Permit PL18-0026 - AT&T - WIRELESS FACILITY
AT&T 0323049057 PARENT FILE PL18-0026 THIS FILE L18-0039 WIRELESS FACILITY/TYPE 1 TO: City of Tukwila Allan Ekberg, Mayor Department of Community Development - Jack Pace, Director June 27, 2018 NOTICE OF DECISION Hannan Rutkosky, Technology Associates (OBO AT&T Wireless) T5 Unison Management, LLC King County Assessor, Accounting Division Agencies with Jurisdiction All Parties of Record This letter serves as a notice of decision and is issued pursuant to TMC 18.104.170 on the following project and permit approval. Protect File Number: Applicant: Type of Permit Applied for: Project Description: Location: Associated Files: Comprehensive Plan Designation/Zoning District: I. PROJECT INFORMATION L18-0039; PL18-0026 Hannan Rutkosky, Technology Associates (OBO AT&T Wireless) Type 1 Wireless Facilities Permit The applicant is proposing modifying the existing building mounted non -concealed wireless communications facility by removing three (3) existing panel antenna, three (3) RRHs and installing six (6) RRHs, three (3) panels and one (1) squid. The project also qualifies as an Eligible Facilities Modification under § 6409 of the FCC's Spectrum Act, which requires the City to approve any eligible facilities request for a modification of an existing tower or base station that does not substantially change the physical dimensions of such tower or base station. This proposal is not considered a substantial change under the Tukwila Municipal Code 18.58.200.7, and falls within the guidelines for an eligible facilities modification. Parcel 0323049057-located at 11030 East Marginal Way South, Tukwila WA 98186 King County Parcel Viewer Address: Parcel 0323049057 10868 East Marginal Way South, Tukwila WA, 98168 PL18-0026 Manufacturing Industrial Center/Heavy Industrial (MIC/H) Tukwila City Hall • 6200 Southcenter Boulevard • Tukwila, WA 98188 • 206-433-1800 • Website: TukwilaWA.gov II. DECISION SEPA Determination: The City SEPA Responsible Official has determined that this application does not require a SEPA threshold determination because it is categorically exempt. Decision on Substantive Permit: The Community Development Director has determined that the application for a Wireless Telecommunication Facility does comply with applicable City and state code requirements and has approved this application. III. YOUR APPEAL RIGHTS The Decision on this Permit Application is a Type 1 decision pursuant to Tukwila Municipal Code §18.104.010. Other land use applications related to this project may still be pending. No administrative appeal of a DNS or an EIS is permitted. One administrative appeal to the City Hearing Examiner of the Decision on the Permit itself is permitted. If an MDNS was issued, any person wishing to challenge either the conditions which were imposed by the MDNS decision or the failure of the Department to impose additional conditions in the MDNS must raise such issues as part of the appeal to the Hearing Examiner. A party who is not satisfied with the outcome of the Hearing Examiner appeal process may file an appeal in King County Superior Court from the Hearing Examiner's decision. IV. PROCEDURES AND TIME FOR APPEALING To appeal the Community Development Director decision on the Permit Application, a written notice of appeal must be filed with the Department of Community Development within 14 days of the issuance of this Decision. The requirements for such appeals are set forth in Tukwila Municipal Code Ch. 18.116. All appeal materials shall be submitted to the Department of Community Development. Appeal materials MUST include: 1. The name of the appealing party. 2. The address and phone number of the appealing party; and if the appealing party is a corporation, association or other group, the address and phone number of a contact person authorized to receive notices on the appealing party's behalf. 3. A statement identifying the decision being appealed and the alleged errors in the decision, including any specific challenge to an MDNS. 4. The Notice of Appeal shall identify (a) the specific errors of fact or errors in application of the law in the decision being appealed; (b) the harm suffered or anticipated by the appellant, and (c) the relief sought. The scope of an appeal shall be limited to matters or issues raised in the Notice of Appeal. 5. Appeal fee per the current fee schedule, additional hourly charges may apply. In addition, all hearing examiner costs will be passed through to the appellant. Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov V. APPEAL HEARINGS PROCESS Any administrative appeal regarding the Permit shall be conducted as a closed record hearing before the Hearing Examiner based on the information presented to the Community Development Director, who made the original decision. No new evidence or testimony will be permitted during the appeal hearing. Parties will be allowed to present oral argument based on the information presented to the Community Development Director before their decision was issued. The Hearing Examiner's decision on the appeal is the City's final decision. Any party wishing to challenge the Hearing Examiner's decision on this application must file an appeal pursuant to the procedures and time limitations set forth in RCW Ch. 36.70C. An appeal challenging a DNS, an MDNS or an EIS may be included in such an appeal. If no appeal of the Hearing Examiner's decision is properly filed in Superior Court within such time limit, the Decision on this permit will be final. The City's decision to issue a DNS, an MDNS or an EIS is final for this permit and any other pending permit applications for the development of the subject property. VI. INSPECTION OF INFORMATION ON THE APPLICATION Project materials including the application, any staff reports, and other studies related to the permits are available for inspection at the Tukwila Department of Community Development, 6300 Southcenter Blvd., Suite 100, Tukwila, Washington 98188 from Monday through Friday between 8:30 a.m. and 5:00 p.m. The project planner is Jonathan Joseph, who may be contacted at 206-431-3662 for further information. Property owners affected by this decision may request a change in valuation for their property tax purposes. Contact the King County Assessor's Office for further information regarding property tax valuation changes. Depart City of rkwila of Community Development Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov City of Tukwila Allan Ekberg, Mayor Department of Community Development - Jack Pace, Director NOTIFICATION: FILE NUMBER: APPLICANT: PROPERTY OWNER: REQUEST: LOCATION: ASSOCIATED PERMITS: SEPA DETERMINATION: COMPREHENSIVE PLAN DESIGNATION: ZONE DESIGNATION: STAFF: ATTACHMENTS: Staff Report PREPARED June 18, 2018 Notification is not required for a Type 1 land use application. L18-0039; PL18-0026 Hannan Rutkosky, Technology Associates (OBO AT&T Wireless) T5 Unison Management, LLC Approval of a Type 1 Wireless Telecommunications Facilities Permit to modify the existing building mounted non -concealed wireless communications facility by removing three (3) existing panel antenna, three (3) RRHs and installing six (6) RRHs, three (3) panels and one (1) squid. Parcel 0323049057-located at 11030 East Marginal Way South, Tukwila WA 98186 King County Parcel Viewer Address: Parcel 0323049057 10868 East Marginal Way South, Tukwila WA, 98168 Electrical permits issued through the City of Tukwila will be required for service alteration for any other electrical service work that is anticipated but not noted on the plans, per article 85.12 (B), Washington electrical code. Building and mechanical permits are required for scope of work stated on the submitted plans. Exempt • Manufacturing Industrial Center/Heavy Industrial (MIC/H) Manufacturing Industrial Center/Heavy Industrial (MIC/H) Jonathan Joseph, Planning Intern Project Plans for Permit L18-0039 Tukwila City Hall • 6200 Southcenter Boulevard • Tukwila, WA 98188 • 206-433-1800 • Website: TukwilaWA.gov Page 2 FINDINGS Vicinity/Site Information Project Description The applicant is proposing modifying the existing building mounted non -concealed wireless communications facility by removing three (3) existing panel antenna, three (3) RRHs and installing six (6) RRHs, three (3) panels and one (1) squid. The project also qualifies as an Eligible Facilities Modification under § 6409 of the FCC's Spectrum Act, which requires the City to approve any eligible facilities request for a modification of an existing tower or base station that does not substantially change the physical dimensions of such tower or base station. This proposal is not considered a substantial change under the Tukwila Municipal Code 18.58.200.7, and falls within the guidelines for an eligible facilities modification. Existing Development This telecommunications facility is preexisting. Surrounding Land Uses The property is zoned Manufacturing Industrial Center/Heavy Industrial (MIC/H). Surrounding parcels are zoned within the MIC/H zone. Background In 2006, the City adopted a Wireless Facilities Chapter (TMC 18.71) to the Zoning Code. The chapter provides location and design requirements for the placement of WCF within the City of Tukwila. In 2016 the city adopted amendments to this ordinance in compliance with the Federal Spectrum Act. Location Selection TABLE A Type of Parntii Required, Based on Type oflAtireless Communicalion Facility Zoning(1) Type of FaciEty Residential Cowl tndustriai Adding, antennas to an rudsting tower of utilty Po% Type VI Typo 1Ri Type 1R} Itigtie facilttie`, modification Type 1 Type 1 Type 1 UliEiy pale cMoea1ion Tye 2 Type 2 Type 2 Concealed big attached Type 2P1 Type 2 } Type 1 angled building: attached Type 2) Type 2 Type 1 New tow or height adjustment rest Type 3I Type 3 Type 3 Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov Page 3 Tukwila Municipal Code (TMC) provides a hierarchy of appropriate locations within the City. Generally, co - locations and utilizing existing structures are favored over the development of new standalone WCF within the City. (1) Zoning for any private/public property or right-of-way Residential — LDR, MDR, or HDR Commercial — O, MUO, RCC, NCC, RC, RCM, TUC, C/LI or TVS Industrial - LI, HI, MIC/L, or MIC/H (2) Provided the height of the tower does not increase and the square footage of the enclosure area does not increase. (3) An applicant may request to install a non -concealed building attached facility, under TMC Section 18.58.150. The applicant is proposing modifying the existing building mounted non -concealed wireless communications facility by removing three (3) existing panel antenna, three (3) RRHs and installing six (6) RRHs, three (3) panels and one (1) squid.This site will be a modification to the property and falls within an Eligible Facilities Modification of the Tukwila Municipal Code. Per TMC 18.58.200.7C. Design Standards The City provides specific design standards for the placement of WCF within the City of Tukwila. The table below indicates if the applicant's proposal complies with required standards. Table 1 (See TMC 18.58.070 for further details) General Requirements Project does comply Project does not comply Not Applicable Notes 1. Generators or other devices which will create noise must comply with TMC 8.22 regarding noise. x 2.Business License Requirement x 3.Only safety signage must be placed on the WCF. x 4. Accommodations for parking for maintenance personal must be provided. X This modification does not affect parking. Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov Page 4 5. Towers shall either maintain a galvanized steel finish or be painted a neutral color so as to reduce its visual obtrusiveness. x 6. The design of all buildings and ancillary structures shall use materials, colors, textures, screening, and landscaping that will blend the tower facilities to the natural setting and built environment. x 7. Antennas shall have the same color scheme as the structure they are located on. x 8. WCF poles and towers shall only have safety lights if required by a government agency. X 9. No advertising is permitted on WCF X No advertising is proposed. 10. ,Each service provider shall be limited to an equipment enclosure of 360 square feet. x Table 2 (See TMC 18.58.110 for further details) Non -Concealed Building Mounted Requirements Project Does Comply Project Does Not Comply Not Applicable Notes 1. The proposed facility must meet the height requirements of the applicable zoning category x 2. If building is at or above the maximum height x Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov Page 5 requirements, the antenna must not extend more than 3ft above the existing roof line 3. Is the proposal utilizing flush mounted antennas x 4. IF not flush mounted, will "shrouds" must be provided for a better visual appearance than exposed antenna equipment X 5. Antennas hall be painted to match the color scheme, of the building(s)/pole x 6. Feed lines and coaxial cables will be painted to match the color scheme of the building(s)/pole? x 7. Cabinet equipment is located within the building or on the rooftop x Equipment cabinet is on the ground 8. Is the equipment cabinet located on the ground with a 6-foot-tall fence x CONCLUSIONS 1. The proposed modifications to the existing WCF will not significantly alter the conditions that currently exist and will not be materially detrimental to the public welfare or injurious to property or improvements in the vicinity. 2. As demonstrated in Table 1, the project meets all applicable development standards for a Type 1 WCF. Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov Page 6 3. The proposed modifications will not alter the surrounding land uses in terms of traffic and pedestrian circulation, building or site design. 4. The proposed project is in keeping with the goals and policies of the Comprehensive Land Use Policy Plan. S. The project also qualifies as an Eligible Facilities Modification under § 6409 of the FCC's Spectrum Act, which requires the City to approve any eligible facilities request for a modification of an existing tower or base station that does not substantially change the physical dimensions of such tower or base station. RECOMMENDATIONS The recommendation to the Director of Community Development is to approve this application for a Type 1 Wireless Telecommunications Facility permit. INFORMATIONAL ITEMS A City of Tukwila electrical permit is required for service alteration. A building and mechanical permit are required for the site work. Please note that the installation of an emergency power disconnect switch is required for Fire Department use. Contact Don Tomaso at 206-971-8723 to get more information about permit requirements for the power disconnect switch. Phone: 206-433-1800 • Email: Mayor@TukwilaWA.gov • Website: TukwilaWA.gov �qsy- Cityof Tukwila Allan Ekberg, Mayor Department of Community Development - Jack Pace, Director Affidavit of Distribution Project Name: AT&T 5C6C Project Number: PL18-0026 Associated File Number(s): L18-0039 Date Mailed: 6/28/18 Mailing requested by: JONATHAN JOSEPH Mailer's signature: ❑ Board of Adjustment Agenda Packet 0 Notice of Application for O Board of Appeals Agenda Packet Shoreline Mgmt Permit 0 Determination of Non -Significance CZ Notice of Decision ❑ Determination of Significance & Scoping Notice ❑ Mitigated Determination of Non - Significance ❑ Notice of Action ❑ Notice of Application Parties of Record: O Notice of Public Hearing ❑ Notice of Public Meeting O Official Notice ❑ Other: ❑ Shoreline Mgmt Permit ❑ Short Subdivision Agenda CITY OF TUKWILA Department of Community Development 6300 Southcenter Boulevard, Tukwila, WA 98188 Telephone: (206) 431-3670 WIRELESS TELE- COMMUNICATION FACILITIES APPLICATION FOR STAFF USE ONLY Permits Plus Type: P-WIRE Planner: File Number: Li 8 - 0039 Application Complete Date: Project File Number: P L / g - ODZ G Application Incomplete Date: Other File Numbers: NAME OF PROJECT/DEVELOPMENT: AT&T 5C 6C Replace (6) antennas, remove (6) BRIEF DESCRIPTION OF PROJECT:SQUID. CIRCLE TYPE - TYPE I TYPE 2 TYPE 3 LOCATION OF PROJECT/DEVELOPMENT: Give street address or, subdivision, access street, and nearest intersection. 11030 E Marginal Way, Seattle, WA 98168 TMAs, add (9) RRUs, add (1) Public hearing notices and Hearing Examiner fees apply if vacant, indicate lot(s), block and LIST ALL TAX LOT NUMBERS (this information nicry be found on your tax statement). 0323049057 DEVELOPMENT COORDINATOR : The individual who: • has decision making authority on behalf of the owner/applicant in meetings with City staff, • has full responsibility for identifying and satisfying all relevant and sometimes overlapping development standards, and • is the primary contact with the City, to whom all notices and reports will be sent. Name: Hannan Rutkosky Address: 650 S Orcas St, Suite R-103, Seattle, WA 98108 Phone: 253-985-5637 FAX: N/A E-mail: Hannan.Rutkosky@taec.net Signature: gtar44 Reer4044 Date: 3/12/2018 • .dcptstore,City Coninton,Teri.larbv July 2S 2015AVireless Communication facility 06.04-15.docs RECEIVED MAY 072018 Community Development Technolo9Ygy' Associates April 26, 2018 City of Tukwila Department of Community Development 6300 Southcenter Blvd Tukwila, WA 98188 RE: AT&T Project No.: SC78 HWY 99 AND HWY 599 Dear Reviewing Parties: Sprint is proposing to modify an existing wireless facility located on a monopole at 10868 E Marginal Way S. The proposed modification includes removing (3) panels, removing (3) RRHs, installing (6) RRHs, installing (3) panels and installing (1) squid. All new and replacement equipment will be attached to existing antenna mounts and no increase to the height or footprint of the existing facility shall result from the proposed modifications The following review is being requested at this time: • Eligible Facility Approval • Building Permit The following items are included as part of the application package: • Building Permit Application Form • Eligible Facility Request • Construction Drawings (8) • Structural Analysis (2) • LL Signed Affidavit • Fees Please feel free to contact me directly at 253-985-5637 or Hannan.rutkoskv@taec.net should you have any questions or require additional information in order to complete your review. Sincerely, Hannan Rutkosky 650 S Orcas Street, Suite 103 Seattle, WA 98108 www.taec.net FIECRVED MAY 07 2018 Community Development April 26, 2018 City of Tukwila Department of Community Development 6300 Southcenter Blvd Tukwila, WA 98188 RE: Request for Minor Modification to Existing Wireless Facility - Section 6409/47 CFR § 1.40001 ("6409") Site Address: 10868 E. MARGINAL WAY S Prior Case No.: L914-0074 AT&T Project No.: SC78 HWY 99 AND HWY 599 Dear City of Tukwila: Sprint is proposing to modify an existing wireless facility located on a monopole at 10868 E Marginal Way S. The proposed modification includes removing (3) panels, removing (3) RRHs, installing (6) RRHs, installing (3) panels and installing (1) squid. Pursuant to Section 6409 of the Spectrum Act (47 U.S.0 1455) Sprint requests approval of the modification as an eligible facility as follows: • Tower height: AT&T proposes to remove (3) panels, remove (3) RRHs, install (6) RRHs, install (3) panels and install (1) squid at a centerline of 80' AGL on an existing monopole. No change to the overall height of the facility shall occur as part of the proposed modifications. • Width: Existing monopole mounting hardware will be utilized. No protrusion from the footprint of the existing monopole shall occur. • Cabinets: 0 additional equipment cabinets are proposed. • Expansions: all work will be performed wholly within the existing premises and utility easements. • Concealment: The existing facility is free from concealment features. The new and replacement equipment will be attached to the monopole in the same manner as existing. • Prior Conditions: all modification work shall be in compliance with previous zoning approvals. A copy of Federal Communications Commission rule 6409 has been attached hereto for your information. Sincerely, Hannan Rutkosky 253-985-5637 Hannan.rutkosky@taec.net 650 S Orcas Street, Suite 103 Seattle, WA 98108 www.taec.net RECEIVED MAY 07 2018 Community Development Title 47 --► Chapter I Subchapter A -i Part 1 —► Subpart CC —+ §1.40001 Title 47: Telecommunication PART 1—PRACTICE AND PROCEDURE Subpart CC —State and Local Review of Applications for Wireless Service Facility Modification §1.40001 Wireless Facility Modifications. (a) Purpose. These rules implement section 6409 of the Spectrum Act (codified at 47 U.S.C. 1455), which requires a State or local government to approve any eligible facilities request for a modification of an existing tower or base station that does not substantially change the physical dimensions of such tower or base station. (b) Definitions. Terms used in this section have the following meanings. (1) Base station. A structure or equipment at a fixed location that enables Commission -licensed or authorized