THE
PARTICULAR COMPONENT BEING SUBMITTED SHALL BE CLEARLY IDENTIFIED. GENERIC CATALOG PAGES WILL
NOT BE ACCEPTABLE. ENGINEER TO REVIEW.
4. WHERE EXISTING COMPONENTS ARE IDENTIFIED FOR REUSE, VERIFY SUITABILITY AND CONDITION. ENSURE
COMPONENTS ARE SIZED APPROPRIATELY FOR THE LOAD TO BE SERVED AND TEST TO VERIFY CONDITION.
CONTRACTOR TO PROVIDE AND REPLACE ALL COMPONENTS THAT CANNOT BE REUSED.
5. INSTALL MATERIAL AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS,
INSTRUCTIONS AND INSTALLATION DRAWINGS. WORKMANSHIP SHALL COMPLY WITH THE NATIONAL
ELECTRICAL CONTRACTORS ASSOCIATION (NECA) NATIONAL ELECTRICAL INSTALLATION STANDARDS.
6. PROVIDE FIREPROOFING FOR ALL PENETRATIONS OF FIRE RATED ASSEMBLIES MADE UNDER THIS CONTRACT.
FIREPROOFING TO BE REVIEWED AND APPROVED BY MCKINSTRY.
7. ALL NEW OR REUSED ELECTRICAL EQUIPMENT MOUNTED OUTDOORS, INCLUDING VARIABLE FREQUENCY
DRIVES, SHALL BE INSTALLED IN SUITABLE WEATHERPROOF ENCLOSURES AND PROTECTED AGAINST
TEMPERATURE EXTREMES OUTSIDE MANUFACTURER'S RECOMMENDATIONS.
SECTION 26 0513 - MEDIUM VOLTAGE WIRES AND CABLES
1. SUBMITTAL: REQUIRED
2. MANUFACTURERS: OKONITE, SOUTHWIRE, PRYSMIAN, GENERAL CABLE
3. PRODUCTS:
A. SINGLE COPPER CABLES. ALUMINIUM MAY BE CONSIDERED WITH ENGINEERING APPROVAL
B. ETHYLENE PROPYLENE RUBBER (EPR), RATED AT 105°C , 133%
C. 5 MIL BARE COPPER TAPE, HELICAL WITH 12-1/2% OVERLAP
D. POLYVINYL CHLORIDE (PVC) LISTED AS TYPE MV-105 PER UL 1072
4. EXECUTION:
A. INSTALL WIRING IN RACEWAY WITH GROUND CONDUCTOR, 1/0 MINIMUM, COPPER, 600V, THHW, GREEN JACKET
B. ALL SPLICES AND TERMINATIONS SHALL BE MADE BY EXPERIENCED ELECTRICIANS USING PRE -PACKAGED
TERMINATION KITS. ALLOWABLE MANUFACTURES INCLUDE; ELASTIMOLD, 3M, OR EQUAL.
C. ALL WORK CARRIED THROUGH TO COMPLETION WITHOUT INTERRUPTION
SECTION 26 0519 - LOW VOLTAGE WIRES AND CABLES
1. SUBMITTAL: REQUIRED
2. PRODUCTS:
A. COPPER, INSULATED FOR 600V. CONDUCTORS SMALLER THAN #12 SHALL NOT BE USED.
B. CONDUCTOR INSULATION TO BE TYPE THWN/THHN 90°C.
C. TYPE NM OR "ROMEX" CONDUCTORS SHALL NOT BE USED.
D. DESIGN ASSUMES THAT CONDUCTOR INSULATION IN RACEWAYS EXPOSED TO HEATING BY THE SUN
SHALL BE XHHW-2 90°C. CONTACTOR MAY USE THWN/THHN ONLY WHERE PROPER TEMPERATURE
ADJUSTMENT FOR SOLAR HEATING HAS BEEN MADE PER NEC 310.15(B)(3)(c).
E. ALUMINUM CONDUCTORS NOT PERMITTED FOR ANY BRANCH CIRCUIT. ALUMINUM MAY BE
CONSIDERED FOR LARGE FEEDERS WITH ENGINEERING APPROVAL.
3. EXECUTION:
A. INSTALL WIRING IN RACEWAY UNLESS SPECIFICALLY AUTHORIZED OTHERWISE.
B.
C.
D.
E.
F.
G.
CONDUCTORS FROM #12 TO #1 OR USED IN CIRCUITS RATED 100A OR LESS SHALL BE SIZED AS 60°C
UNLESS TERMINATIONS AT BOTH ENDS OF THE CONDUCTOR ARE RATED AT 75°C.
CONDUCTORS LARGER THAN #1 OR FOR CIRCUITS RATED OVER 100A SHALL BE SIZED AS 75°C
CONDUCTORS.
90°C AMPACITY MAY BE USED FOR AMPACITY CORRECTION AND/OR ADJUSTMENT PER NEC
110.14(C)(1).
UNLESS OTHERWISE NOTED, BRANCH CIRCUITS SHALL BE (2) #12 WITH (1) #12 EGC IN %2" CONDUIT.
EGC MAY BE SHARED BY THE UNGROUNDED CONDUCTORS IN A MULTI -WIRE BRANCH CIRCUIT BUT
EACH PHASE CONDUCTOR MUST HAVE A DEDICATED NEUTRAL. WHEN APPROVED BY THE OWNER,
SHARED NEUTRALS ARE ALLOWED WHEN PROTECTED BY A MULTI -POLE OVERCURRENT PROTECTION
DEVICE. DISCONNECTING MEANS MUST COMPLY WITH NEC 210.4(B).
LONGER BRANCH CIRCUITS: BRANCH CIRCUITS INDICATED TO BE #12 AWG (BY DESIGNATION OR
STANDARD SYMBOL) ON PLANS AND WHICH ARE GREATER IN CONDUCTOR LENGTH (MEASURED FROM
PANEL BOARD TO BEGINNING OF THE LAST TAP) THAN THE FOLLOWING SCHEDULE SHALL BE CHANGED
TO #10 AWG:
I. 120 VOLT: 75 FT.
II. 277 VOLT: 150 FT.
SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
1. SUBMITTAL: NOT REQUIRED
2. GROUNDING ELECTRODE SYSTEM:
A. SOLIDLY -GROUNDED ELECTRODE SYSTEM SHALL BE PROVIDED TO GROUND THE SERVICE ENTRANCE
EQUIPMENT. GROUNDING ELECTRODE SYSTEM SHALL BE PROVIDED AS SHOWN ON THE DRAWINGS
AND IN ACCORDANCE WITH THE NEC.
B. ALL MATERIALS LISTED OR LABELED BY NRTL. EXOTHERMIC OR NON -REVERSIBLE COMPRESSION
FITTINGS.
C. GROUND CONDUCTORS BROUGHT THROUGH THE FLOOR OR WALLS SHALL BE IN PVC CONDUIT
SLEEVES. GROUND CONDUCTORS SHALL NOT BE LOCATED IN TRAFFIC AREAS OR WHERE SUBJECT TO
DAMAGE.
D. TEST USING THE THREE-POINT FALL OF POTENTIAL METHOD. INSTALL ADDITIONAL GROUNDING
ELECTRODES AS REQUIRED TO REACH A RESISTANCE OF 10 OHMS OR LESS TO GROUND.
3. EQUIPMENT GROUNDING CONDUCTOR:
A. EQUIPMENT GROUND CONDUCTOR (EGC) FOR EACH NEW FEEDER AND BRANCH CIRCUIT SHALL BE A
SEPARATE WIRE IN THE RACEWAY AND SIZED IN ACCORDANCE WITH NEC.
