HomeMy WebLinkAboutPermit D07-347 - NORTHWEST RESTAURANT - PARTITIONS, DOORS AND RELITESNORTHWEST
RESTAURANT
16000 CHRISTENSEN RD
SUITE 101
D07 -347
Parcel No.: 2523049077
Address: 16000 CHRISTENSEN RD TUKW
Suite No:
Cityf Tukwila
Owner:
Name: BRCP RIVERVIEW PLAZA LLC
Address: 248 HOMER AVE , PALO ALTO CA 94301
Phone:
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Tenant:
Name: NORTHWEST RESTAURANT
Address: 16000 CHRISTENSEN RD, STE 101 , TUKWILA WA
Contact Person:
Name: APRIL FILIPPI
Address: 2202 64 AV W , MOUNTLAKE TERRACE WA 98043
Phone: 425 670 -6706
Contractor:
Name: GATEWAY CONSTRUCTION SRVCS INC.
Address: 11414 NE 60TH ST , KIRKLAND, WA 98033
Phone: 425 - 822 -5178
Contractor License No: CATEWCS992C3
DESCRIPTION OF WORK:
NEW INTERIOR PARTITIONS, NEW DOORS, AND NEW RELITES.
doc: IBC-10 /06
DEVELOPMENT PERMIT
* *continued on next page **
Permit Number: D07 - 347
Issue Date: 10/19/2007
Permit Expires On: 04/16/2008
Expiration Date: 03/04/2008
Value of Construction: $8,600.00 Fees Collected: $346.41
Type of Fire Protection: SPRINKLER/AFA International Building Code Edition: 2006
Type of Construction: VB Occupancy per IBC: 0008
D07 -347 Printed: 10 -19 -2007
Public Works Activities:
Channelization / Striping: N
Curb Cut / Access / Sidewalk / CSS: N
City oTukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Fire Loop Hydrant: N Number: 0 Size (Inches): 0
Flood Control Zone:
Hauling: N Start Time: End Time:
Land Altering: Volumes: Cut 0 c.y. Fill 0 c.y.
Landscape Irrigation:
Moving Oversize Load: Start Time: End Time:
Sanitary Side Sewer:
Sewer Main Extension: Private: Public:
Storm Drainage:
Street Use: Profit: N Non - Profit: N
Water Main Extension: Private: Public:
Water Meter:
doc: IBC-10 /06
N
Permit Center Authorized Signature: // U\I \lN�`� 7�/11iJLJt Date:
I hereby certify that I have read and s ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complie , whether specified herein or not.
The granting of this • ermit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or th ` ormance of wo . I = •* orized to sign and obtain this development permit.
Signature: ' ' Date:
/0 "../ "7
Print Name: 6h4-pin 0 K
Permit Number: D07 -347
Issue Date: 10/19/2007
Permit Expires On: 04/16/2008
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
D07 -347 Printed: 10 -19 -2007
Parcel No.: 2523049077
Address:
Suite No:
Tenant:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16000 CHRISTENSEN RD TUKW
NORTHWEST RESTAURANT
1: ** *BUILDING DEPARTMENT CONDITIONS * **
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
D07 -347
ISSUED
09/11/2007
10/19/2007
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431 - 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: New suspended ceiling grid and light fixture installations shall meet the non - building structures seismic design
requirements of ASCE 7.
6: Partition walls that are tied to the ceiling and all partitions greater than 6 feet in height shall be laterally braced
to the building structure.
7: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
8: There shall be no occupancy of a building until final inspection has been completed and approved by Tukwila building
inspector. No exception.
9: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
10: All construction noise to be in compliance with Chapter 8.22 of the City of Tukwila Municipal Code. A copy can be
obtained at City Hall in the office of the City Clerk.
11: Ventilation is required for all new rooms and spaces of new or existing buildings and shall be in conformance with the
International Building Code and the Washington State Ventilation and Indoor Air Quality Code.
12: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
13: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206 - 431- 3670).