wireless communications between user equipment and a communications network. The term does not encompass a tower as defined in this subpart or any equipment associated with a tower. (i) The term includes, but is not limited to, equipment associated with wireless communications services such as private, broadcast, and public safety services, as well as unlicensed wireless services and fixed wireless services such as microwave backhaul. (ii) The term includes, but is not limited to, radio transceivers, antennas, coaxial or fiber-optic cable, regular and backup power supplies, and comparable equipment, regardless of technological configuration (including Distributed Antenna Systems and small -cell networks). (iii) The term includes any structure other than a tower that, at the time the relevant application is filed with the State or local government under this section, supports or houses equipment described in paragraphs (b)(1)(i) through (ii) of this section that has been reviewed and approved under the applicable zoning or siting process, or under another State or local regulatory review process, even if the structure was not built for the sole or primary purpose of providing such support. (iv) The term does not include any structure that, at the time the relevant application is filed with the State or local government under this section, does not support or house equipment described in paragraphs (b)(1)(i)-(ii) of this section. ECF! VED MAY 072018 Community Development • • (2) Collocation. The mounting or installation of transmission equipment on an eligible support structure for the purpose of transmitting and/or receiving radio frequency signals for communications purposes. (3) Eligible facilities request. Any request for modification of an existing tower or base station that does not substantially change the physical dimensions of such tower or base station, involving: (i) Collocation of new transmission equipment; (ii) Removal of transmission equipment; or (iii) Replacement of transmission equipment. (4) Eligible support structure. Any tower or base station as defined in this section, provided that it is existing at the time the relevant application is filed with the State or local government under this section. (5) Existing. A constructed tower or base station is existing for purposes of this section if it has been reviewed and approved under the applicable zoning or siting process, or under another State or local regulatory review process, provided that a tower that has not been reviewed and approved because it was not in a zoned area when it was built, but was lawfully constructed, is existing for purposes of this definition. (6) Site. For towers other than towers in the public rights -of -way, the current boundaries of the leased or owned property surrounding the tower and any access or utility easements currently related to the site, and, for other eligible support structures, further restricted to that area in proximity to the structure and to other transmission equipment already deployed on the ground. (7) Substantial change. A modification substantially changes the physical dimensions of an eligible support structure if it meets any of the following criteria: (i) For towers other than towers in the public rights -of -way, it increases the height of the tower by more than 10% or by the height of one additional antenna array with separation from the nearest existing antenna not to exceed twenty feet, whichever is greater; for other eligible support structures, it increases the height of the structure by more than 10% or more than ten feet, whichever is greater; (A) Changes in height should be measured from the original support structure in cases where deployments are or will be separated horizontally, such as on buildings' rooftops; in other circumstances, changes in height should be measured from the dimensions of the tower or base station, inclusive of originally approved appurtenances and any modifications that were approved prior to the passage of the Spectrum Act. EC fED MAY 07 2018 Community Development • (ii) For towers other than towers in the public rights -of -way, it involves adding an appurtenance to the body of the tower that would protrude from the edge of the tower more than twenty feet, or more than the width of the tower structure at the level of the appurtenance, whichever is greater; for other eligible support structures, it involves adding an appurtenance to the body of the structure that would protrude from the edge of the structure by more than six feet; (iii) For any eligible support structure, it involves installation of more than the standard number of new equipment cabinets for the technology involved, but not to exceed four cabinets; or, for towers in the public rights -of -way and base stations, it involves installation of any new equipment cabinets on the ground if there are no pre- existing ground cabinets associated with the structure, or else involves installation of ground cabinets that are more than 10% larger in height or overall volume than any other ground cabinets associated with the structure; (iv) It entails any excavation or deployment outside the current site; (v) It would defeat the concealment elements of the eligible support structure; or (vi) It does not comply with conditions associated with the siting approval of the construction or modification of the eligible support structure or base station equipment, provided however that this limitation does not apply to any modification that is non- compliant only in a manner that would not exceed the thresholds identified in §1.40001(b)(7)(i) through (iv). (8) Transmission equipment. Equipment that facilitates transmission for any Commission -licensed or authorized wireless communication service, including, but not limited to, radio transceivers, antennas, coaxial or fiber-optic cable, and regular and backup power supply. The term includes equipment associated with wireless communications services including, but not limited to, private, broadcast, and public safety services, as well as unlicensed wireless services and fixed wireless services such as microwave backhaul. (9) Tower. Any structure built for the sole or primary purpose of supporting any Commission -licensed or authorized antennas and their associated facilities, including structures that are constructed for wireless communications services including, but not limited to, private, broadcast, and public safety services, as well as unlicensed wireless services and fixed wireless services such as microwave backhaul, and the associated site. (c) Review of applications. A State or local government may not deny and shall approve any eligible facilities request for modification of an eligible support structure that does not substantially change the physical dimensions of such structure. (1) Documentation requirement for review. When an applicant asserts in writing that a request for modification is covered by this section, a State or local government may require the applicant to provide documentation or information only to the extent f EC V E 7 MAY 07 2018 Community Development reasonably related to determining whether the request meets the requirements of this section. A State or local government may not require an applicant to submit any other documentation, including but not limited to documentation intended to illustrate the need for such wireless facilities or to justify the business decision to modify such wireless facilities. (2) Timeframe for review. Within 60 days of the date on which an applicant submits a request seeking approval under this section, the State or local government shall approve the application unless it determines that the application is not covered by this section. (3) Tolling of the timeframe for review. The 60-day period begins to run when the application is filed, and may be tolled only by mutual agreement or in cases where the reviewing State or local government determines that the application is incomplete. The timeframe for review is not tolled by a moratorium on the review of applications. (i) To toll the timeframe for incompleteness, the reviewing State or local government must provide written notice to the applicant within 30 days of receipt of the application, clearly and specifically delineating all missing documents or information. Such delineated information is limited to documents or information meeting the standard under paragraph (c)(1) of this section. (ii) The timeframe for review begins running again when the applicant makes a supplemental submission in response to the State or local government's notice of incompleteness. (iii) Following a supplemental submission, the State or local government will have 10 days to notify the applicant that the supplemental submission did not provide the information identified in the original notice delineating missing information. The timeframe is tolled in the case of second or subsequent notices pursuant to the procedures identified in this paragraph (c)(3). Second or subsequent notices of incompleteness may not specify missing documents or information that were not delineated in the original notice of incompleteness. (4) Failure to act. In the event the reviewing State or local government fails to approve or deny a request seeking approval under this section within the timeframe for review (accounting for any tolling), the request shall be deemed granted. The deemed grant does not become effective until the applicant notifies the applicable reviewing authority in writing after the review period has expired (accounting for any tolling) that the application has been deemed granted. (5) Remedies. Applicants and reviewing authorities may bring claims related to Section 6409(a) to any court of competent jurisdiction. [80 FR 1269,Jan. 8,2015] RECEEVED MAY 07 2018 Community Development CITY OF TUKWILA Department of Community Development 6300 Southcenter Boulevard, Tukwila, WA 98188 Telephone: (206) 431-3670 AFFIDAVIT OF OWNERSHIP AND HOLD HARMLESS PERMISSION TO ENTER PROPERTY STATE OF WASHINGTON ss COUNTY OF KING The undersigned being duly sworn and upon oath states as follows: 1. I am the current owner of the property which is the subject of this application. 2. All statements contained in the applications have been prepared by me or my agents and are true and correct to the best of my knowledge. 3. The application is being submitted with my knowledge and consent. 