B. USE OF METALLIC RACEWAY AS EQUIPMENT GROUNDING CONDUCTOR SHALL BE PERMITTED ONLY BY
PRIOR WRITTEN APPROVAL OF ENGINEER AND OWNER.
C. WHERE NEW CONDUCTORS ARE BEING RE -PULLED IN EXISTING METALLIC CONDUIT SERVING AS EGC,
PROVIDE A SEPARATE WIRE EGC WITH THE NEW CONDUCTORS UNLESS PRECLUDED BY CONDUIT SIZE.
SECTION 26 05 29 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
1. SUBMITTAL: NOT REQUIRED
2. PRODUCTS: BRACKETS, FRAMES, AND HANGERS FABRICATED FROM STANDARD ROLLED STRUCTURAL STEEL
SHAPES OR PREFABRICATED STRUCTURAL SYSTEMS.
3. EXECUTION:
A. INSTALL SO THAT SUPPORT INSTALLATION DOES NOT WEAKEN OR OVERLOAD BUILDING STRUCTURE.
B. ELECTRICAL SYSTEM HANGERS AND SUPPORTS SHALL BE INDEPENDENT OF PARTITION AND CEILING
SYSTEM SUPPORTS.
C. NO OTHER TRADES SHALL HANG OR SUPPORT HVAC EQUIPMENT, DUCTWORK, OR PIPING FROM
ELECTRICAL SYSTEM HANGERS AND SUPPORTS.
D. CONTRACTOR SHALL COMPLY WITH ALL SEISMIC ANCHORAGE AND BRACING REQUIREMENTS IN
COMPLIANCE WITH BUILDING CODES. PROVIDE DOCUMENTATION OF CALCULATIONS AND DETAILS TO
ENGINEER AND/OR AHJ FOR REVIEW AND APPROVAL PRIOR TO INSTALLATION.
E. ANY MOUNTING BRACKETS THROUGH THE EXTERIOR WALLS OR THROUGH HISTORIC MATERIALS
SHALL BE PLANNED AND EXECUTED TO PROTECT HISTORIC ELEMENTS.
SECTION 26 05 33 - RACEWAY AND BOXES
1. SUBMITTAL: NOT REQUIRED, EXCEPT FOR SURFACE METAL RACEWAY AS NOTED BELOW.
2. PRODUCTS:
A. FLEXIBLE CONDUIT: INDUSTRY STANDARD (ALUMINUM OR THIN WALL FLEX NOT PERMITTED).
PROVIDE TO EQUIPMENT SUBJECT TO VIBRATION, MOVEMENT OR LIGHTING FIXTURES.
B. LIQUID TIGHT FLEXIBLE CONDUIT: USE FOR MOTORS, TRANSFORMERS, PUMPS OR EQUIPMENT
REGULARLY WASHED DOWN OR IN DAMP LOCATIONS.
C. RIGID METAL CONDUIT (RMC): USE GALVANIZED STEEL UNLESS OTHERWISE INDICATED. ALUMINUM
RMC WHERE INDICATED OR IN SIZES 4" AND LARGER WHERE APPROVED BY ENGINEER.
D. RIGID NONMETALLIC CONDUIT (RNC): PVC-40 PERMITTED IN UNDERGROUND APPLICATIONS AND IN
CONCRETE DUCT BANKS. UNDERGROUND TURNS OF 90 DEGREES OR GREATER SHALL BE MADE USING
LONG RADIUS WITH A MINIMUM TURN RADIUS OF TEN TIMES THE CONDUIT DIAMETER.
E. SURFACE METAL RACEWAY: PLASTIC RACEWAY NOT PERMITTED. WIREMOLD OR EQUAL. SUBMITTAL
REQUIRED.
F. CONDULETS:
1. OBROUND TYPE FOR AND 1" SIZES
2. FORM 7 FOR 11/2" THROUGH 2" SIZES
3. LBD TYPE FOR 2" AND LARGER SIZES
G. ELECTRICAL GUTTERS AND PULL BOXES: CODE -GAUGE GALVANIZED OR PAINTED SHEET STEEL. FLUSH
OR SURFACE MOUNTED AS INDICATED.
3. EXECUTION:
A. DEVICE MOUNTING HEIGHTS TO THE TOP OF THE BOX:
OUTLET MOUNTING HEIGHT (TYPICAL)
SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE
ARCHITECTURAL DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR REQUIRED, THEN
LOCATE OUTLETS AS NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE FINISHED FLOOR
TO THE UPPER OR LOWER EDGE OF THE BOX AS NOTED BELOW.
RECEPTACLES
15" AFF TO BOTTOM OF BOX
LIGHT SWITCHES
48" AFF TO TOP OF BOX
PANELBOARDS
72" AFF TO TOP OF PANELBOARE
TELEPHONE OUTLET - DESK
15" AFF TO BOTTOM OF BOX
TELEPHONE OUTLET - WALL
48" AFF TO TOP OF BOX
COMPUTER OUTLET - DESK
15" AFF TO BOTTOM OF BOX
. COORDINATE LOCATIONS WITH WORK OF OTHER TRADES TO AVOID CONFLICTS, MAINTAIN FIRE
RATINGS, AND MAINTAIN ACCESS.
SECTION 26 05 53 - IDENTIFICATION ELECTRICAL SYSTEMS
1. SUBMITTAL: NOT REQUIRED
2. SCOPE: LABEL RECEPTACLES, JUNCTION BOXES, DISCONNECTS, MCC CUBICLES AND OTHER EQUIPMENT.
(MATCH EXISTING LABELS ON ASSOCIATED EQUIPMENT)
3. PRODUCTS:
A. PROVIDE NEATLY TYPED PANEL SCHEDULES INSIDE EACH EXISTING PANEL BOARD AFFECTED BY THIS
CONTRACT. LETTERS SHALL BE BLACK AND A MINIMUM OF 1/8" HIGH ON A WHITE BACKGROUND.
B. NAMEPLATES TO BE ENGRAVED AND CONSTRUCTED OF 1/260 INCH THICK PHENOLIC LAMINATED
MATERIAL. LETTERS SHALL BE A MINIMUM OF HIGH.
4. EXECUTION: SECURELY ATTACH PHENOLIC LABELS AND NAMEPLATES WITH SCREWS OR RIVETS.
SECTION 26 2416 - PANELBOARDS
1. SUBMITTALS: REQUIRED.
2. MANUFACTURERS: GE, EATON, SQUARE-D, OR SIEMENS
3. PRODUCTS:
A. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE ONLY
B. SERIES RATED EQUIPMENT IS NOT ACCEPTABLE
C. 100% NEUTRAL BUS UNLESS OTHERWISE NOTED IN THE DRAWINGS
4. EXECUTION:
A. PANEL BOARDS SHALL BE INSTALLED IN STRICT ACCORDANCE TO THE NEC
SECTION 26 2413 - SWITCHBOARDS
1. SUBMITTALS: REQUIRED.
2. MANUFACTURERS: GE, EATON, SQUARE-D, OR SIEMENS
3. PRODUCTS:
A. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE ONLY
B. SERIES RATED EQUIPMENT IS NOT ACCEPTABLE
C. 100% NEUTRAL BUS UNLESS OTHERWISE NOTED IN THE DRAWINGS
4. EXECUTION:
A. PANEL BOARDS SHALL BE INSTALLED IN STRICT ACCORDANCE TO THE NEC
SECTION 26 27 26 - WIRING DEVICES
1. SCOPE: PROVIDE WIRING DEVICES AS INDICATED.
2. SUBMITTALS: NOT REQUIRED.
3. PRODUCTS:
A. ALL DEVICES TO BE 20 AMP SPECIFICATION GRADE, UNLESS OTHERWISE NOTED.
B. ALL ELECTRICAL ENCLOSURES AND CABINETS TO BE NEMA RATED FOR APPROPRIATE APPLICATION.
C. ALL WIRING DEVICES SHALL BE NEW AND RATED FOR THE SERVICE IN WHICH THEY ARE TO BE USED.
4. EXECUTION: REFER TO SECTION 26 05 33 FOR BOX MOUNTING HEIGHTS.
SECTION 26 28 00 - LOW VOLTAGE CIRCUIT PROTECTIVE DEVICES
1. SCOPE: PROVIDE DISCONNECTS, FUSED AND UNFUSED, SHOWN AND REQUIRED BY CODE FOR EQUIPMENT
FURNISHED UNDER THIS AND OTHER DIVISIONS OF THESE SPECIFICATIONS.