4. Owner grants the City, its employees, agents, engineers, contractors or other representatives the right to enter upon Owner's real property, located at _11030 E Marginal Way, Seattle, WA 98168 for the purpose of application review, for the limited time necessary to complete that purpose. 5. Owner agrees to hold the City harmless for any loss or damage to persons or property occurring on the private property during the City's entry upon the property, unless the Toss or damage is the result of the sole negligence of the City. 6. Non -responsiveness to a City information request for ninety (90) or more days, shall be cause to cancel the application(s) without refund of fees. EXECUTED at Woburn (city), MA (state), on 20 18 (Print Name) 10 Presidential Way, Woburn (Address) 781-92 (Phone/ (Signature) Margaret Robinson, Senior Counsel, American Tower Asset Sub, LLC, as attorney -in -fact for Seattle Police Athletic Association, Inc. On this day personally appeared before me Margaret Robinson, Senior Counsel to me known to be the individual who executed the foregoing instrument and acknowledged that he/she signed the same as his/her voluntary act and deed for the uses and purposes mentioned therein. SUBSCRIBED AND SWORN TO BEFORE ME ON THIS 114ti DAY OF arL 18 41/An,: GERARD T. HEFFRON Notary Public Commonwealth of Massachusetts My Commission ExpiresAugust 9, 2024 NOTARY PUBLIC in and for the State of W no' wtsetts ,gt residing at Middlesex County My Commission expires on 11deplstore\City ComnwnkrerMirbyVuly 28 20151Wireless Communication Facility 06-04-15.docc 70- Lf RECEIVED MAY 07 2018 Community flay innment SITE PHOTO PROJECT INFORMATION SITE INFORMATION SITE NAME: FA /: PTN #: LATITUDE: LONGITUDE: SITE ADDRESS: COUNTY: JURISDICTION: ZONING CLASSIFICATION: CONSTRUCTION TYPE: OCCUPANCY: CURRENT STRUCTURE USE: PARCEL NUMBER: APPLICANT INFORMATION APPLICANT/LESSEE: ADDRESS: PROPERTY OWNER NAME: HWY 99&HWY 599 10092623 3801PCONCJ/3801AOCXQN 47- 30' 12.03" N (47.503342') 127 17' 12.177" W (-122.286716') 10868 E. MARGINAL WAY S TUKWILA WA 98168 KING CITY OF TUKWILA MIC/H I I-B U TELECOMMUNICATIONS FACIUTY 0323049057 AT&T MOBILITY 11520 FINANCIAL CENTRE PKWY LITTLE ROCK, AR 72110 N/A PROJECT TEAM NOT TO SCALE • at&t LOCATION MAP SITE SCOPE OF WORK NORTH CLIENT SITE ID: SITE NAME: SITE ADDRESS: FA #: PTN #: SITE TYPE: DIRECTIONS SC78 HWY 99 & HWY 599 10868 E. MARGINAL WAY S TUKWILA, WA 98168 10092623 3801 AOCWCJ/3801 AOCXQN 121'-0" MONOPOLE CONSTRUCTION MANAGER NAME: CONTACT: PHONE: PROJECT MANAGER NAME: CONTACT: PHONE: SITE DESIGN NAME: ADDRESS: CITY, STATE, ZIP: CONTACT: PHONE: MASTEC, NETWORK SOLUTIONS RON EVENSON (253) 246-4348 MASTEC, NETWORK SOLUTIONS DANIEL KELLY (253) 246 4348 MASTEC, NETWORK SOLUTIONS 1000 CENTREGREEN WAY, SUITE 300 CARY, NC 27513 RAPHAEL MOHAMED (919) 674-5895 DESIGN CRITERIA TELECOMMUNICATIONS FACILITY DESIGNED PER THE CRITERIA BELOW: 1 WIND LOAD PER 2015 IBC W/ SUBSEQUENT SUPPLEMENTS A. ULTIMATE WIND SPEED: 110 MPH, 3 SEC. GUST. B. WIND IMPORTANCE FACTOR: 1.0 UNMANNED TELECOMMUNICATIONS FACILITY BUILDING CATEGORY II. C. WIND EXPOSURE: C. 2. DEAD LOAD: A. EQUIPMENT WEIGHT PER MANUFACTURER DATA. 3. SEISMIC LOAD DOES NOT GOVERN THIS DESIGN. THIS IS NOT AN ALL INCLUSIVE LIST. CONTRACTOR SHALL USE SPECIFIED EQUIPMENT PART OR ENGINEER APPROVED EQUIVALENT. CONTRACTOR SHALL VERIFY ALL NEEDED EQUIPMENT TO PROVIDE A FUNCTIONAL SITE. THE PROJECT GENERALLY CONSISTS OF THE FOLLOWING: LTE 5C/6C: - REMOVE (6) EXISTING PANEL ANTENNAS - REMOVE (6) EXISTING DIPLEXERS -INSTALL (9) PROPOSED RRH'S - INSTALL (6) PROPOSED PANEL ANTENNAS -INSTALL (1) PROPOSED SQUID -INSTALL (1) PROPOSED DC TO DC CONVEYER - INSTALL (4) PROPOSED CONVERTER MODULES - INSTALL (1) PROPOSED 6C BCEM CARD - INSTALL (1) PROPOSED 2C BCEM CARD - INSTALL (1) PROPOSED 5C BCEM CARD - INSTALL (1) PROPOSED RAYCAP - INSTALL NOKIA FSM4 LEGAL DESCRIPTION POR OF SW 1/4 BEG NXN ELY LN OF OLD SEATTLE-TACOMA INTERURBAN RW R/W & N LN CEDAR RIVER PL R/W TH TH NWLY ALG SD S T 1 RW R/W 551.183 FT TO EXIST CONCRETE WALL TH N 68-48-07 E ALG S LN OF SD WALL & SAME PROD 350.005 FT TH S 20-53-36.5 E 215.144 FT TH ON CURVE TO RT RAD 3264.93 FT 482.1 FT TO N LN SD PL R/W TH N 87-41-10 W ALG SD N LN 363.46 FT TO BEG LESS TRANS LN R/W DEPART FROM: 16221 NE 72ND WAY, REDMOND, WA 98052 1. GET ON WA-520 W FROM BEAR CREEK PKWY AND LEARY WAY 2. FOLLOW WA-520 W AND 1-5 S TO S BOEING ACCESS RD IN TUKWILA. TAKE EXIT 158 FROM 1-5 S 3. CONTINUE ON S BOEING ACCESS RD TO YOUR DESTINATION ARRIVE AT. 10868 E. MARGINAL WAY S, TUKWILA, WA 98168 DO NOT SCALE DRAWINGS CONTRACTOR SHALL VERIFY ALL PLANS & EXISTING DIMENSIONS & CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE ARCHITECT OR ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME. Know what's below. CaII before you dig. Digitally signed by Raphael Mohamed ON E =Raphael. Mohamed@mastec.com Raphael Mohamed ou=Ma°TecINetworkSo° gears OU=Service Lines. DC=mestec, DC=local Date. 2018.05 02 11,29'46-04'00' INDEX OF DRAWINGS SHEET DESCRIPTION T-1 GN-1 GN-2 S-1 A-1 A-2 A-3 A -4 A-5 A-6 G-1 G-2 TITLE SHEET GENERAL NOTES GENERAL NOTES SIGNAGE DETAILS SITE PLAN EXISTING & PROPOSED EQUIPMENT PLAN EXISTING & PROPOSED BUILDING ELEVATION EQUIPMENT DETAILS EXISTING ANTENNA PLAN & EQUIPMENT SCHEDULE PROPOSED ANTENNA PUN & EQUIPMENT SCHEDULE • GROUNDING SCHEMATIC PUN GROUNDING DETAILS REV DATE 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 05/02/2018 1 Osj0272018 CODE COMPLIANCE ALL WORK AND MATERIALS SHALL BE PREFORMED AND INSTALLED IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCATION GOVERNING AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THE LATEST EDITIONS OF THE FOLLOWING: 2015 INTERNATIONAL BUILDING CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL RESIDENTIAL CODE 2015 INTERNATIONAL WILDLAND-URBAN CODE APPROVALS PROPERTY OWNER/LANDLORD: MASTEC SITE ACQUISITION. MASTEC ROOM READY: MASTEC CONSTRUCTION MANAGER: MASTEC LTE PROJECT MANAGER: AT&T: DATE: TO OBTAIN LOCATION OF PARTICIPANTS UNDERGROUND FACILITIES BEFORE YOU DIG IN WASHINGTON, CALL UTILITY NOTIFICATION CENTER TOLL FREE: 1-800-424-5555 OR www.callbeforeyoudig.org WASHINGTON STATUTE REQUIRES MIN OF 2 WORKING DAYS NOTICE BEFORE YOU EXCAVATE Com Devi]: • atstt 1111 W CAPITOL AVE R11 1070 LITTLE ROCK, AR 72201-3005 "-PING PREPARED BY. :IasTec Network Solutions 4300 STOCKTON ERNE, NORTH UTILE ROM(. AR 72117 501-260-7633 EXPIRAT1088 6192018 04/19/18 DATE Si AYE CRRTU DIRECT S1IPERNSIDN AND TIT I M1 A DULY REGISTERED ENGPEER UNDER TIE LAMS OF TIE STA1E CC 11PSHNGTOM REVISIONS REV. MOE PTION —1D S A 03/17/18 90% CD'S GJJ 0 04/19/18OR OONSTRJCElON VSAA m 05/02/18 aim maims GJJ • NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WTTHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY SHEET TITLE TITLE SHEET ,1 SHEET NUMBER T-1 LIMITS OF LIABIUTY • MNS HAS MADE EVERY EFFORT TO CREATE COMPLETE AND ACCURATE CONTRACT DOCUMENTS WITH THE BEST INFORMATION AVAILABLE AT THE TIME OF THEIR COMPLETION. CONTRACTORS ARE CAUTIONED THAT MINOR OMISSIONS OR ERRORS IN THE CONTRACT DOCUMENTS MAY OCCUR AND SHALL NOT EXCUSE THE CONTRACTOR FROM COMPLETING THE PROJECT AND IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF THE DOCUMENTS. REFERENCE ADMINISTRATIVE REQUIREMENTS. CONTRACT DOCUMENTS; 1. THE CONTRACT DOCUMENTS INCLUDE THE AGENCY APPROVED PROJECT SPECIFICATIONS. PLANS AND THEIR LATEST REVISIONS. ADDENDA, AND CLARIFICATIONS. THE CONTRACT DOCUMENTS MAY ALSO INCLUDE NETWORK CARRIER STANDARDS FOR INSTALLATION OF TELECOMMUNICATION EQUIPMENT. 2.THE CONTRACTOR SHALL KEEP A MINIMUM OF ONE SET OF CONTRACT DOCUMENTS ON FILE IN THE PROJECT OFFICE AT THE JOB SITE. COPIES OF THE PROJECT DOCUMENTS USED BY SITE STAFF SHALL BE UP TO DATE WITH PROJECT OFFICE COPY. 3.THE CONTRACTOR SHALL NOTIFY THE PROJECT TEAM OF ANY ERRORS, OMISSIONS, AND INCONSISTENCIES FOUND IN THE CONTRACT DOCUMENTS. THE NOTIFICATION SHALL BE GIVEN BOTH VERBALLY AND IN WRITING WITHIN 24 HOURS OF DISCOVERY. 4.IF AN ERROR OR OMISSION IN THE PROJECT DOCUMENTS REQUIRES RECTIFICATION, THE CONTRACTOR SHALL SUBMIT A PROPOSAL TO THE PROJECT TEAM TO RECTIFY THE ISSUE. THE PROPOSAL MUST BE APPROVED PRIOR TO WORK. 5.THE CONTRACT DRAWINGS ARE PREPARED TO SCALE WITH THE BEST KNOWLEDGE OF THE SITE GIVEN TO MNS. WHERE DIMENSIONS ARE NOT SHOWN IN THE DRAWINGS, NE CONTRACTOR SHOULD CLARIFY WITH THE PROJECT TEAM WHEN THE INFORMATION IS CRITICAL TO PROPER INSTAUATION. 6. THE CONTRACTOR SHALL DOCUMENT ALL CHANGES ANS SUBSTITUTIONS ON THE PROJECT OFFICE COPY OF THE CONTRACT DOCUMENTS. 7. WHEN FABRICATION OF STRUCTURAL ITEMS ARE REQUIRED, IT MAY BE NECESSARY TO SUBMIT SHOP DRAWINGS FOR REVIEW BY MNS. SEE STRUCTURAL NOTES. 8.DEFERRED SUBMITTALS ARE REQUIRED FOR MATERIALS TO BE PROVIDED BY THE CONTRACTOR. WHERE MATERIALS IN THE PLANS ARE DESIGNATED AS PROVIDED BY CONTRACTOR, THE CONTRACTOR SHALL SUBMIT THE PREFERRED MATERIAL TO THE PROJECT TEAM FOR REVIEW ND APPROVAL TO WORK. ADMINISTRATIVE REQUIREMENTS. 1. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS REQUIRED (INCLUDING FEES) TO COMPLETE THE WORK DESCRIBED BY THE CONSTRUCTION DOCUMENTS. 2. PRIOR TO BIDDING, THE CONTRACTOR IS RESPONSIBLE FOR REVIEW OF THE PROJECT SITE AND CONTRACT DOCUMENTS TO UNDERSTAND THE DESIGN AND CONDITIONS AFFECTING THE WORK TO BE PERFORMED. ANY ERRORS, OMISSIONS. AND DISCREPANCIES MUST BE SUBMITTED TO THE PROJECT TEAM VERBALLY AND IN WRITING. 3. THE CONTRACTOR SHALL PROVIDE A WARRANTY FOR WORK FOR A PERIOD OF ONE YEAR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND SHALL REMEDY ALL FAULTY. INTERIOR, AND/OR IMPROPER MATERIALS, DAMAGED GOODS, ND/OR FAULTY WORKMANSHIP. ALL ROOFING AND WATERPROOFING MUST BE WARRANTED FOR A PERIOD OF TWO YEARS. THE PERIOD BEGINS AT SUBSTANTIAL COMPLETION OF THE PROJECT. 4. THE CONTRACTOR SHALL PROVIDE SHALL PROVIDE A COPY OF LICENSE AND INSURANCE TO THE TELECOMMUNICATION CARRIER. SITE SAFETY; 1. THE CONTRACTOR SHALL PROVIDE OSHA COMPUANT PROTECTION FOR THE SAFETY OF THE SITE STAFF AT ALL TIMES DURING THE CONSTRUCTION OF THE PROJECT. 2.CONTRACTOR SHALL KEEP GENERAL WORK AREA CLEAN AND HAZARD FREE DURING CONSTRUCTION. SITE SHALL BE LEFT IN CLEAN CONDITION AND FREE FROM DIRT AND DEBRIS. SURFACES SHALL BE CLEANED OF GREASE. PAINT. OR OTHER MATERIALS NOT SPECIFIED IN THE CONSTRUCTION DOCUMENTS. 3.THE CONTRACTOR IS TO PROVIDE PROTECTION FOR ADJOINING PROPERTIES FROM PHYSICAL HARM, NOISE, DUST, DIRT, AND FIRE AS REQUIRED BY THE GOVERNING AGENCIES. THE CONTRACTOR IS RESPONSIBLE FOR REPAIR OF ANY DAMAGE. 4. THE CONTRACTOR IS RESPONSIBLE FOR THE SECURITY OF THE PROJECT SITE AREA. 5.WHERE WORK REQUIRES OPEN HAZARDS TO SITE STAFF, THE HAZARD SHALL BE TEMPORARILY MITIGATED TO OSHA STANDARD UNTIL THE HAZARD IS CLOSED. 6. SEE STRUCTURAL NOTES. 01.021..Effa 1. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH UTILITY AGENCIES PRIOR TO WORK WITH UTILITIES. 2. CONTRACTOR TO LOCATE AU. UTILITIES PRIOR TO WORK. 3. CONTRACTOR TO PROTECT, REPLACE AND/OR REROUTE ANY EXISTING UTILITIES ENCOUNTERED DURING THE COURSE OF WORK. SPECIAL CONSIDERATIONS FOR WEATHERPROOFING; 1. ALL PENETRATIONS TO EXISTING STRUCTURES MUST BE SEALED WITH APPROVED WEATHERPROOFING. IF WEATHERPROOFING IS OMITTED, CONTACT THE PROJECT TEAM FOR CLARIFICATION OR PROVIDE A WEATHERPROOFING PROPOSAL FOR APPROVAL 2. CONTRACTOR SHALL COORDINATE WITH OWNER AND THE EXISTING ROOFING CONTRACTOR OF RECORD FOR ANY AUGMENTATION TO THE ROOF MEMBRANE, AND HAVING THE WORK GUARANTEED UNDER THE ROOFING CONTRACTOR'S EXISTING WARRANTY. WORK REQUIREMENTS; 1. ALL WORK MUST BE PERFORMED DURING THE OWNERS PREFERRED HOURS. 2. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR AU. CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES. AND PROCEDURES FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE CONTRACT. 3. ALL WORK PERFORMED ON THE PROJECT SHALL BE IN ACCORDANCE WITH ALL APPUCABLE CODES AND STANDARDS. SEE STRUCTURAL NOTES. 4. IF INSPECTION OF WORK IS REQUIRED, THE CONTRACTOR SHALL NOTIFY THE INSPECTION ENTITY 24 HOURS IN ADVANCE OF THE WORK TO BE PERFORMED. 5. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH UTILITY AGENCIES PRIOR TO WORK WITH UTILITIES. REFERENCE UTILITIES SECTION. 6. THE CONTRACTOR SHALL COORDINATE ON -SITE STORAGE WITH OWNER IN ADVANCE OF WORK. PERMITS MAY BE REQUIRED FOR STORAGE ON PUBUC RIGHT OF WAY. 7. ALL NEW CONSTRUCTION SHALL MATCH EXISTING CONSTRUCTION IN FORM, TEXTURE, FINISH, AND IN MATERIALS EXCEPT AS NOTED IN THE CONSTRUCTION DOCUMENTS. 8. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO PROTECT EXISTING WORK FROM DAMAGE DURING THE COURSE OF WORK FOR THIS PROJECT. 9. THE CONTRACTOR SHALL PROVIDE WORK WHICH IS LEVEL, PLUMB, AND WITHIN TOLERANCES SPECIFIED BY CODES AND STANDARDS INCLUDED IN THE STRUCTURAL NOTES. 10. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT MATERIAL ACCORDING TO MANUFACTURES SPECIFICATIONS UNLESS NOTED OTHERWISES OR WHERE LOCAL CODES OR OREINANCES TAKE PRECEDENCE. 11. ANY SUBSTITUTIONS OF MATERIALS MUST BE APPROVED BY THE PROJECT TEAM IN WRmNG. 12. THE CONTRACTOR SHALL SUPPLY ALL MATERIALS INCIDENTAL TO THE WORK DESCRIBED BY THE CONTRACT DOCUMENTS. 13. THE CONTRACTOR MUST RESTORE AU. PORTIONS OF THE PROJECT SITE TO IT'S PRE -WORK CONDITION. WHERE THE WORK PERFORMED DOES NOT ALLOW FOR PRE -WORK RESTORATION, WORK AREAS MUST BE REPAIRED OR REPLACED TO MATCH EXISTING FINISH AND SITE GRADING. 14. THE CONTRACTOR IS RESPONSIBLE FOR ALL DISPOSAL OF DEBRIS AND ITEMS WHICH ARE SPECIFIED TO BE REMOVED IN THE COURSE OF WORK. CAST -IN PLACE CONCRETE; 1. ALL CONCRETE DESIGN DESCRIBED BY THIS SET OF DRAWINGS IS BASED ON ACI 318. 2. ALL STRUCTURAL CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI. UNLESS SPECIFIED OTHERWISE. 3. EACH CONCRETE MIX DESIGN SHALL HAVE A CYUNDER TEST HISTORY OF 60 DAYS MINIMUM, TESTED IN ACCORDANCE WITH ASTM C39, TESTED BY AN ACI CERTIFIED STRENGTH TESTING TECHNICIAN, AND THE STRENGTH STATISTICALLY DETERMINED IN ACCORDANCE WITH ACI 318. EACH MIX DESIGN USED ON SITE SHALL BE SUBMITTED TO, AND RECEIVED BY THE PROJECT TEAM BEFORE THE CONCRETE IS PLACED ON SITE. 4. RAW MATERIALS, MANUFACTURE. AND DELIVERY TO THE FORMWORK SHALL BE IN ACCORDANCE WITH ASTM C94 AND ACI 318. 5. EMBEDDED ITEMS ARE TO BE SECURELY FASTENED SO THAT THEY DO NOT MOVE DURING PLACEMENT OF THE CONCRETE. REFERENCE THE REINFORCING STEEL SECTION. 6. TWO CYUNDERS SHALL BE TAKEN FOR EACH LOAD DELIVERED TO THE FORMWORK. SAMPLES ARE TO BE TAKEN FROM THE CONCRETE AS IT IS PLACED IN THE FORMWORK IN ACCORDANCE WITH ASTM C172. CYUNDERS ARE TESTED PER ASTM C39 AND TESTED BY AN ACI CERTIFIED CSTT. CONCRETE SAMPLES ARE TO BE TESTED FOR AIR CONTENT AND WATER CEMENT RATIO. ALL TEST RESULTS ARE SUBMITTED TO THE PROJECT TEAM WITHIN ONE MONTH OF PLACING THE CONCRETE ON SITE. 7. WHEN AMBIENT TEMPERATURES FALL BELOW 55 DEGREES FAHRENHEIT, THE CONTRACTOR SHALL FOLLOW GUIDEUNES DESCRIBED IN ACI 306. WHEN AMBIENT TEMPERATURES RISE ABOVE 90 DEGREES FAHRENHEIT. THE CONTRACTOR SHALL FOLLOW GUIDEUNES DESCRIBED IN ACI 305. THE CONCRETE SHALL BE PROTECTED FROM FREEZING OR FROM EXCESSIVE HEAT WITH TENTS OR BLANKETS TO PROVIDE FOR HEAT OR MOISTURE LOSS. 8. ALL CONCRETE SHALL BE PLACED AS CLOSE TO PRACTICAL TO THE FINAL DESTINATION IN THE FORM. CONCRETE SHALL NOT BE PLACE FROM A HEIGHT GREATER THAN 6 FEET FROM THE POINT OF DISCHARGE. 9. VIBRATION SHALL BE USED TO CONSOUDATE CONVENTIONAL CONCRETE. EXTERNAL STINGER VIBRATORS SHALL BE INSERTED VERTICALLY INTO FORMS EVERY 36 INCHES MAXIMUM AND FOR EACH UFT. STINGER VIBRATORS SHALL BE INSERTED TO A VERTICAL DEPTH OF 12 INCHES INTO PREVIOUS UFTS TO ENSURE CONSOUDATION. FOLLOW GUIDEUNES USED IN ACI 309R. 10. REPAIRS FOR MINOR DEFECTS MAY BE ADMINISTERED BY AN EXPERIENCED CRAFTSMAN WITHOUT AN APPROVED PROCEDURE. A MINOR DEFECT INCLUDES BUG HOLES, HONEYCOMBING, CHIPS, AND SPALLS THAT DO NOT EXCEED 'A INCH OF DEPTH INTO THE FACE OF THE CONCRETE. MAJOR REPAIRS EXTENDING BEYOND 'A INCH OF DEPTH AND UP TO THE REINFORCING MAY BE REPAIRED WITH AN APPROVED REPAIR PROCEDURE. REPAIR PROCEDURES MAY BE SUBMITTED TO THE PROJECT TEAM FOR APPROVAL IN ADVANCE OF FIELD WORK. DAMAGE EXTENDING BEYOND STEEL REINFORCING REQUIRES A RETROFIT DESIGN OR IS REJECTED. 11. SEE ARCHITECTURAL NOTES FOR CONCRETE FINISH REQUIREMENTS EXISTING STRUCTURES; 1. THE EXISTING FRAMING IS REPRODUCED FROM THE LATEST .INFORMATION PROVIDED. SOME FRAMING AND MATERIALS ENCOUNTERED AT THE TIME OF CONSTRUCTION MAY VARY FROM THAT SHOWN IN THE PLANS. IF THE PLAN CONDITION VARIES FROM THE AS -BUILT CONDITION, THE CONTRACTOR SHOULD CONSULT THE PROJECT TEAM FOR A REVISED DETAIL OR DIRECTION TO PROCEED. CONCRETE SLABS ON GRADE. 1. SLAB -ON -GRADE CONSTRUCTION SHALL BE SUPPORTED ON A 6 INCH LAYER OF CLEAN 3/4 INCH MINUS SUBGRADE COMPACTED TO A DENSITY OF NO LESS THAN 9511 OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY (ASTM D-1557). SUBGRADE SHALL BE SUPPORTED ON UNDISTURBED NATIVE SOIL OR PROPERLY PLACED AND COMPACTED STRUCTURAL FILL 2. INTERIOR SLABS -ON -GRADE SHALL BE CAST OVER A 4 MIL VAPOR BARRIER. 3. PROVIDE CONTROL JOINTS IN ALL SLABS ON GRADE. JOINTS ARE TO BE INSTALLED AT 14 TO 16 FEET ON CENTER EACH WAY MAXIMUM UNLESS SHOWN OTHERWISE ON THE DRAWINGS. ALL SAW CUT JOINTS IN CONCRETE SLABS ARE TO BE MADE WITH AN EARLY CUT SAW AS SOON AS POSSIBLE AFTER POURING BUT NO LATER THAN ONE HOUR AFTER FINISHING. 4. PROVIDE ISOLATION JOINTS AROUND ALL COLUMNS/SPREAD FOOTINGS. JOINTS SHALL BE FORMED BY INSERTING PREFORMED JOINT FILLER FOR THE FULL DEPTH OF THE SLAB. 5. PROTECT CONCRETE FROM DAMAGE OR REDUCED STRENGTH DUE TO COLD OR HOT WEATHER IN ACCORDANCE WITH ACI 305 AND 306. CONTRACTOR SHALL TAKE SPECIAL CURING PRECAUTIONS TO MINIMIZE SHRINKAGE CRACKING OF CONCRETE SLABS. 6. THE CONTRACTOR SHALL TAKE CARE THAT HEAVY EQUIPMENT AND AREAS USED FOR STAGING DO NOT AND DAMAGE SLABS ON GRADE. DAMAGED SLABS ON SHALL BE REPAIRED OR REPLACED AT NO ADDITIONAL EXPENSE TO THE OWNER. 7. CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2,500 PSI. UNLESS SPECIFIED OTHERWISE. CONCRETE OR MASONRY ANCHORAGE; 1. EXPANSION BOLTS INTO CONCRETE SHALL BE -KWIK BOLT TZ' AS MANUFACTURED BY THE HILTI CORP., INSTALLED IN STRICT ACCORDANCE WITH ICC-ES REPORT ESR-1917. SPECIAL INSPECTION IS REQUIRED. EXPANSION ANCHORS EXPOSED TO WEATHER SHALL BE STAINLESS STEEL BFINFQR(INSL 5TFFI - 1 . ALL DETAIUNG, FABRICATION, AND PLACEMENT OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH THE ACI MANUAL OF CONCRETE PRACTICE. 2. REINFORCING BARS SHALL BE DEFORMED AND CONFORM TO ASTM A615 OR A706, GRADE 60. REINFORCING TIE WIRE MAY BE GRADE 40. 3. REINFORCING STEEL SPLICES SHALL BE 40 BAR DIAMETER OR TWO TRANSVERSE WIRE SPACING FOR WIRE MATS. 4. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE ACCORDANCE WITH ACI 318. 5. NO.5 OR LARGER REINFORCING BARS SHALL NOT BE RE -BENT WITHOUT APPROVAL BY THE STRUCTURAL ENGINEER. 6. WELDING OF REBAR IS NOT ALLOWED WITHIN THE MIDDLE THIRD OF THE BAT LENGTH. WELDING OF REBAR IS CONDUCTED IN ACCORDANCE WITH AWS D1.4. USE ONLY ASTM A706 REINFORCING. 7. WIRE REINFORCING CONFORMS TO ASTM A82 OR A185. 8. CONCRETE COVER FOR REINFORCING STEEL CONFORMS TO ACI 318. FiECE,Pf MAY 07 2 Community Developmen [at&t 1111 W CAPITOL AVE RM 1070 WTTLE ROM AR 72201-3005 i •:.IasTec Network Solutions 4300 STOCKTON DRIVE, NORTH LIME ROM AR 72117 501-260-7633 RATIOre 61e201e 04/19 /18 1 P IE OR UPEER W DIRECT SUPERVISION AND TWLT I Ail A DULY REGISTERED OF TIE STATE OF INISIINSTCW REVISIONS REV. DATE DESCRIPTION Ifl S A 03/17/18 90% CD'S GJJ 0 04/19/18 FOR CONSTRUCTION VSA ® 05/02/18 CUM O Ible1TS GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. • SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY U SHEET NUMBER GN-1 ABBREVIATIONS. A/C AIR CONDMONING AGL ABOVE GROUND LEVEL AMSL ABOVE MEAN SEA LEVEL APPROX APPROXIMATELY AWG AMERICAN WIRE GAGE BCW BARE COPPER WIRE BLDG BUILDING BLK BLOCKING CLR CLEAR COAX COAXIAL CABLE CONC CONCRETE CONST CONSTRUCTION CONT CONTINUOUS DIA DIAMETER DWG DRAWING EA EACH ELEV ELEVATION ELEC ELECTRICAL EQ EQUAL EQUIP EQUIPMENT EXT EXTERIOR FIN FINISH FLUOR FLUORESCENT FUR FLOOR FT FOOT FRP FIBER -REINFORCED POLYMER GA GAUGE GALV GALVANIZED GC GENERAL CONTRACTOR GPS GLOBAL POSITIONING SYSTEM GRND GROUND HORZ HORIZONTAL HR HOUR HT HEIGHT HVAC HEATING VENTILATION AIR CONDITIONING ID INSIDE DIAMETER IN INCH INFO INFORMATION INSUL INSULATION INT INTERIOR IBC INTERNATIONAL BUILDING CODE LBS POUNDS LMU LOCATION MEASUREMENT UNIT LTE LONG TERM EVOLUTION MAX MAXIMUM MECH MECHANICAL MTL METAL MFR MANUFACTURE MGR MANAGER MIN MINIMUM MISC MISCELLANEOUS NA NOT APPUCABLE NIC NOT IN CONTRACT NTS NOT TO SCALE OC ON CENTER OD OUTSIDE DIAMETER PLYWD PLYWOOD PROJ PROJECT PROP PROPERTY PT PRESSURE TREATED REQ REQUIRED RF RADIO FREQUENCY RM ROOM RO ROUGH OPENING RRH REMOTE RADIO HEAD RRU REMOTE RADIO UNIT SHT SHEET SIM SIMILAR SPEC SPECIFICATION SF SQUARE FOOT Alt • REVISION -¢ FIRE HYDRANT 31 UGHT STANDARD D4 GATE VALVE Ev POWER VAULT ® WATER METER ® UTILTIY BOX jra FIRE STAND PIPE 0 UTILITY POLE ❑ CATCH BASIN, TYPE I E- POLE GUY WIRE ® CATCH BASIN. TYPE II Ij GAS VALVE n SIGN ❑O GAS METER o BOLLARD r=j TELEPHONE VAULT o MAIL BOX 0 TELEPHONE VAULT • 234.21 SPOT ELEVATION O GRID REFERENCE p DETAIL REFERENCE l:J GRID REFERENCE .