2. SUBMITTALS: REQUIRED FOR STANDALONE (IE. OUTSIDE OF PANEL BOARDS AND SWITCHBOARDS)
OVERCURRENT PROTECTION DEVICES RATED 100A AND LARGER.
3. PRODUCTS:
A. SUITABLY HORSEPOWER RATED FOR MOTOR LOADS.
B. MANUFACTURERS:
1. FUSES: BUSSMANN, LITTELFUSE, OR MERSEN
2. BREAKERS: GE, EATON, SQUARE D, OR SIEMENS.
C. FUSES:
1. CLASS R REJECTION TYPE.
2. CLASS K1 FOR ALL EXCEPT MOTOR CIRCUITS
3. CLASS K5 MOTOR LOAD TYPE FOR MOTORS.
D. MOLDED CASE CIRCUIT BREAKERS OF THERMAL -MAGNETIC OR MAGNETIC ONLY TYPE WHERE
INDICATED. BOLT -IN TYPE ONLY.
E. EACH BREAKER TO BE "FULLY RATED" FOR THE FAULT CURRENT AVAILABLE AT ITS LINE -SIDE TERMINAL
(SERIES RATINGS NOT ACCEPTABLE).
4. EXECUTION:
A. INSTALL IN APPROPRIATE EQUIPMENT WITH TRIP RATINGS AS SHOWN.
B. SECURE SOLIDLY TO WALL OR APPROVED MOUNTING FRAME.
C. PROVIDE ENGRAVED PHENOLIC NAMEPLATES WITH THE FOLLOWING INFORMATION: LOAD AND AREA
SERVED, VOLTAGE, PHASE, AND FUSE SIZE AND TYPE
SECTION 26 2913 - MOTOR CONTROLLERS
1. MANUFACTURERS: GE, EATON, SQUARE D, OR SIEMENS.
2. NEMA RATED.
3. SUBMITTALS: NOT RrEQUIRED.
4. MOTOR CONTROLLERS TO HAVE INTEGRAL CONTROL TRANSFORMER AND HAND -OFF -AUTO SELECTOR
SWITCH.
5. UNDERVOLTAGE AND PHASE LOSS PROTECTION WHERE CONSISTENT WITH CONTROL SCHEME.
6. MANUAL STARTERS: SHALL BE EQUAL TO SQUARE D, CLASS 2510 FG-1, WITH PILOT LIGHT, OR APPROVED
EQUAL.
7. MCC AND MCC DISCONNECTS SHALL BE COMPATIBLE WITH EXISTING MCC.
SECTION 26 29 23 - VARIABLE FREQUENCY AC DRIVES
1. SEE VARIABLE FREQUENCY DRIVE SCHEDULE(S) IN ELECTRICAL DRAWINGS FOR SPECIFICATIONS.
2. SUBMITTALS: REQUIRED.
3. WHERE INDICATED IN THE CONTRACT DOCUMENTS, CONTRACTOR SHALL DETERMINE MOST APPROPRIATE
METHOD AND MATERIALS FOR REPLACING EXISTING MOTOR STARTERS WITH VARIABLE FREQUENCY DRIVES
(VFD). COORDINATE WITH OWNER TO DETERMINE VFD LOCATION. PROVIDE AND INSTALL ALL NECESSARY
COMPONENTS AND SYSTEM COMMISSIONING TO PROVIDE A COMPLETE AND OPERABLE SYSTEM
4. WHERE REUSING AN EXISTING MOTOR STARTER TO FEED A VFD, REMOVE THE CONTACTOR, OVERLOADS,
MOTOR CIRCUIT PROTECTOR OR INSTANTANEOUS TRIP BREAKER AND PROVIDE AN APPROPRIATELY SIZED
THERMOMAGNETIC CIRCUIT BREAKER TO MATCH THE VFD.
VIEWED FOR-
C°NFPA 70 - NECIT"H
JUN 12 2019
City of Tukwila
BUILDING DIVISION
RECEDED
CITY OF TUKWILA
JUN 032019
PERIT CENTER
fe Of Tour Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS.
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
0
0
0
c
a
0
w
E.
0
7
ELECTRICAL SHEET I
SPECIFICATION
SHEET NUMBER:
-002
AFTER
PANEL: PNL MA
LOCATION: MECH M02
SUPPLY FROM: SWBD DP1
MTG / ENCL: SURFACE/NEMA 1
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM. 480Y/277V,30,4W
GROUND BUS: Yes
SPD: No
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
3
5
HP-15
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-16
2
4
6
7
9
11
HP-17
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-18
8
10
12
13
15
17
HP-19
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-20
14
16
18
19
21
23
HP-09
20
3
2.41
1.63
2.41
1.63
2.41
1.63
3
20
HP-10
20
22
24
25
SPARE
20
1
0
1.63
27
SPARE
20
1
0
1.63
29
SPARE
20
1
0
1.63
3
20
HP-12
26
28
30
31
33
35
HP-21
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-14
32
34
36
37
SPARE
20
1
0
0
1
20
SPARE
38
39
SPARE
20
1
0
0
1
20
SPARE
40
41
SPARE
20
1
0
0
1
20
SPARE
42
43
45
47
FEED THRU TO PNL MB
0
3
44
17.11
46
17.11
48
TOTAL AMPS: 129.41
129.41
129.41
PHASE A CONNECTED LOAD: 35.85 kVA
PHASE B CONNECTED LOAD: 35.85 kVA
PHASE C CONNECTED LOAD: 35.85 kVA
129.4 A
129.41
129.41
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
R
RECEPTACLES
0.00
0.00%
0.00
L
LIGHTING
0.00
0.00%
0.00
CONNECTED LOAD:
107.5 kVA
EQUIPMENT
107.54
100.00%
107.54
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
107.54
DEMAND:
129.35
Notes:
1. NOTE 1...
PANEL: PNL MC
LOCATION: MECH M02
SUPPLY FROM: SWBD DP1
MTG / ENCL: SURFACE/NEMA 1
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM 480Y/277V,30,4W
GROUND BUS: Yes
SPD: No
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
SPARE
20
1
0
1.63
3
SPARE
20
1
0
1.63
5
SPARE
20
1
0
1.63
3
20
HP-30
2
4
6
7
9
11
HP-33
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-45
8
10
12
13
15
17
19
HP-46
SPARE
20
20
3
1
2.41
0
1.63
2.41
2.41
1.63
2.41
1.63
21
SPARE
20
1
0
2.41
23
SPARE
20
1
0
2.41
3
3
20
20
HP-47
HP-49
14
16
18
20
22
24
25
27
29
HP-08
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-11
26
28
30
31
33
35
HP-24
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-41
32
34
36
37
SPARE
20
1
0
0
1
20
SPARE
38
39
SPARE
20
1
0
0
1
20
SPARE
40
41
SPARE
20
1
0
0
1
20
SPARE
42
43
45
47
FEED THRU TO PNL MD
R; E
0
3
19.39
44
19.48
46
13.78
48
TOTAL AMPS: 137.66
137.99 114.29
PHASE A CONNECTED LOAD: 37.27 kVA
PHASE B CONNECTED LOAD: 37.36 kVA
PHASE C CONNECTED LOAD: 31.66 kVA
137.7 A
137.99
114.29
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
R
RECEPTACLES
1.98
100.00%
1.98
L
LIGHTING
0.00
0.00%
0.00
CONNECTED LOAD:
106.3 kVA
PANEL: PNL P7
LOCATION: MECH M02
SUPPLY FROM: TMD2
MTG / ENCL: SURFACE/NEMA 1
FEEDER...