® D SECTION REFERENCE REVISION — ROW — -CGAX - OH? P GAS OHU- TI- x x SUBJECT BOUNDARY UNE RIGHT -OF- WAY CENTERUNE RIGHT-OF-WAY UNE ADJACENT BOUNDARY UNE SECTIONAL BREAKDOWN UNE COAX CABLE LINE FIBER OPTIC CABLE LINE OVERHEAD POWER LINE BURIED POWER LINE BURIED GAS LINE OVERHEAD TELEPHONE LINE BURIED TELEPHONE LINE BURIED WATER LINE BURIED SANITARY SEWER BURIED STORM DRAIN DITCH LINE/FLOW LINE VEGETATION UNE CHAIN LINK FENCE WOOD FENCE BARED WIRE/WIRE FENCE MAY 07 20 Community Developmer at&t 1111 W CAPITOL RVE KW 1070 UTIE ROCK, AR 72201-3005 RAMS PREMED BY • i •:.IasTec Network Solutions 4300 SIOCKTON ME, NORM UTTIE ROCK AR 72117 501-260-7633 I 1 HEREBY CiRIIFY 11MT N ESE RUNS DERE CIRECT SUPERMONDig I#IADULY REGISTERED DOM UPCER IHE OF THE STATE OF 9PSHINGTON. REVISIONS REV. L1A1E DESCRIPTION HMS A 03/17/18 90% CD'S GU 0 04/19/18 FOR CONSTRUCTION VSA ® 05/02/18 QJENT OOM&NTs GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THEE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOWTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY SHEET TITLE GENERAL NOTES SHEET NUMBER GN-2 .0. 0 0RTIAIISRMlEPAIifD [ ,......., at&t 1lnwawra�RM10T0 UTUE BOCK, AR 72201-3008 NOTICE CAUTION , Cc� j1� (((4) -III Network NORTH B� asTec Solutions 1300 SIOgRON .RUE ROCK, 501-260-7633 ORME, M 72117 Beyond This Point you are entering a controlled area where RF emissions may exceed the FCC Beyond This Point you are entering a controlled area where RF emissions may exceed the FCC ALERTING SIGN ALERTING SIGN ALERTING SIGN General Population Exposure Limits. Follow all posted signs and site guidelines for working in a RF environment. Occupational Exposure Limits. Obey all posted signs and site guidelines for working in a RF environment. (FOR CELL SITE BATTERIES) (FOR DIESEL FUEL) (FOR PROPANE) MOH, GENERAL SIGNAGE GUIDELINES ese4.-oF A Q.tP$L WASyq.oFO •P. v' v. z RA'4. o , A :' EXPIRATION: 04 18 19 18 `• Ref: 47CPR 1.130Tro) atat •/ `• att • •S Ref: I7CFIt 1.1s07ro} T Structure Type INFO SIGN #1 INFO SIGN #2 INFO SIGN #3 ALERTING SIGNS A Towers Y Monopole/Monopine/Monopalm entrance gates, shelter doors OR on the outdoor cabinets climbing side of the Tower On backside of Antennas WARNING! 0�`t • DANGER DO NOT TOUCH TOWER! sERlovs RF BURN HAZARD! MAINTAIN AN ADEQUATE CLEARANCE BETWEEN TOWER SUPPORTS AND GUY WIRES FAILURE'. OBEY ALL POSTED SIGNS AND SITE GUIDELINES FOR W000ING IN A RADIO FRFCUENCYENYDwNTr�TGOGIDRESULT IS SERIOUS INJURY. CO TACTCURRFNF MAY EXCEED LIMITS PRESCRIBED INANSI/EEE casa-.yy° FOR CONTROLLED ENVIRONMENTS.A PROPERTY OF AT&T AUTHORIZED PERSONNEL ONLY - A C SDE Towers / Towers with high oltage ga entrance gates, shelter doors OR on the outdoor cabinets climbing side of the Tower On backside of Antennas 1 NtREHYY 1W►T MSC PIAt6 w>:RE PREMED ED Br MEOR Iltoat MT OIRECT SUPBM9ON NC MAT I MA A DULY RD351E1ED DICKER MIER DE UM OF THE K 3 Light Poles Flag Poles entrance gates, shelter doors OR on the outdoor cabinets on the pole, no less than 3ft below the Antenna and no less than 9ftabove ground On backside of Antennas REVISIONS REV, DATE DESCRIPTION M1MlS 03/17/18 .T/A CD'S GJJ 0 04/19/18 FOR OOPISTRUCDON VSA F Utility wood Poles (IPA) entrance gates, shelter doors OR on the outdoor cabinets on the pole, no less than 3ft below the Antenna and no less than 9ft above ground On backside of Antennas • + t • IN CASE OF EMERGENCY, OR PRIOR TO ® 05/02/18 CUMCameosGmCALL PERFORMING MAINTENANCE ON THIS SITE, BOO —63B-2822 AND REFERENCE CELL SITE NUMBER - - `• •J E E T Microcells mounted on non -IPA poles entrance gates, shelter doors OR on the outdoor cabinets on the pole, no less than 3ft below the Antenna and no less than 9ft above ground On backside of Antennas ALERTING SIGN INFO SIGN #4 NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET Roof Tops + W a } l8it F At all access points to the roof X THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. R On AntEnnas X Concealed Antennas X X INFORMATION O Antennas mounted facing outside the building X X m ATBT.p..ele.mmm,im6m . I. aatea..I k ,.0.b .a. Rem. leasto, 3feet away fr.R,.ntenn..mall obey posted sig.Roof ...(a)d..v.D&n T ....�A dma.ma&a nt the dantenna(s) Prior b mr...ing.Y M Antennas on support structure X X view Graph: A Radiation area is within 3ft from antenna X adjacent to each antenna SC78 HWY 99 & HWY 599 10868 E. MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY N Radiation area is beyond 3ft from antenna adjacent to each antenna �O.ATYral "ne`Wr,p. rAMT.���b INFORMATION Cont. the m.d,.mentoff..unma..r/tutehiet.bfound®na.a. ACTIVE ANTENNAS ARE MOUNTED T E N Church Steeples Access to steeple adjacent to antennas if antennas are concealed On backside of Antennas INFORMACION IG ❑ BEHINOTHIBPANBL 0 ON1HL95TRUCNRE SHEET TITLE , R.7,. SIGNAGE DETAILS ? " x �. I L J18 Eirm Froptdad re atlna ante. de telecorn.dentiones op.,.,,, p..A"T. Faro manna, m. dB .d. de.. mean de s 14b14b44.a., m3o6.Nm e®�.®el prop....w.a..as.de m ante. m°.ee Mb.. oen.. • trot dbp.h de memdes pe de b.Tenn. A'hT- teed ro.&a m.L°An m.andm,.am. Canton.. arm npndwa.aa deh.atew de AThT. Liu ahantlpv Wavvmero- Faun roma.=eon It add. de h.dmbh.nd.ddS&b data punt , .wtpann se...re.ta elated.. STAY BACK A MINIMUM OF 3 FEET FROM THESE ANTENNAS Noonh.prioATnT at_.adf.Bm.Wd, ta.°au®pdmmpalmmb,.�m.b�.a.m eep.In doer dna J fed from We a.tmvu ThbbATATdu. N A Water Stations Access to ladder adjacent to antennas if antennas are concealed On backside of Antennas ���ppp pp � - z"" + ^tea fd Notes for Rooftop sites: MAY 0 7 MAY • atet • atet l a a 1. Either NOTICE or CAUTION signes need to be posted at each sector as close as possible to: the outer edge of the striped off area or the outer antennas of the sector. 2. If Roofview shows: only blue + Notice Sign, blue and yellow = Caution Sign, only yellow = Caution Sign to be installed. Comm UT Developrr Ir/ SHEET NUMBER E nt S-1 INFO SIGN #1 INFO SIGN #2 INFO SIGN #3 SIGNAGE GUIDELINES CHART I NOTES; 1. VERIFICATION THAT THE ANTENNA MOUNTS CAN SUPPORT ALL PROPOSED LOADING SHALL BE PERFORMED BY REGISTERED STRUCTURAL ENGINEER. 2. STRUCTURAL ANALYSIS AND DESIGN TO BE PERFORMED PRIOR TO FCD COMPLETION. 3. THIS IS NOT A SITE SURVEY. ALL PROPERTY UNES AND BOUNDARIES ARE TAKEN FROM AN EXISTING PARCEL VIEWER AND ARE APPROXIMATE. • • RF SAFETY NOTE; AT&T HAS IMPLEMENTED RF SAFETY PROCEDURES AND ACTIONS ON THIS ROOFTOP SITE. ALL GENERAL SAFETY RECOMMENDATIONS WILL BE FOLLOWED IN ORDER TO COMPLY WITH FCC & COUNTY GUIDELINES. SUBJECT ZONING USE: SERVICE BUILDING ZONE:MIC/H . PARCEL NUMBER: 0323049057 EXISTING BUILDING EXISTING AT&T 20'-0 x 12.-0" CONCRETE PAD EXISTING _ CHAIN —LINK FENCE — — — - PROPERTY LINE EXISTING MONOPO \-o ca m EXISTING --I/ PARKING AREA (TYP.) raft MAY 0 Comm Develol ©D NORTH [ Aii;.-.0, at&t 1111 W OBIS( RE FM 1070 LITRE ROCK, IR 72201-3005 I,AIU r,w u HI• •. asiec Network Solutions 4300 SIOCIRON DRIVE. NORTH UTTIE ROCK, AR 72117 501-260-7633 1 EXPIRATIOPL 18 04 19/18 1f7iEHI CERRFY 1}N THESE RIMS WERE FREPPBED BY SUPERASICN MD DIRECT 1HTu 1AMADULY FB15IERED THE STATE OF REVISIONS REV. DATE DESCRIPTION NIWS A 03/17/18 90% CD'S GJJ 0 04/19/18 FOR CCNSTRUCT1ON VSA ® 05/02/18 cum OOM.€41S GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET e THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY SHEET TITLE 1 tim .. - SITE PLAN 2018 a y r Iel)Y SHEET NUMBER A-1 SITE PLAN 0, 1(1 0 30 SCALE: 1/32'-1•-0" (22:34) (OR) 1/64"-1'—O" (11a17) 1 • EXISTING AT&T EQUIPMENT CABINETS TO REMAIN (TYP.) EXISTING AT&T ICE BRIDGE TO REMAIN (6) EXISTING AT&T 7/8" COAX CABLES TO REMAIN (3) EXISTING AT&T RRH2X60-850 TO REMAIN EXISTING AT&T 20'-0" X 12'-0" EQUIPMENT CONCRETE PAD TO REMAIN aD NORTH EXISTING AT&T EOUIPMENT CABINETS (TYP.) EXISTING AT&T 20.-0" X 12.-0" EQUIPMENT CONCRETE PAD EXISTING AT&T ICE BRIDGE (6) EXISTING AT&T 7/8" COAX CABLES (3) EXISTING AT&T RRH2X60-850 INSTALL (1) PROPOSED AT&T 5C BCEM CARD, (1) PROPOSED AT&T 2C BCEM CARD, (1) PROPOSED AT&T 6C BCEM CARD, (1) PROPOSED AT&T DC TO DC CONVERTER, (4) PROPOSED AT&T CONVERTER MODULES & (1) PROPOSED AT&T RAYCAP INSIDE (1) PROPOSED AT&T FSM4 EXISTING AT&T CABINET MAY 07 Commun Devel m 413 NORTH 1111 W CAFITOL AVE RR 1070 LIME ROCK, AR 72201-3005 PING PREPARED Br. • •:11asiec Network Solutions uao sionna ani xanx umE wa w mn Network Solutions 4303 SiOaaa1 ORNE; NORTH URIE ROOK. AR 72117 bi-tau 501-260-7633 • 1 PREPAREDOAR UNIR Iff OR& f REGISTEAm�EDtW9°NMI) 1}11T BxiN6 R UNDER ITHE INAS OF 1HE STIUE OF 11P81614 IOI4f REVISIONS REV. DATE DESCRIPTION ROILS A 03/17/18 90% CD'S GJJ O 04/19/18 FOR CONSTRICTION VSA ® 05/02/18 CUEM COMIETDS GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASIEC NETWORK SOLUTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY SHEET TITLE t [KITING & PROPOSED EQUIPMENT PLAN )I It SHEET NUMBER A-2 EXISTING EQUIPMENT PLAN 0® SCALE: 3/8' = 1'-0' (24x36) (OR) 3/16' x 1'-0' (11x17) 2 PROPOSED EQUIPMENT PLAN O® SCALE: 3/8' = 1'-0' (24x38) (OR) 3/16" x 1'-0' (11x17) 1 C.L. TING PANEL ANTENNAS (BY OTHERS) ELEV. 1P 0' AGL $TOP OF TOWER ELEV. 121.-0" AGL EXISTING PANEL ANTENNAS (BY OTHERS) (TYP.) (2) EXISTING AT&T 3JR52703AAAA ANTENNAS TO BE REMOVED, (1) PER SECTOR IN POSITION 1, (ALPHA & GAMMA SECTORS) (2) EXISTING AT&T SBNHH-1D65C ANTENNAS TO REMAIN, (1) PER SECTOR IN POSITION 3, (ALPHA & GAMMA SECTORS) (3) EXISTING AT&T 625 RRH4X25—WCS-4R TO REMAIN, (1) PER SECTOR IN POSITION 3, (TYP. OF 3 SECTORS) Alp C.L. OF EXISTING AT&T PANEL ANTENNAS q ELEV. 80'-0" AGL (6) EXISTING AT&T LGP 21401 TMA'S TO REMAIN, (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (6) EXISTING AT&T DIPLEXERS TO REMAIN, (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (2) EXISTING AT&T SQUID TO REMAIN TO REMOVED, (1) PER SECTOR INNNAS POSRION 2, (1YP. OF 3 SECTORS) (3) EXISTING AT&T RRH2x40W-07L TO REMAIN, (1) PER SECTOR IN POSITIONS 1, (TYP. OF 3 SECTORS) EXISTING 121'-0" MONOPOLE EXISTING BUILDING EXISTING AT&T GPS ANTENNAS EXISTING AT&T UTILITY H—FRAME EXISTING AT&T EQUIPMENT CABINETS (TYP.) EXISTING AT&T 20.-0" X 12'-0" EQUIPMENT CONCRETE PAD T • EXISTING LIGHTNING ROD (6) EXISTING AT&T 7/8" COAX CABLES TO REMAIN EXISTING EOUIPMENT SHELTERS (TYP.) (BY OTHERS) EXISTING CHAIN —LINK FENCE AL FINISHED GRADE (REF.) ELEV. 0'-0" AGL 6\14- C.L. 0' E. TING PANEL ANTENNAS ELEV. 123 0" AGL ATOP OF TOWER ELEV. 121.-0" AGL (BY OTHERS) l EXISTING PANEL ANTENNAS (BY OTHERS) (TYP.) (2) EXISTING AT&T SBNHH-1065C ANTENNAS, (1) PER SECTOR IN POSITION 3, (ALPHA & GAMMA SECTORS) (3) EXISTING AT&T B25 RRH4X25—WCS-4R, (1) PER SECTOR IN POSITION 3, (TYP. OF 3 SECTORS) C.L OF PROPOSED AT&T PANEL ANTENNAS Nv ELEV. 80'-0" AGL 4C.L. OF EXISTING AT&T PANEL ANTENNAS [rELEV. 80'-0" AGL NOTES; CONCEALMENT WILL MATCH EXISTING. EXISTING LIGHTNING ROD W4H (6) EXISTING AT&T LGP 21401 TMA'S, — (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (6) EXISTING AT&T DIPLEXERS, (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (1) PROPOSED AT&T SQUID (2) EXISTING AT&T SQUID EXISTING 121.-0" MONOPOLE EXISTING BUILDING EXISTING AT&T GPS ANTENNAS EXISTING AT&T UTILITY H—FRAME EXISTING AT&T EQUIPMENT CABINETS (TYP.) (STING AT&T EQUIPMENT CONCRETE PAD r � t ofo (3) PROPOSED AT&T RRH 4T4R B12/B14, (1) PER SECTOR IN POSITION 2, (TYP. OF 3 SECTORS) —SEE DETAIL 2/A-4 (2) PROPOSED AT&T SBNHH-1D65C ANTENNAS, (1) PER SECTOR IN POSITION 1, (ALPHA & GAMMA SECTORS) — SEE DETAIL 1/A-4 (3) EXISTING AT&T RRH2x40W-07L, (1) PER SECTOR IN POSITIONS 1, (TYP. OF 3 SECTORS) (3) PROPOSED AT&T 825 RRH4X30-4R, (1) PER SECTOR IN POSITION 1, (TYP. OF 3 SECTORS) —SEE DETAIL 5/A-4 (3) PROPOSED AT&T B66A RRH4X45, (1) PER SECTOR IN POSITION 2, (TYP. OF 3 SECTORS) — SEE DETAIL 8/A-4 (2) PROPOSED AT&T 80010966 ANTENNAS (1) PER SECTOR IN POSITION 2, (ALPHA & GAMMA SECTORS) — SEE DETAIL 6/A-4 (6) EXISTING AT&T 7/8" COAX CABLES EXISTING CHAIN —LINK FENCE A,FINISHEDGRADE (REF.) ELEV. 0'-0" AGL MAY 0 7 Commu Developr wootx at&t 1111 It CAROL WE RM 1070 LITTLE ROCK. AR 72201-3005 PUNS PREPARED Br: •:.HasTec Network Solutions NORTH UTTIE ROC(, OR 72117 501-260-7633 • i EXPIRATIOP! 18 04 19/18 �KRIM DPI MBE R/J6 VIRE P IYECR MIR lif ERECT SUPERMEN EN AND THE I NA A DULY REGISTERED EI ER OF THE REVISIONS REV. DATE DESCRIPTION INNS A 03/17/18 90% CD'S G.0 0 04/19/18FOR CONSTRUCTION VSA ® 05/02/18 CUENT mamas Gil NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WTTHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. • SC78 HWY 99 & HWY 599 10868 E. MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY • SHEET TITLE EXISTING & PROPOSED TOWER ELEVATION MEET NUMBER A-3 EXISTING TOWER ELEVATION 0 2 4 SCALE: 1/8' = 1'-O (24x36) (OR) 1/16'=1'.0 (11x17) 2 PROPOSED TOWER ELEVATION 0 Y® SCALE: 1/8' = 1'.0 (24x36) (OR) 1/16' = 1'.0 (11x17) 1 ♦ _ -----, FL-LUOfM R66A-RRN4X43 DIMENSIONS. NAIAD: 25.8'x11.8-x7.2' WBGHT.wr UT MouNnNG KIT: Krt: 56.8 IDs 8' MOUNTING PIPE CNIRER ,(11 atsct 1111 W MIDI ME RM 1070 LITRE ROCK AR 72201-3005 i KATHREIN 80010965 , DIMENSIONS. HXWXD: 78.7'x20'x6.9' NET WEIGHT: 97.6 LBS CONNECTOR: 8 x 4.3-10 FEMALE CONNECTOR POSfT10N: BOTTOM i• m O_% t t ' PREPARED IIIIN O i i o 11111111111111111111.111.1M11 'SQUID" MIS • Network MORDI BY: a sTe Solutions 4300 STOCKTON MI6 ROM. 501-260-7633 % c ORME, IR 72117 -imi RAYCAP DC — — — SURGE PROTECTOR , ���������������►������������� ---mm 1 --- ---•kag; TO BE 1 mop on INSTALLED WITHIN 6 c , 258• 10E --- FEET OF RADIO UNIT — — — J —+7 1 — — — t 1.8' i i MANUFACTURER: RAYCAP MODEL: DC6-48-60-18-8F "SQUID' T 3 L M I "-I-I I= I p t 1 01 II ilil2i =— ei ,� • ■ o r Tel re 20" .0 e't' F wnsy,�'yF Fp 1C F. p fn llv Z . �i R 422 oror, A 19 1 18 .i' .+' �,s.s, zo" , -r r,', "„�„ MOUNTING BRACKET BY MANUFACTURER l�II!?!d 1�AN SIDE �� SCALE 9 SCALE 8 DC6 SQUID DETAIL SCALE 7 ANTENNA SPECIFICATION N.T.S. RRH SPECIFICATION N.T.S. N.T.S. ALCATEL-LUCENT B25 RRH4X30-4R NOTE- S`MA04 DIMENSIONS, HxWxD: 21.2 x11.97'x7.18" WEIGHT, WITHOUT MOUNTING KIT: 52.9 lbs 11,97" XATHREIN 80010964 DIMENSIONS, HXWXD: 96'x20'x6.9' NET WEIGHT: 114.E LBS CONNECTOR: 8 x 4.3-10 FEMALE CONNECTOR POSITION: BOTTOM �, �, PROPOSED RRH UNISTRUT SECURED TO MOUNTING PIPE (Typ.) r- — (r7FJ v = _ C = = — = — _ = —• = — — _ �- 1. INSTALL ANCHORS/FASTENERS . MAXIMUM OF 2.-0" ON 2. THROUGH BOLT - 1 /4'0 THREADED ROD W/ NUTS WASHERS ANCHORS AND CHANNEL SHALL HAVE GALVANIZED FINISH. 3. MOUNT UNISTRUT TBOLTINGUT 3/8"0 HARDWARE AND SPRING TYPICAL FOUR PER DEVICE. SUBCONTRACTOR SHALL 4.SUBCONTRACTOR SHALL OTHER MATERIALS AND MOUNTING HARDWARE. CENTER. A36/A307 AND UNISTRl1T� HOT -DIPPED WITH NUTS. SUPPLY. SUPPLY INSTALL A ALL ALL MEW CERTIFY TENT THESE MG MERE PREMEDFMAE qt DICER 1 S1lRRASI 4 NV DMZ I AM A DILY ER LINER DE VMS OF DE OFF X I 1 11.97" X X I 4 I I I I REVISIONS o DESCRIPTION 03�1 �18 GJJ o I� IIII III m O 0 04/18/18 FOR OONST1 JCfl0N VSA ^ ■ ■ ® o ®06/02/18 C1JEJ4T cameos GJJ o 0 �± N me O ttt _ 20 �, uu II a71P - t7 NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET A.9-. J. 20" �. ELM EESINE _ DIME THE INFORMATION CONTAINED IN TM DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. SCALE 6 SCALE RRH MOUNTING DETAIL SCALE 4 RRH SPECIFICATION N.T.S. }� 5 ANTENNA SPECIFICATION N.T.S. �-� --� N.T.S. mil! 1• + ���/ a 1 •�;; '• --1MOUNTING %a" •I)Q {��:i - PROPOSED LTE PANEL ANTENNA � 1. INSERT SCISSOR BRACKETS ANTENNA MOUNTING KIT BETWEEN THE UPPER ANTENNAmin BRACKET AND THE UPPER POLE ADAPTER BRACKET. SECURE USING 1/2 INCH HARDWARE PROVIDED. 2. TO SET THE DEGREE OF DOWNTILT, ALIGN THE DESIRED HOLES ON THE SCISSOR AND SECURE USING 5/16 INCH HARDWARE PROVIDED. 3. THE NUMBER OF CONNECTORS VARY BASED ON ANTENNA EXISTING ANTENNA PIPE MOUNT 4 107)nA - RRH 4T4R 812l814 COOMMSCOPE SBNHH-1D65C a ' 7 DIMENSIONS. HxWxD: 28.74'x15.35'x9.44' WEIGHT, WITHOUT MOUNTING KIT: 101.41 LEIS v DIMENSIONS, HXWXD: 72.0%11.9%7.1' NET WEIGHT: 40.6 LBS CONNECTOR: (6) 7/16 FEMALE CONNECTOR POSITION: BOTTOM DIN c n _ o p Ca Ul SC78 HWY 99 & HWY 599 10868 E. MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY o I I I1111 SHEETsi SHf TITLE �C UIPMENT DETAILS EZ o 9•µ _ o 0 28.74" ■ ■ ■ ■ 1Ca ‘'' -1535• -- ICE 7 � '�j� ' - - 13 15.35" OMNI \ IMIA I, 11.9- I- L1Y 7.1' I I. • C7130 11.9" I. BEET NUMBER A-4 6 //A ddd ELAN SIDE 1:1348Q AAd ANTENNA MOUNTING DETAIL SCALE 3 SCALE SSE SCALEANTENNA RRH SPECIFICATION N.T.S. N.T.S. SPECIFICATION N.T.S. 1 • IIP CAS 1 at&t 1111 W CAPITOL NOE IWI 1070 UME ROCK AR 72201-3005 A PUWS •4IasTec Network NORTH AiEPNRED r. Solutions /300 s CCICTON UITUE ITOC(, 501-260-7633 OM. AR 72117 �P�L MOyq pQ 0* WAsyb�.iC tea 0 ci lle Z -i _ 42214 R�'S�o' A .+ EXPIRATION: 04 18 19 18 SCALE 9 SCALE SCALE I NOT USED N.T.S. NOT USED N.T.S. NOT USED N.T.S. 7 • 1 HEREBY CERTIFY DID THESE PUNS MERE MINED BY1EORUNDER MYCRBCT FESTERED ENGINEER t1ER THE MS OF DE STALE OF MAR#lGIOM' REVISIONS REV. DATE DESCRIPTION NTUIS A 03/17/18 90% CD'S GJJ 0 04/19/18 FOR OOrSTRUCD0N VSA ® 05/02/18 CLIENT OOMEMIS GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. ' SCALE 6 SCALE SCALE 4 NOT USED N.T.S. NOT USED N.T.S. NOT USED N.T.S. - COOMMSCOPE SBNHH-1D6512 DIMENSIONS, HXWXD: 72.0"x11.9"x7.1" NET WEIGHT: 40.6 LBS CONNECTOR: (6) 7/16 DIN FEMALE CONNECTOR POSITION: BOTTOM 0 n 0 n CI e f A.-7 tC; a 1 SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY SHEET TIM . J IPMENT DETAILS E 0 o> • ■ 0 7u ' I II II 9 L a e.A.. 1 SHEET NUMBER A-4.1 AAA ELM XI SCALE 3 SCALE • 2 SCALE 1 NOT USED N.T.S. NOT USED N.T.S. ANTENNA SPECIFICATION N.T.S. - - W MIII EXISTING RF EQUIPMENT SCHEDULE SECTOR FREQUENCY BAND ANTENNA MAKE /MODEL RAD CENTER AZIMUTH E TILT M.TILT TMA/DIPLEXER (OTY.) SURGE PROTECTION (OTY.)' CABLES (OTY.) CABLEPOSITION LENGTH 108'-O• Al LTE 1900/700 (1) AW AA 3J152703AMA (R) 80'-0' 180' 7/5' 7 (1) RRH2x40W-07L (E) (2) SQUID (E) (2) 7/8• COAX (1) 1.12' HYBRID A2 WITS 1900/830 (1) KATHREN 742-254 (R) 80'-0' 180' 8117 0' - - - - A3 LTE WCS/BSI (1) COMMSCOPE SBNNM-1063C (E) 80'-0• 180' 0'/4'/V 7 (1) RRH2x60-850 (E) ((ON GROUND) (1) RRH4x25—WCS-4R (E) — (2) 7/8• COWL (2) 0.76' 8 AWG 6 1_0- 08• A4 (MTS 1900/850 (1) KATHREIN 742-264 (E) 80'-0' 180' 8'/17 0' (2) LGP 21401 (E) (2) POLDER- (2) 7/8' COAX 108'-O' 81 LIE /000/700 (1) AW PA 382527031MA (R) 80'-0' 280' 7/5' 7 (1) RRH2x40W-07L (E) - (2) 7/8• COAX (1) 1.12' HYBRID 108.-0' 62 10115 1900/830 (1) KATNEN 742-264 (R) 80•-O 260' 17/4• a - - - - B3 LTE WCS/850 (1) COMMSCOPE SBNHH-11:3658 (E) 80'-0• 260' O/S/O' 7 _ (1) RRH2x60-850 (E) (ON GROUND). (1) RRH4x25-WCS-4R (E) - (2) 7/8• COAX (1) 0.76" 8 AWG 6 108•-0• B4 UMTS 1900/850 (1) KATHREIN 742-264 (E) 80'-0' 260' 014' 0' (2) LGP 21401 (E) (2) DPIDRR (R) - (2) 7/8' COAX 108'-0' C1 LTE 1900/700 (1) AW AA 313352703 (R) 80'-0' 60' 0'/3' 0' (1) RRH2x40W-07L (E) - (2) 7/8• COAX 108'-0' C2 NOS 1900/830 (1) KATHREIN 742-264 (R) 80'-0' 60' 0'/4' 0' - - - - C3 LTE WCS/850 (1) COMMSCOPE SBNHH-ID65C (E) 80'-0' 60' 0'/3/0' 0' (1) RRH2x60-850 (E) (ON GROUND) (1) RRH4x25-WCS-4R (E) _ (2) 7/8' COAX (1) 0.76' 8 AWG 6 108'-0' cos UMTS 1900/850 (1) KATHREIN 742-264 (E) 80'-0' 60' 7/4' p' (2) LGP 21401 (E) (2) OREM (R) - (2) 7/8• COAX 108'-0' (E) - EXISTING EQUIPMENT (R) = EXISTING EQUIPMENT TO BE REMOVED (XR)= EXISTING EQUIPMENT TO BE RELOCATED (6) EXISTING AT&T LGP 21401 TMA'S TO REMAIN, (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (3) EXISTING AT&T 742-264 ANTENNAS TO REMAIN, (1) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (1) EXISTING AT&T SBNHH-1D65B ANTENNA TO REMAIN IN POSITION 3, (BETA SECTOR) ANTENNA S EXISTING BNHH-1 D6SECTOR) 58 (BON ousTHG 74212 . 6Q - 92 EXISTING 121'-0" MONOPOLE EXISTING 742 64 ANTENNA PER SECT R (VP AZ. =260' - (BO (3) EXISTING 742-264 ANTENNAS TO BE REMOVED. (1) PER SECTOR IN POSITION 2. (TYP. OF 3 SECTORS) DING 1270 R (1) EXISTING AT&T 3JR52702MM ANTENNA TO BE REMOVED IN POSITION 1. (BETA SECTOR) (3) EXISTING RRH2X40W-07L TO REMAIN, (1) PER SECTOR IN POSITION 1, (TYP. OF 3 SECTORS) B2 z N z w 0O Z Z ,r) < - I U =as z z < m vi (f < z N W otte 11'1�ova (2) EXISTING AT&T SBNHH-1 D65C ANTENNAS TO REMAIN, (1) PER SECTOR IN POSITION 3, (ALPHA & GAMMA SECTORS) 03 SONS MP c, j S Q�.p, GPM G'S QPj EXISTING AT&T PLATFORM MOUNT .0 a (3) EXISTING AT&T RRH4x25-WCS-4R TO REMAIN, (1) PER SETCOR IN POSITION 3, (TYP. OF 3 SECTORS) (6) EXISTING AT&T DIPLEXER TO BE REMOVED. (2) PER SETCOR IN POSITION 4. (TYP. OF 3 SECTORS) (2) EXISTING AT&T SQUID TO REMAIN (2) EXISTING AT&T 3JR52703AAAA ANTENNAS TO BE REMOVED. (1) PER SECTOR IN POSITION 1. (ALPHA & GAMMA SECTORS) RECFEVE MAY 07 2011 Community Develop , t a® NORTH w6a1c at&t 1111 W COMM ROE RY 1070 UmLE ROCK, AR 72201-3005 PUSS PREPARED BY: r•:VIasTec Network Solutions 4300 aonna om� NMI um[ imc M mn m-ao-nu Network Solutions NOR URU: ROO(, 117 501-260-76i3 ♦ tow mire THAT THESE PUSS DERE PREMED BY NE OR DIEM SUPERVISION MDT u II MI DER NAY DULY REGISTERED BIGOEER UNCER DE WS OFSTATE OF WASHINGTON* THE REVISIONS REV. DATE DESCRIPTION HIWIS A 03/17/18 90% CD'S GJJ 0 04/19/18 FOR CONSTRUCTION VSA ® 05/02/18 cum OO J O4TS GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET 119 THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTIC NETWORK SOLUTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA. WA 98168 KING COUNTY SHEET TITLE 1-1 EXISTING ANTENNA PLAN & EQUIPMENT SCHEDULE SHEET NUMBER A-5 EXISTING ANTENNA PLAN & EQUIPMENT SCHEDULE 0 6- 1' 2' SCALE: 1/2' = I'-0' (24x36) (OR) 1/4' = 1'-0' (11x17) 1 • PROPOSED RF EQUIPMENT SCHEDULE • SECTOR POSITION FREQUENCY BAND ANTENNA MAKE /MODEL RAD CENTER AZIMUTH E. TILT M.TILT RADIO/TMA/DIPLEXER (QTY.) SURGE PROTECTION (QTY.) CABLES (QTY.) Al LTE 1900/700/AWS (1) COMMSCOPE SBNHH-1065C (P) 18U 7/7/4' 7 (1) RRH2x40W-07L (E) (1) 825 RRH4X30-4R (P) (2) SQUID (E) (2) 7/8' COAX (1) 1.12' HYBRID CABLE LENGTH 108'-0' A2 UMTS 1900/850 (1) KATHREIN 80010966 (P) 180' 6'/17 0' (1) 866A RRH4X45 (P) (1) RRH 4T4R 1312/14 (P) A3 LTE WCS/850 (1) COMMSCOPE SBNHH-1D65C (E) 80'-0' 180' 11411' 7 (1) RRH2:60-850 (E) (ON GROUND) (1) RRH4x25-WCS-4R (E) (2) 7/8' COAX (2)0.76"8AWG6 108.