LUG SIZE:
AFTER
THORNDYKE ELEMENTARY SCHOOL WSHP
REPLACEMENT
SYSTEM: 208Y/120V,30,4W
GROUND BUS: Yes
SPD: Yes
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 225 A
05/30/19
MAINS TYPE: MCB
MCB RATING: 100
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
3
20
2
1.49
0.88
1.49
0.88
2
20
2
4
5
SPARE
20
1
0
0
1
20
SPARE
6
7
9
HP-43
20
2
1.49
0.52
1
20
EF 03
8
1.49
0.84
1
20
10
11
SPARE
20
1
0
0.53
1
20
HWC 2
12
13
15
20
2
0.88
0.3
1
20
EF 4
14
0.88
0.32
1
20
EF 6
16
17
REC. IN ATTIC
20
1
0.72
0.32
20
EF 5
18
19
REC. IN ATTIC
20
1
0.72
0.08
20
EF 7
20
21
REC. IN ATTIC
20
1
0.54
0.32
20
EF 8
22
23
SPARE
20
1
0
0
1
20
SPARE
24
25
SPARE
20
1
0
0.84
1
20
26
27
SPARE
20
1
0
0.53
1
20
28
29
SPARE
20
1
0
0
1
20
SPARE
30
31
SPACE
0
0
1
20
SPARE
32
33
SPACE
0
0
1
20
SPARE
34
35
SPACE
0
0
20
SPARE
36
37
39
41
SPARE
20
3
0
0
20
SPARE
38
0
0
20
SPARE
40
0
0
20
SPARE
42
TOTAL AMPS: 67.03
67.78
13.08
PHASE A CONNECTED LOAD: 7.18 kVA
PHASE B CONNECTED LOAD: 7.27 kVA
PHASE C CONNECTED LOAD: 1.57 kVA
67.78
13.08
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
RECEPTACLES
1.98
100.00%
1.98
LIGHTING
0.00
0.00%
0.00
CONNECTED LOAD:
16 kVA
EQUIPMENT
14.04
100.00%
14.04
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
16.02
EXISTING
0.00
0.00%
0.00
DEMAND:
44.47
Notes:
PANEL: PNL MB
LOCATION: MECH MO2
SUPPLY FROM: PNL MA
MTG / ENCL: SURFACE/NEMA 1
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM. 480Y/277V,30,4W
GROUND BUS: Yes
SPD: No
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
3
5
SPARE
20
3
0
1.63
0
1.63
0
1.63
3
20
2
4
6
7
9
11
HP-26
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-27
8
10
12
13
15
17
HP-28
20
3
2.41
1.63
2.41
1.63
2.41
1.63
3
20
HP-31
14
16
18
19
21
23
HP-35
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-38
20
22
24
25
27
29
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
HP-22
26
28
30
31
SPARE
20
1
0
1.63
33
SPARE
20
1
0
1.63
35
SPARE
20
1
0
1.63
3
20
32
34
36
37
SPARE
20
1
0
0
1
20
SPARE
38
39
SPARE
20
1
0
0
20
SPARE
40
41
SPARE
20
1
0
0
20
SPARE
42
TOTAL AMPS: 61.76
61.76
61.76
PHASE A CONNECTED LOAD: 17.11 kVA
PHASE B CONNECTED LOAD: 17.11 kVA
PHASE C CONNECTED LOAD: 17.11 kVA
61.76
61.76
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
RECEPTACLES
0.00
0.00%
0.00
LIGHTING
0.00
0.00%
0.00
CONNECTED LOAD:
51.3 kVA
EQUIPMENT
51.32
100.00%
51.32
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
51.32
DEMAND:
61.73
Notes:
PANEL: PNL MD
LOCATION: MECH MO2
SUPPLY FROM: PNL MC
MTG / ENCL: SURFACE/NEMA 1
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM 480Y/277V,30,4W
GROUND BUS: Yes
SPD: No
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
3
5
HP-37
20
3
1.63
1.63
1.63
1.63
1.63
1.63
3
20
2
4
6
7
SPARE
20
1
0
1.63
9
11
13
20
3
1.63
2.41
1.63
1.63
1.63
1.63
15
17
19
20
3
1.63
2.41
1.63
2.41
3
3
20
20
HP-40
8
10
12
14
16
18
1.63
1.63
21
SPARE
20
1
0
1.63
23
SPARE
20
1
0
1.63
3
20
HP-44
20
22
24
25
SPARE
20
0
0
1
20
SPARE
26
27
SPARE
20
1
0
0
1
20
SPARE
28
29
SPARE
20
1
0
0
1
20
SPARE
30
31
33
35
XFMR FOR PANEL "P6"
125
3
0
0
1
20
SPARE
32
0
0
1
20
SPARE
34
0
0
SPACE
36
37
39
41
XFMR TP7 FOR PNL P7
R; E
60
3
7.18
0
SPACE
38
7.27
0
SPACE
40
1.57
0
SPACE
42
TOTAL AMPS: 73.11
73.44
49.74
PHASE A CONNECTED LOAD: 19.39 kVA
PHASE B CONNECTED LOAD: 19.48 kVA
PHASE C CONNECTED LOAD: 13.78 kVA
73.1 A
73.44
49.74
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
RECEPTACLES
1.98
100.00%
1.98
LIGHTING
0.00
0.00%
0.00
CONNECTED LOAD:
52.6 kVA
EQUIPMENT
50.66
100.00%
50.66
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
GENERAL NOTES
A. UNLESS OTHERVVISE NOTED, BOLD TEXT ON EXISTING PANEL SCHEDULES INDICATES
WORK THAT IS TO BE DEMO'D. BOLD TEXT ON NEW PANEL SCHEDULES INDICATES
NEW WORK. NEW BREAKERS SHALL HAVE AIC RATINGS MATCHING THE AIC RATING
OF THE EXISTING BREAKERS IN PANEL.
B. ALL PANEL SCHEDULES ON THIS SHEET ARE EXISTING PANELS, AND REPRESENT THE
STATE OF THE PANELS AFTER COMPLETION OF THIS PROJECT.
VI WED FO
COMPLVSNCE WITH
NFPA 70 - NEC
JUN 1 2 2019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
PERMIT CENTER
inStrY
le Of Your Building
McKINSTRY Co, LLC
SEATTLE:
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL PANEL
SCHEDULES
C:IData SethSlRevit Local1201149-Thomdyke Elementary School_v19_SethSLJED9,rvt
EQUIPMENT
104.30
100.00%
104.30
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
106.28
DEMAND:
127.84
Notes:
KITCHEN
0.00
0.00
DEMAND LOAD:
52.64
DEMAND:
63.32
Notes:
P7
MA
MB
MC
MD
ELR- OHO
SHEET NUMBER:
E-01 3
EL
CO
6.
PANEL: (E) PNL LA SEC 1 & 2
LOCATION: ROOM 114
SUPPLY FROM: SWBD DP1
MTG / ENCL: SURFACE/NEMA 1
BEFORE
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM. 480Y/277V,30,4W
GROUND BUS: Yes
SPD: Yes
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
C
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
LTS - GYMNASIUM
L
20
1
2.4
5.65
3
LTS - GYMNASIUM
L
20
1
2.4
5.65
5
LTS-102103118
L
20
1
1.8
5.65
3
20
TVSS
2
4
6
7
LTS -105
L
20
1
2.82
4.84
9
UNKNOWN
L
20
1
2.34
4.84
11
UNKNOWN
L
20
1
3.3
4.84
3
20
E.
(E) HP-06
8
10
12
13
LTS - RM 104
L
20
1
2.4
1.38
15
LTS - RM 104
L
20
1
3.3
1.38
17
19
21
FC-01
20
3
0.9
1.38
3
20
(E) HP-03
14
16
18
0.9
2.63
0.9
2.63
23
SPARE
20
1
0
2.63
3
20
(E) HP-04
20
22
24
25
27
29
(E) HP-05
20
3
4.84
2.66
4.84
2.66
4.84
2.66
3
20
(E) HP-07
26
28
30
31
33
35
FC-01
E
20
3
1.33
1.94
1.33
1.94
1.33
1.94
3
20
TVSS
32
34
36
37
39
41
43
45
47
CWP-01
(E) HP-01
20
20
3
3
6.62
5.4
4.85
5.4
6.62
5.4
4.85
5.4
6.62
5.4
4.85
5.4
3
3
20
20
CWP-02
(E) HP-02
38
40
42
44
46
48
49
SPACE
0
0
51
SPACE
0
0
53
SPACE
0
0
3
20
SPARE
50
52
54
55
57
59
SPARE
20
3
0
0
SPACE
56
0
0
SPACE
58
0
0
SPACE
60
TOTAL AMPS: 203.84 205.35 193.34
PHASE A CONNECTED LOAD: 56.07 kVA
PHASE B CONNECTED LOAD: 56.49 kVA
PHASE C CONNECTED LOAD: 53.55 kVA
203.8 A
205.35
193.34
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
R
RECEPTACLES
0.00
0.00%
0.00
L
LIGHTING
20.76
125.00%
25.95
CONNECTED LOAD:
166.1 kVA
EQUIPMENT
145.36
100.00%
145.36
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
AFTER
PANEL: PNL LA SEC 1 &2
LOCATION: ROOM 114
SUPPLY FROM: SWBD DP1
MTG I ENCL: SURFACE/NEMA 1
THORNDYKE ELEMENTARY SCHOOL WSHP REPLACEMENT 05/30/19
SYSTEM. 480Y/277V,30,4W
GROUND BUS: Yes
SPD: Yes
SCCR: UNKNOWN
BUS MATERIAL: CU
BUS RATING: 400 A
MAINS TYPE: MLO
CKT
DESCRIPTION
LOAD
AMPS
POLES
A
POLES
AMPS
LOAD
DESCRIPTION
CKT
1
LTS - GYMNASIUM
L
20
1
2.4
5.65
3
LTS - GYMNASIUM
L
20
1
2.4
5.65
5
LTS-102103118
L
20
1
1.8
5.65
3
20
TVSS
2
4
6
7
LTS -105
L
20
1
2.82
4.24
9
UNKNOWN
L
20
1
2.34
4.24
11
UNKNOWN
L
20
1
3.3
4.24
3
20
HP-06
8
10
12
13
LTS - RM 104
L
20
1
2.4
1.63
15
LTS - RM 104
L
20
1
3.3
1.63
17
19
21
FC-01
20
3
0.9
1.63
3
20
HP-03
14
16
18
0.9
2.41
0.9
2.41
23
SPARE
20
1
0
2.41
3
20
E
HP-04
20
22
24
25
27
29
31
33
35
HP-05
FC-01
20
20
3
3
4.32
2.41
1.94
4.32
1.33
2.41
1.94
4.32
1.33
2.41
1.94
3
3
20
20
HP-07
TVSS
26
28
30
32
34
36
37
39
41
20
3
6.62
4.85
6.62
4.85
6.62
4.85
3
20
CWP-02
38
40
42
43
45
47
49
SPACE
20
3
5.45
0
5.45
0
5.45
5.45
5.45
5.45
51
SPACE
0
0
53
SPACE
0
0
3
3
20
20
HP-02
SPARE
44
46
48
50
52
54
55
57
59
SPARE
20
3
0
0
SPACE
56
0
0
SPACE
58
0
0
SPACE
60
TOTAL AMPS: 199.34
200.86 188.84
PHASE A CONNECTED LOAD: 54.83 kVA
PHASE B CONNECTED LOAD: 55.25 kVA
PHASE C CONNECTED LOAD: 52.31 kVA
200.86
188.84
LOAD CLASSIFICATION
CONNECTED LOAD
DEMAND FACTOR
DEMAND LOAD
PANEL TOTALS
RECEPTACLES
0.00
0.00%
0.00
LIGHTING
20.76
125.00%
25.95
CONNECTED LOAD:
162.4 kVA
EQUIPMENT
141.63
100.00%
141.63
HEATING
0.00
0.00%
0.00
COOLING
0.00
0.00%
0.00
GENERAL NOTES
A. UNLESS OTHERWISE NOTED, BOLD TEXT ON EXISTING PANEL SCHEDULES INDICATES
WORK THAT IS TO BE DEMO'D. BOLD TEXT ON NEW PANEL SCHEDULES INDICATES
NEW WORK NEW BREAKERS SHALL HAVE AIC RATINGS MATCHING THE AIC RATING
OF THE EXISTING BREAKERS IN PANEL.
B. ALL PANEL SCHEDULES ON THIS SHEET ARE EXISTING PANELS, AND REPRESENT THE
STATE OF THE PANELS BEFORE AND AFTER COMPLETION OF THIS PROJECT.
COMPLIANCE WIT'H
JUN 1 2 2019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKIIVILA
JUN 03 2019
PERMIT CENTER
Ye Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL PANEL
SCHEDULES
CO
coI
CD
0
03
Lu
co
co
65
co
CI
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
171.31
DEMAND:
206.06
Notes:
THIS PANEL IS EXPERIENCING A NET LOAD REDUCTION
KITCHEN
0.00
0.00%
0.00
DEMAND LOAD:
167.58
DEMAND:
201.56
Notes:
THIS PANEL IS EXPERIENCING A NET LOAD REDUCTION
PNL LA
SHEET NUMBER:
-014
5/30/2019 6:18:10 PM
r
TO UTILITY
u^
123135
22544 I
3P-1600A
3-1600AF
L
22544
PADMOUNT TRANSFORMER
SERVICE ENTRANCE POINT
UNDERGROUND SECONDARY
CIRCUIT
6 SETS EACH WITH, 3#300KCMIL +
1#300 N + 1#1 G, 3"C.