-0' M UMTS 1900/850 (1) KATHREIN 742-264 (E) 80'-0' 160' 6117 0' (2) LGP 21401 (E) (2) 7/8' COAX 108'-0' B1 LTE 1900/700/AWS (1) COMMSCOPE SBNHH-1D658 (P) 60-0. 260' 7/7/3' 7 (1) RRH2x40W-07L (E) (1) 825 RRH4X30-4R (P) (1) SQUID (P) (2) 7/8' COAX (1) 1.12' HYBRID 108'-0' B2 UMTS 1900/850 (1) KATHREIN 80010985 (P) 260' 0'/4' 0' (1) 868A RRH4X45 (P) (1) RRH 4T4R B12/14 (P) 83 LTE WCS/850 (1) COMMSCOPE SBNHH-10658 (E) 80'-O 260' 7/S/7 7 (1) RRH2x60-850 (E) (ON GROUND) (1) RRH4x25-WCS-4R (E) (2) 7/8' COAX (1)0.76"8AWG6 (1) 0.76' 8 AWG 6 108'-0' 84 UMTS 1900/850 (1) KATHREIN 742-264 (E) 80'-0' 260' 0'/4' 0' (2) LGP 21401 (E) (2) 7/8' COAX 108'-0' Cl LTE 1900/700/AWS (1) COMMSCOPE SBNHN-1D65C (P) 80'-0' 60' 7/7/3' D' (1) RRH2x40W-07L (E) (1) 825 RRH4X30-4R (P) (2) 7/8' COAX (1) 1.12' HYBRID 108'-0' C2 UMTS 1900/850 (1) KATHREIN 80010988 (P) 60' 014' 0' (1) B66A RRH4X45 (P) (1) RRH 4T4R 812/14 (P) C3 LTE WCS/850 (1) COMMSCOPE SBNHH-1D65C (E) 60'-0' 60' 01310' 0' (1) RRH2x60-850 (E) (ON GROUND) (1) RRH4x25-WCS-4R (E) (2) 7/8' COAX (1)0.76'8AWG6 (1)0.76'8AWG6 108'-0' C4 UMTS 1900/850 (1) KATHREIN 742-264 (E) 60' 0'/4' 0' (2) LGP 21401 (E) (2) 7/8 COAX 108'-0' (P) = PROPOSED EQUIPMENT (E) = EXISTING EQUIPMENT (XR)= EXISTING EQUIPMENT RELOCATED (6) EXISTING AT&T LGP 21401 TMA'S, (2) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (3) EXISTING AT&T 742-264 ANTENNAS, (1) PER SECTOR IN POSITION 4, (TYP. OF 3 SECTORS) (1) EXISTING AT&T SBNHH-1D65B ANTENNA TO REMAIN IN POSITION 3, (BETA SECTOR) EXISTING AT&T PLATFORM MOUNT EXISTING 121.-0" MONOPOLE TENNA EXI5TIN((TV. PER 742-264 SECTOR 1 4 AZ. =260' - (B ) 10658 ANTENNA EXISTING "WAN- BETA SECTOR AZ260 - (63) = (1) PROPOSED AT&T SQUID -SEE DETAIL 7/A-4 PROPOSED 80010E A TO 26C1 - (B2) c (1) PROPOSED AT&T 80010965 ANTENNA IN POSITION 2, (BETA SECTOR) - SEE DETAIL 1/A-4 (3) PROPOSED AT&T 866A RRH4X45, (1) PER SECTOR IN POSITION 1, (TYP. OF 3 SECTORS) - SEE DETAIL 5/A-4 NNA ANTE PROPOSED SBNHH-1p65B BETk tt (1) PROPOSED AT&T SBNHH-1D6513 ANTENNA IN POSITION 1, (BETA SECTOR) -SEE DETAIL 1/A-4.1 (3) PROPOSED AT&T B25 RRH4X30-4R, (1) PER SECTOR IN POSITION 1, (TYP. OF 3 SECTORS) - SEE DETAIL 5/A-4 (3) EXISTING RRH2X40W-07L, (1) PER SECTOR IN POSITION 1, (TYP. OF 3 SECTORS) co 0 0 co 0 (2) PROPOSED AT&T SBNHH-1D65C ANTENNAS, (1) PER SECTOR IN POSITION 1, (ALPHA & GAMMA SECTORS) -SEE DETAIL 1/A-4 (3) PROPOSED AT&T RRH 4T4R B12/14, (1) PER SECTOR IN POSITION 2, (TYP. OF 3 SECTORS) -SEE DETAIL 2/A-4 (2) PROPOSED AT&T 80010966 ANTENNAS (1) PER SECTOR IN POSITION 2, (ALPHA & GAMMA SECTORS) -SEE DETAIL 6/A-4 (2) EXISTING AT&T SBNHH-1D65C ANTENNAS, (1) PER SECTOR IN POSITION 3, (ALPHA & GAMMA SECTORS) (3) EXISTING AT&T RRH4x25-WCS-4R, (1) PER SETCOR IN POSITION 3, (TYP. OF 3 SECTORS) (2) EXISTING AT&T SOUID MAY 072018 Community Developmen 4® NORTH a**7..?``1.° at&t 1111 W CAPITOL AVE RM 1070 LIME ROCK, AR 72201-3005 pw HQJ'WCD 87: •:IasTec Network Solutions 4300 STOCKTON ORNE, NORTH UTTIE ROCK. AR 72117 501-260-7633 i ♦ PREPARED IE OR (IER D18.T SPWASION AND THAT I AM A DULY REGISTERED ENGOifR UNDER llf OFSTATE OF YASHRIGICtr THE REVISIONS REV. DATE DESCRIPTION NIV S A 03/17/18 90% CD'S Gal 0 04/19/18 FOR OONSTR)CIION %SA ® 05/02/18 CLIENT COMuENTS GJJ NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE. REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. SC78 HWY 99 & HWY 599 10868 E. MAR(NA1 WAY S TUKWILA, WA 98168 KING COUNTY SHEET TITLE PROPOSED ANTENNA PLAN & EQUIPMENT SCHEDULE SHEET NUMBER A-6 PROPOSED ANTENNA PLAN & EQUIPMENT SCHEDULE 0 6- 1' r SCALE: 1/2' = 1'43' (24x36) (OR) 1/4' = 1'-0' (11)(17) 1 • #6 AWG ANTENNA MOUNT GROUND TO SECTOR GROUND BAR (TYP.) -SEE DETAILS ON SHEET G-2 41> NORTH SYMBOL DESCRIPTION • 0 COPPER GROUND ROD CADWELD EXOTHERMIC WELD TEST WELL GROUND BAR GROUND WIRE /2 AWG GROUND RING FIELD VERIFY & TIE INTO EXISTING GROUNDING SYSTEM GENERAL NOTE& 1. ALL DETAILS ARE SHOWN IN GENERAL TERMS. ACTUAL INSTALLATION AND CONSTRUCTION MAY VERY DUE TO SITE SPECIFIC CONDMONS. 2. GROUND ALL ANTENNA BASES, FRAMES, CABLE RUNS, AND OTHER METALLIC COMPONENTS USING GROUND WIRES AND CONNECT TO SURFACE MOUNTED BUS BARS. FOLLOW ANTENNA AND BTS MANUFACTURER'S PRACTICES FOR GROUNDING REQUIREMENTS. GROUND COAX SHIELD AT BOTH ENDS AND EXIT FROM TOWER OR POLE USING MANUFACTURERS PRACTICES. 3. ALL GROUNDS CONNECTIONS SHALL BE CADWELD. ALL WIRES SHALL BE COPPER THHN/THWN. ALL GROUND WIRE SHALL BE GREEN INSULATED WIRE ABOVE GROUND. 4. CONTRACTOR TO VERIFY AND TEST GROUND SOURCE. GROUNDING AND OTHER OPERATIONAL TESTING WILL BE WITNESSED BY WIRELESS REPRESENTATIVE. 5. REFER TO DMSION 16 GENERAL ELECTRIC; GENERAL ELECTRICAL PROVISION AND COMPLY WITH ALL REQUIREMENTS OF GROUNDING STANDARDS. 6. ELECTRICAL CONTRACTOR TO PROVIDE DETAILED DESIGN OF GROUNDING SYSTEM. AND RECEIVE APPROVAL OF DESIGN BY AUTHORIZED WIRELESS REPRESENTATIVE, PRIOR TO INSTALLATION OF GROUNDING SYSTEM. PHOTO DOCUMENT AU. CADWELDS AND GROUND RINGS. 7. NOTIFY CONSTRUCTION MANAGER IF THERE ARE ANY DIFFICULTIES INSTALLING GROUNDING SYSTEM DUE TO SITE SOIL CONDITIONS. 8. USE PANI SCHEME FOR LOADING GROUNDS ON MGB AS DISCUSSED IN NSTD 119.33 & 36. DROUND ROD NOTES. 1. ELECTRICAL CONTRACTOR SHALL ORDER GROUND RESISTENCE TESTING ONCE THE GROUND SYSTEM HAS BEEN INSTALLED; A QUUFIED INDMDUAL, UTIUZING THE FALL OF POTENTIAL METHOD, SHOULD PERFORM THE TEST. THE REPORT WILL SHOW LOCATION OF THE TEST AND CONTAIN NO LESS THEN 9 TEST POINTS ALONG THE TESTING UNE. GRAPHED OUT TO SHOW THE PLATE. 2. POINT GROUND TEST OR 3 POINT 62R TESTS WILL NOT BE ACCEPTED AS ALTERNATIVES TO THE AFORE MENTION GROUND TEST. TEST SHALL BE PERFORMED WHILE THE COUNTERPOISE IS ISOLATED FROM THE A/C SYSTEM GRIDS AND EXISTING COMMUNICATION FACILITY. #6 AWG ANTENNA MOUNT GROUND TO SECTOR GROUND BAR (TYP.) SEE DETAILS ON SHEET G-2 EXISTING GROUND LEADS AT BASE OF TOWER CONTINUING TO GROUND RING (FIELD VERIFY) CADWELD (TYP.) SEE DETAIL 1 ON SHEET G-2 SECTOR GROUND BAR LOCATED EACH /-- SECTOR SEE DETAIL 3 ON SHEET G-2 (FIELD VERIFY LOCATION) EXISTING MAIN ANTENNA GROUND BUSS BAR (FIELD VERIFY LOCATION) m• '�r- C uxu li MAY 0 7 2010 Community Development NORTH A..m*itale? at&t 1111 W CAPITOL AC RM 1070 u t ROCK AR 72201-3005 .• •:IasTec Network Solutions NORTH UTT1E ROCK AR 72117 501-260-7633 MERBIT WEFT TIESE PM MERE PREPARED WIC OAR MIR MY CIRECT SUPSIMSION Ate DPW I AM A DULY REGISTERED IC MIER (t OF THE REVISIONS REV. DATE DESCRIPTION PAYS A 03/17/18 90% WS GJJ 0 04/19/18 FOR CONSTRICTION VSA & 05/02/18 CLIENT COMrEMTS GW NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY BY NATURE REPRODUCTION OR CAUSING TO BE REPRODUCED THE WHOLE OR ANY PART OF THESE DRAWINGS WITHOUT THE PERMISSION OF MASTEC NETWORK SOLUTIONS IS PROHIBITED. • SC78 HWY 99 & HWY 599 10868 E MARGINAL WAY S TUKWILA. WA 98168 KING COUNTY ♦ • 3 SHEET 1111E GROUNDING SCHEMATIC PLAN SHEET NUMBER G-1 SCHEMATIC GROUNDING PLAN 0 1S SCALE: 3/16' a 1'-0' (24x36) (OR) 3/32' .1*-0" (11417) 2 SCHEMATIC GROUNDING PLAN 0 6 1 SCALE: 1/2' = 1'-0' (24x36) (OR) 1/4' = 1'-0' (11417) 1 s V INSPECTION WINDOW REQUIRED FOR ALL BUTT CONDUCTOR • mat&t �� 1111 /CAPITOL AVE Tal 1070 UIRF ROCK, AR 72201- • NOTE: GROUND.LEAD INSIDE RUBBER GROMMET TO BE ATTACHED WITH X-CROSS ZIP TIES TO BRACKET. DO NOT USE SNAP -IN HANGERS AROUND GROUNDS. INTERIOR TWO -HOLE CONNECTORS INSULATION UP AGAINST TOOTHED THE CONNECTOR BARRELCOLD ■■� Network NORTH • a s Solutions IJ00 STOCKION UTUIE ROCK 501-2�763J • T e c ORNE, OR 72117 SECTOR ANTENNA \ EXTERNAL 3/8"0x1 1/2' SHROR EQUAL S/S NUT 1" MIN 1APPR0VEDINK S/S LOCK WASHER I 1 1 1 S/S FLAT WASHER 4- - - - — Q ANTENNA PIPE MOUNT r r _ _I_I1 j_/JJJ1111APPLY L NO-OX �- 1/4" MIN '''' W Syy44-/ 4 `4' �c' ci) ��e F. z ; P2ziQ c 4.. - +' A 04 18 19 18 TOP JUMPER \ 1 M M 1 CABLE TYP. ( ) S/S FLAT WASHER S/S BOLT (1 OF 2) GROUND BAR 0 TINNED COPPER GROUNDING BAR Y7: - COLD SHRINK OR APPROVED EQUAL "DO NOT DISCONNECT" TAG ON ALL GROUNDING BAR INTERCONNECTS�'rO� AND EQUALIZERS �---� "I KRIM CERRFY 1R T 1FE51: RUNS MERE PRERIFIEDJOVI Eff ME OR IT I A DIRECT SUPERVISOR AND 1FNT I MI A DULY METERED DIMMER LRCM THE WAS Cr THE STATEOF S EXTERIOR TWO HOLE LUG DETAIL SCALE 4 SCALE 2 ' RRUS UNIT , N.T.S. NOT USED N.T.S. #4 OR #6 AWG STRANDED CU CONDUCTOR WITH GREEN, 600V, THWN-2 INSULATION _ _, i� low % —/, `^ No,...,;• , \ `:E: TYPE SS TYPE PT JYPE GL REVISIONS REV. DATE DESCRIPTION W S A 03/17/18 SOIL CD'S GJJ JUMPER CABLES 0 04/19/18 FOR CONSTRUCTION VSA SECTOR GROUND BAR�1 GROUND BAR (VERIFY EXACT LOCATION IN FIELD) i - 0 - n _ - 0 - __. 0_ _ ®05/02/18 CLIENT OOMMETIIS GJJ I I ,�_� / I I RAYCAP DC6-48-60-18-8F UNIT \ �.` �W,....,..,,.: TYPE TA \r ' 'I)i(• � � • TYPE VN TYPE NQ t COLLECTION GROUND BAR �1AWL FIBER NOT FOR CONSTRUCTION UNLESS LABELED AS CONSTRUCTION SET O . O O U O O \/ O O v O v O v t/18' O• THE INFORMATION CONTAINED IN THESE DOCUMENTS IS PROPRIETARY ON OR CAUSINNGNTRO�BEERREPRODUCED THE WHOLE OR ANY PART OF THEE DRAWINGS WITHOUT THE PERMISSION OF UAS'TEC NETWORK SOLUTIONS S ` PROHIBITED. GROUND TO EQUIPMENT/TOWER GROUND BAR DC CONDUCTOR EQUIPMENT CABINET/RACK tli ���� TYPE W rt#0., \ TYPE VS AM) �� TYPE VB �'- (2) TWO EXOTHERMIC TO BE USED WITH #2 AWG SOLID BARE TINNED COPPER GROUND CONDUCTOR, EXOTHERMIC WELD TO BURIED GROUND RING AND GROUND BAR PVC NONMETALLIC CONDUT SCH 40 TYPE (NMC) CONDUIT WITH STRAP WITHIN TWO INCHES OF CONDUIT END �'�il tO C78 S& 99 & HWY 599 10868E MARGINAL WAY S TUKWILA, WA 98168 KING COUNTY ?I EXISTING GROUNDHWY BAR i w EXISTING GROUND I BAR I ' % `a Aka ' `9. Off.m a }/ MK. ertiO Q ALARM PANEL SHEET TITLE 'j ���" 0 ���� R G �7FIDI4�7G'DETAILS Development I I i• Il TYPE '; I� ,:: �� GT TYPE ` ►�• GY `� �` 0# TYPE GR 1NT ' �•�- COLLECTION GROUND BAR EQU GROUND EBAR --------� SHEET NUMBER G-2 SCALE 5 GROUND BAR DETAIL SCALE 3 SCALE 1 CABLE GROUNDING N.T.S. N.T.S. CADWELD DETAILS N.T.S.