REMOTE METER
- PANEL "DP1" (277/480V. 3PH, 4W)
1600A BUS-
GENERAL NOTES
A. UNLESS OTHERWISE NOTED, ALL WORK SHOWN ON THIS ONE -LINE IS EXISTING AND
IS NOT AFFECTED BY THIS SCOPE OF WORK.
KEYNOTES
1 ENCLOSED AREAS INDICATE PANELS IMPACTED UNDER SCOPE OF THIS PROJECT.
15KW GENERATOR
WITH SOUND PROOF
ENCLOSURE
3P-400A
j 3-300AF
3", 4-350KCMIL
+ 1 #2 GND
r 16891
I 1
IIL 1J J�
SECTION 1 SECTION 2 I
SPD I- SPD I D
PANEL"LA"
L J
0
1
7 3P-400A
ii 3-300AF
3", 4-350KCMIL
+ 1 #2 GND
118577
FYI
1 1 3P-125A
o-
3P-125A
PANEL "LB"
6472
SPD
480V
1 1/2", 3 #1
+ 1 #6 GND
SPACE
6472 �--�
"TLB1" 75KVA
11]TRANSFORMER
Y;-
120V
208Y 2", 4 #4/0
+ 1 #2 GND
3P-225A 1
2", 4 #4/0
+ 1 #2 GND
I I I
480V
"TLB2" 75KVA
ILYTRANSFORMER
120 J
208Y
;13P-200A
'L I- L_ J-n
T SECTION 1 SECTION 2 t Ej
- SPD SPD
PANEL"P3"
PANEL "P2"
SPD -'
i/ 3P-200A
L 3-200AF
2 1/2", 4 #4/0
+ 1 #2 GND
3P-60A
SPACE
3P-125A
PANEL "LC"
1 1/2", 3 #1
+ 1 #6 GND
480V
' !\.,;1.• ' "TLC1" 75KVA
TRANSFORMER
Y 1
- 120V
208Y
- 2", 4 #4/0
+ 1 #2 GND
9`, 13P-200A
11
- 2", 4 #4/0
+ 1 #2 GND
1",3#6
+ 1 #8 GND
480V
^\• ' "TLC2" 45KVA
Iv TRANSFORMER
120V
208Y
11/4",4#3
+ 1 #8 GND
3P-100A
1 1/4", 4 #3
+ 1 #8 GND
1 1 1 1 1
n-L 1' L_
T SECTION 1 SECTION 2 l
i
SPD ' SPD I- SPD
PANEL"P4"
PANEL"P5"
( 3P-200A
3-200AF
2 1/2", 4 #4/0
+ 1 #2 GND
r
( 3P-400A
3-300AF
3", 4 #350KCMIL
+ 1 #2 GND
1
J
PANEL"MA" PANEL"MB"
L ° �)
PANEL "MC" PANEL "MD"
L_
I / --(1) �l
3P-60A
I
3P-125A I
1 1/2", 3 #1
+ 1 #6 GND
0
3P-200A
13-200AF
SPARE
480V
:`7 "TMD1" 75KVA
TRANSFORMER
120V
208Y 2", 4 #4/0
+ 1 #2 GND
1 ,,13P-225A
Ly_r L 1t
SECTION 2 SECTION 1
SPD --'
PANEL "P6"
2", 4 #4/0
+ 1 #2 GND
SPD
r
1", 3 #6
+ 1 #8 GND
480V
' -1 "TMD2" 45KVA
TRANSFORMER
120V
208Y 1 1/4", 4 #3
+ 1 #8 GND
`1 3P-100A
16-I 0
11/4",4#3
+ 1 #8 GND
M1
L_ 4
SPD
PANEL"P7"
L J
1
% 3P-100A
Cl 3-70AF
1", 3 #6
+ 1 #8 GND
i 3P-200A-
3-200AF
19068 j 480V 19068 1 480V
1-H, "TP1" 45KVA 3670 in,I s ' ' "TK" 112.5KVA
1 1 TRANSFORMER '/•�" I TRANSFORMER
120V = 120V
208Y 208Y 3, 4#350KCMIL
+ 1 #2 GND
13670
2", 3 #1/0
+ 1 #6 GND
PANEL"P1"
ONE LINE DIAGRAM
1 1/2", 4 #1
+ 1 #6 GND
I SPD SPD
E-040
SCALE: NTS
I -313P-300A
1 1
3", 4#350KCMIL
+ 1 #2 GND
r IT�1
1 1 1
n-L ° IJ J-n
SECTION 1 SECTION 2
SPD
PANEL "K"
30AS/3P
3P-30A
3-30AF
30AF/3P ' VI/
1",4#10
+ 1 #10 GND
3",4#10
+ 1 #10 GND
FC-01
PONY FAN
100AS/3P
70AF/3P
FC-01
3P-100A
3-100AF
1",4#4
+ 1 #8 GND
1", 4 #4
+ 1 #8 GND
I
3P-60A
•
3-40AF
1",4#6
+ 1 #8 GND
1 13P-40A
IKI
1",4#6
+ 1 #8 GND
`J
ELEVATOR (20 HP)
' 3P-200A
3-200AF
( 3P-30A
3-30AF
WP
G
71
3P-30A
1"C, 4 #8
+ 1 #8 GND
30A/3P
30AF
I I I
J L_
1"C, 4 #8
+ 1 #8 GND
11024 1
n
AUTOMATIC
TRANSFER SWITCH
3P-100A (ATS-1)
n
1"C, 4 #8
+ 1 #8 GND
3P-30A
SPD -�
PANEL"X1"
864
1"C, 4 #10
+ 1 #10 GND
480V
"TX" 15KVA
T"RANSFORMER
120V
1)208Y 1"C, 4 #6
+ 1 #8 GND
S'Y13P-60A
1 '1
Fy
1"C, 4 #6
+ 1 #8 GND
I_ -I
SPD
PANEL"X2"
R VIEWED FO11
COMNFPLA 70 - NEC
l�
JUN 12 2019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN032019
PERMIT CENTER
ife Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL ONE
LINE
of
0
w
J
Cl)
0)
>I
0
0
U
0
E
0
w
a)
E
0
F-
0)
03>
a)
0
0
SHEET NUMBER:
-04
5/30/2019 6:18:11 PM
BC
2
ED-121
ELECTRICAL DEMOLITION PLAN - MECHANICAL ROOM
SCALE: 1/4" =
' (E) HP-07,i
(BA)
(BB)
(E) HP-05
480/30
/A17.5FLA''
(E) HP-06
// /;
480/30
480/30
9.6FLA
17.5FLA
(E) HP-03,
, (E) HP-04
480/30
5FLA
480/30
9.5FLA
(BC)
0
2'
4'
8'
(3 )
GENERAL NOTES
A. EXISTING BRANCH CIRUCITS SHALL BE USED FOR ALL EQUIPMENT.
B. DARK LINE WEIGHT ON DEMO PLANS INDICATES EXISTING WORK THAT IS TO BE
DEMO'D. DARK LINE WEIGHT ON NEW PLANS INDICATES NEW WORK. ANY
MECHANICAL EQUIPMENT THAT IS BEING DEMO'D SHALL BE DEMO'D BY MC.
KEYNOTES 0
1 PANEL IMPACTED UNDER THIS PROJECT SCOPE.
2 ELECTRICAL CONTRACTOR TO DISCONNECT EXISTING DUCT SMOKE DETECTOR.
RETAIN CONDUIT AND WIRE FOR RE -USE AT NEW LOCATION OF THE SMOKE
DETECTOR.
R' VIEWED FOR
GONFPA70CE WITH
-NEC
JUN 12 Z019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUJKWILA
JUN 03 2019
PERMIT CENTER
le Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19.
SHEET TITLE:
ELECTRICAL DEMO
PLAN MECH RM &
PLATFORM
C:IData SethS\Revit Loca11201149-Thomdyke Elementary School_v19_SethSLJED9.rvt
1
ED-121
ELECTRICAL DEMOLITION PLAN - MECHANICAL PLATFORM NORTH
SCALE: 1/4" = 1'-0"
0
2'
4'
8'
SHEET NUMBER:
121
5/30/2019 6:18:11 PM
(E) HP-29
208/10
9.2FLA
(E) HP-37
480/30
5FLA
(E) HP-34
480/30
9.2FLA
(E) HP-42
(E) HP-36
480/30
480/30
5FLA
5FLA
(E) HP-43
480/30
10.2FLA
(E) HP-45
480/30
5FLA
(E) HP-47
480/30
5FLA
(E) HP-08
480/30
5FLA
(E) HP-24
480/30
5FLA
0
J
(E) HP-35
480/30
5FLA
(E) HP-38
480/30
5FLA
(E) HP-39
480/30
5FLA
AG) (AH)
(E) HP-16
480/30
5FLA
(E) HP-19
480/30
5FLA
(E) HP-48
480/30
5FLA
AJ )
1
ED-122
(E) HP-12
480/30
5FLA
(E) HP-15
480/30
5FLA
(E) HP-17
480/30
5FLA
(E) HP-40
480/30
9.5FLA
(E) HP-44
480/30
5FLA
(E) HP-46
480/30
9.6FLA
CL
J
z
0_
0
J
z
a
(E) HP-33
480/30
5FLA
(E) HP-30
480/30
5FLA
(E) HP-49
480/30
9.6FLA
ELECTRICAL DEMOLITION PLAN - ATTIC EAST
SCALE: 1/8" = 1'-0"
(E) HP-09
480/30
9.6FLA
(E) HP-21
480/30
5FLA
(E) HP-13
480/30
5FLA
0
4'
8'
16'
(E) HP-23
208/10
10.2FLA
(E) HP-11
480/30
5FLA
(E) HP-25
480/30
5FLA
(E) HP-41
480/30
5FLA
(E) HP-26
480/30
5FLA
(E) HP-32
480/30
5FLA
(E) HP-18
480/30
SFLA
(AC)
(E) HP-20
480/30
5FLA
(E) HP-10
480/30
5FLA
(E) HP-14
480/30
5FLA
(E) HP-22
480/30
5FLA
AD) (AE)
(E) HP-27
480/30
5FLA
(E) HP-28
480/30
9.5FLA
(E) HP-31
480/30
5FLA
(8)
8)
( 9 )
GENERAL NOTES
A. EXISTING BRANCH CIRUCITS SHALL BE USED FOR ALL EQUIPMENT.
B. DARK LINE WEIGHT ON DEMO PLANS INDICATES EXISTING WORK THAT IS TO BE
DEMO'D. DARK LINE WEIGHT ON NEW PLANS INDICATES NEW WORK. ANY
MECHANICAL EQUIPMENT THAT IS BEING DEMO'D SHALL BE DEMO'D BY MC.
KEYNOTES 0
1 PANEL IMPACTED UNDER THIS PROJECT SCOPE.
R VIEWWED 6=0
GNFPA 70 NEr
Jim 1 2 2019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN 03 2019
PERMIT CENTER
Ye 0f Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL DEMO
PLAN ATTIC EAST &
WEST
C:1Data SethS\Revit Loca11201149-Thomdyke Elementary School_v19_SethSLJED9.rvt
2
ED-122
ELECTRICAL DEMOLITION PLAN - ATTIC WEST
SCALE: 1/8" = 1'-0"
0
4'
8'
16'
SHEET NUMBER:
2
5/30/2019 6:18:12 PM
MECHANICAL
EQUIPMENT
SCHEDULE
EQUIPMENT INFORMATION
ELECTRICAL INFORMATION
FEEDER
PROVISIONS
MIN. SCCR
SMOKE DETECTOR
COMMENTS
EQUIP. TAG
DESCRIPTION
VOLTAGE
POLES
NEUTRAL
REQUIRED
LOAD
kVA
MCA
MOCP
ALT. POWER
PANEL -CIRCUIT
FEEDER TAG
CONTROLLER TYPE
CONTROLLER
FURNISHED BY
CONTROLLER
INSTALLED BY
DISCONNECT
FURNISHED BY
DISCONNECT
INSTALLED BY
HP-01
HEAT PUMP
480
3
NO
19.7FLA
16.36
21.70
25
No
PNL LA SEC 1 & 2-43,45,47
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
RE -LOCATE EXISTING
HP-02
HEAT PUMP
480
3
NO
19.7FLA
16.36
21.70
25
No
PNL LA SEC 1 & 2-44,46,48
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
RE -LOCATE EXISTING
HP-03
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL LA SEC 1 & 2-14,16,18
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-04
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL LA SEC 1 & 2-20,22,24
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-05
HEAT PUMP
480
3
NO
15.6FLA
12.95
16.90
20
No
PNL LA SEC 1 & 2-25,27,29
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
RE -LOCATE EXISTING
HP-06
HEAT PUMP
480
3
NO
15.3FLA
12.71
16.90
20
No
PNL LA SEC 1 & 2-8,10,12
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
RE -LOCATE EXISTING
HP-07
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL LA SEC 1 & 2-26,28,30
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
BC)
30/1/25
HP-01
480/30
19.7FLA
30/1/25
HP-02
480/30
19.7FLA
SWBD DP1
PNL LA SECTION 1
PNL LA SECTION 2
2
EP-121
ELECTRICAL PLAN - MECHANICAL ROOM (c,
SCALE: 1/4" = 1'-0"
0
2'
4'
8'
HP-07/
/l
( 0 lI( I
HP-05
480/30
HP-06
480/30
30/1/15
41
480/30
8.7FLA
/i
BBB.
/715.6FLA' ; 15 3FLA'
HP-03 ,i
480/30
;%"
HP-04
5.9FLA
480/30
8.7FLA
(BC
2)
GENERAL NOTES
A. EXISTING BRANCH CIRUCITS SHALL BE USED FOR ALL EQUIPMENT.
B. DARK LINE WEIGHT ON DEMO PLANS INDICATES EXISTING WORK THAT IS TO BE
DEMO'D. DARK LINE WEIGHT ON NEW PLANS INDICATES NEW WORK. ANY
MECHANICAL EQUIPMENT THAT IS BEING DEMO'D SHALL BE DEMO'D BY MC.
KEYNOTES 0
1 PANEL IMPACTED UNDER THIS PROJECT SCOPE.
2 ELECTRICAL CONTRACTOR TO EXTEND DUCT SMOKE DETECTOR CIRCUIT TO NEW
LOCATION AND RECONNECT CIRCUIT. MECHANICAL CONTRACTOR TO RELOCATE DUCT
SMOKE DETECTOR.
.., VIEW D FOFC
CONFPMPLI
AC70 - NEECITN
JUU122019
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN Oa 2019
le Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
KEY PLAN
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL PLAN -
MECH RM &
PLATFORM
ari
0
w
3
>1
0
0
0)
E
a)
w
a)
>,
0
E
0
o)0
0
-ct
0)
0)
as
0
0
1
EP-121
ELECTRICAL PLAN - MECHANICAL PLATFORM NORTH
SCALE: 1/4" =1'-0"
0
2'
4'
8'
PERMIT CENTER
SHEET NUMBER:
=121
00
CIS
03
N
O
LO
MECHANICAL
EQUIPMENT
SCHEDULE
EQUIPMENT INFORMATION
ELECTRICAL INFORMATION
FEEDER
PROVISIONS
MIN. SCCR
SMOKE DETECTOR
COMMENTS
EQUIP. TAG
DESCRIPTION
VOLTAGE
POLES
NEUTRAL
REQUIRED
LOAD
kVA
MCA
MOCP
ALT. POWER
PANEL -CIRCUIT
FEEDER TAG
CONTROLLER TYPE
CONTROLLER
FURNISHED BY
CONTROLLER
INSTALLED BY
DISCONNECT
FURNISHED BY
DISCONNECT
INSTALLED BY
HP-08
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-25,27,29
RE -USE EXISTING
WA
N/A
N/A
EC
EC
5KA
WA
HP-09
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL MA-19,21,23
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-10
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-20,22,24
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-11
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-26,28,30
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-12
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-26,28,30
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-13
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-32,34,36
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-14
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-32,34,36
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
WA
HP-15
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-1,3,5
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-16
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-2,4,6
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-17
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-7,9,11
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-18
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-8,10,12
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-19
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-13,15,17
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-20
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-14,16,18
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-21
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MA-31,33,35
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-22
HEAT PUMP
480
3
NO
5.9FLA
4.90 i
7.00
15
No
PNL MB-26,28,30
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-23
HEAT PUMP
208
2
NO
14.3FLA
2.97
17.50
30
No
PNL P7-1,3
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-24
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-31,33,35
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-25
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-2,4,6
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-26
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-7,9,11
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-27
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-8,10,12
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-28
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL MB-13,15,17
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-29
HEAT PUMP
208
2
NO
8.4FLA
1.75
10.20
15
No
PNL P7-2,4
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-30
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-2,4,6
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-31
HEAT PUMP
480
3
NO
5.9FLA
4.90 !
7.00
15
No
PNL MB-14,16,18
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-32
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-25,27,29
RE -USE EXISTING
N/A
N/A
WA
EC
EC
5KA
N/A
HP-33
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-7,9,11
RE -USE EXISTING
N/A
WA
N/A
EC
EC
5KA
N/A
HP-34
HEAT PUMP
208
2
NO
8.4FLA
1.75
10.20
15
No
PNL P7-13,15
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-35
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MB-19,21,23
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-36
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-9,11,13
REUSE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-37
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-1,3,5
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-38
HEAT PUMP
480
3
NO
5.9FLA
4.90 '
7.00
15
No
PNL MB-20,22,24
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-39
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-8,10,12
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-40
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL MD-14,16,18
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-41
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-32,34,36
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-42
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-2,4,6
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-43
HEAT PUMP
208
2
NO
14.3FLA
2.97
17.50
30
No
PNL P7-7,9
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-44
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-20,22,24
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-45
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-8,10,12
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-46
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL MC-13,15,17
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
WA
HP-47
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MC-14,16,18
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-48
HEAT PUMP
480
3
NO
5.9FLA
4.90
7.00
15
No
PNL MD-15,17,19
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-49
HEAT PUMP
480
3
NO
8.7FLA
7.22
10.40
15
No
PNL MC-20,22,24
RE -USE EXISTING
N/A
N/A
N/A
EC
EC
5KA
N/A
HP-29
208/10
8.4FLA
HP-37
480/30
5.9FLA
HP-34
208/10
8.4FLA
HP-42
HP-36
480/30
480/30
5.9FLA
5.9FLA
HP-43
208/10
14.3FLA
HP-45
480/30
5.9FLA
HP-47
480/30
5.9FLA
30/1/15
30/1/15
30/1/15
30/1/15 30/1/15
30/1/15
0
30/1/30
30/1/15
30/1/15
30/1/15
HP-35
480/30
5.9FLA
iAG )
HP-38
480/30
5.9FLA
HP-16
480/30
HP-39
480/30
5.9FLA
HP-19
480/30
5.9FLA1
HP-48
480/30
5.9FLA
HP-12
480/30
5.9FLA
5.9FLA
30/1/15
HP-15
480/30
5.9FLA
HP-17
480/30
5.9FLA
30/1/15
AJ)
1
HP-40
480/30
8.7FLA
HP-44
480/30
5.9FLA
HP-46
480/30
8.7FLA
AK
0
J
a.
ELECTRICAL PLAN - ATTIC EAST
0
J
z
EL
0
J
a.
HP-08
HP-24
480/30
480/30
.'
'
5.9FLA
4
5.9FLA
30/1/15 30/1/15
HP-49
HP-11
HP-33
480/30
5.9FLA
30/1/15
HP-30
480/30
5.9FLA
480/30
8.7FLA
EP-122
SCALE: 1/8" = 1'-0"
HP-09
480/30
8.7FLA
HP-21
480/30
5.9FLA
0
4'
8'
16'
HP-13
480/30
5.9FLA
HP-23
208/10
14.3FLA
480/30
5.9FLA
AL )
HP-25
480/30
5.9FLA
HP-41
480/30
5.9FLA
HP-26
480/30
5.9FLA
HP-32
480/30
5.9FLA
J
z
a-
0
J
z
a.
I AM )
30/1/15
30/1/15
30/1/15
30/1/15
30/1/30
30/1/15
30/1/15
00
HP-18
480/30
5.9FLA
AB) (AC )
HP-20
480/30
5.9FLA
HP-10
480/30
5.9FLA
(AD)
HP-14
480/30
5.9FLA
HP-22
480/30
5.9FLA
(AE)
HP-27
480/30
5.9FLA
HP-28
480/30
8.7FLA
AF)
HP-31
480/30
5.9FLA
9 )
GENERAL NOTES
A. EXISTING BRANCH CIRUCITS SHALL BE USED FOR ALL EQUIPMENT.
B. DARK LINE WEIGHT ON DEMO PLANS INDICATES EXISTING WORK THAT IS TO BE
DEMO'D. DARK LINE WEIGHT ON NEW PLANS INDICATES NEW WORK. ANY
MECHANICAL EQUIPMENT THAT IS BEING DEMO'D SHALL BE DEMO'D BY MC.
KEYNOTES 0
1 PANEL IMPACTED UNDER THIS PROJECT SCOPE.
R VIEWED FO
COMPLIANCE WITH
NFPA 70 - NEC
JUF 12 2019
City of Tukwila
BUILDING DIVISION
CITY OF TUKWILA
J1LA
JUN 03 2019
PERMIT CENTER
fe Of Your Building
McKINSTRY Co, LLC
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
www.mckinst .com
PROJECT:
THORNDYKE
ELEMENTARY
SCHOOL
WSHP
REPLACEMENT
4415 SOUTH 150TH ST.
TUKWILA, WA 98168
CONSULTANTS:
KEY PLAN
\/
REGISTRATION:
ISSUES:
NO
2
4
DATE
05/17/2019
05/31/2019
DESCRIPTION
75% REVIEW SET
PERMIT SET
DESIGNED: SWS
DRAWN: SWS
CHECKED: DS
JOB NO: 201149-003
ISSUED ON: 05/30/19
SHEET TITLE:
ELECTRICAL PLAN
ATTIC EAST & WEST
SHEET NUMBER:
cri.
0
w
-J
0
cn�
a)
0
0
cn
0
E
m
E
0
as
as
U
2
EP-122
ELECTRICAL PLAN - ATTIC WEST
SCALE: 1/8" = 1'-0"
0
4'
8'
16'
2
5/30/2019 6:18:12 PM