14: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: Cond -10/06
D07 -347 Printed: 10 -19 -2007
15: ** *FIRE DEPARTMENT CONDITIONS * **
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
17: The total number of fire extinguishers required for a light hazard occupancy with Class A fire hazards is calculated at
one extinguisher for each 3,000 sq. ft. of area. The extinguisher(s) should be of the "all purpose" (2A, 10 B:C) dry
chemical type. The travel distance to any extinguisher must be 75' or less. (IFC 906.3) (NFPA 10, 3 -2.1)
18: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or
brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation
instructions. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so
that its top is not more than 5 feet (1524 mm) above the floor. Hand -held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the
floor. The clearance between the floor and the bottom of the installed hand -held extinguishers shall not be less than 4
inches (102 mm). (IFC 906.7 and IFC 906.9)
19: Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot
be completely avoided, means shall be provided to indicate the locations of the extinguishers. (IFC 906.6)
20: Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available
for use. These locations shall be along normal paths of travel, unless the fire code official determines that the
hazard posed indicates the need for placement away from normal paths of travel. (IFC 906.5)
21: Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached that
indicates the month and year that the inspection was performed and shall identify the company or person performing the
service. Every six years stored pressure extinguishers shall be emptied and subjected to the applicable recharge
procedures. If the required monthly and yearly inspections of the fire extinguisher(s) are not accomplished or the
inspection tag is not completed, a reputable fire extinguisher service company will be required to conduct these
required surveys. (NFPA 10, 4-3, 4-4)
22: Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
(IFC 1008.1.8.3 subsection 2.2)
23: Dead bolts are not allowed on auxiliary exit doors unless the dead bolt is automatically retracted when the door handle
is engaged from inside the tenant space. (IFC Chapter 10)
24: Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the
International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. (IFC
1008.1.8.1)
25: Exit hardware and marking shall meet the requirements of the International Fire Code. (IFC Chapter 10)
26: Aisles leading to required exits shall be provided from all portions of the building and the required width of the
aisles shall be unobstructed. (IFC 1013.4)
27: Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress
travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access
corridor is more than 100 feet (30,480 nun) or the listed viewing distance for the sign, whichever is less, from the
nearest visible exit sign. (IFC 1011.1)
28: Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with
the principal strokes of the letters not less than 0.75 inch (19.1 mm) wide. The word "EXIT" shall have letters having
doc: Cond -10/06
D07 -347 Printed: 10 -19 -2007
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
a width not less than 2 inches (51 mm) wide except the letter "I ", and the minimum spacing between letters shall not be
less than 0.375 inch (9.5 mm). Signs larger than the minimum established in section 1011.5.1 of the International Fire
Code shall have letter widths, strokes and spacing in proportion to their height. The word "EXIT" shall be in high
contrast with the background and shall be clearly discernible when the exit sign illumination means is or is not
energized. If an arrow is provided as part of the exit sign, the construction shall be such that the arrow direction
cannot be readily changed. (IFC 1011.5.1)
29: Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90
minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system
provided from storage batteries, unit equipment or on -site generator. (IFC 1006.1, 1006.2, 1006.3)
30: Means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means
of egress is occupied. The means of egress illumination level shall not be less than 1 foot -candle (11 lux) at the
floor level. The power supply for the means of egress illumination shall normally be provided by the premise's
electrical supply. In event of a power failure an emergency power system shall provide power for a duration of not less
than 90 minutes and shall consist of storage batteries, unit equipment or on -site generator. (IFC 1006.1, 1006.2,
1006.3)
31: Maintain sprinkler coverage per N.F.P.A. 13. Addition/relocation of walls, closets or partitions may require relocating
and/or adding sprinkler heads. (IFC 901.4)
32: Sprinklers shall be installed under fixed obstructions over 4 feet (1.2 m) wide such as ducts, decks, open grate
flooring, cutting tables, shelves and overhead doors. (NFPA 13- 8.6.5.3.3)
33: All electrical work and equipment shall conform strictly to the standards of the National Electrical Code. (NFPA 70)
34: The maximum flame spread class of finish materials used on interior walls and ceilings shall not exceed that set forth
in Table No. 803.5 of the International Building Code.
35: In order to provide you with the fastest police and fire protection under emergency conditions, please post your suite,
room or apartment number in a conspicuous place near the main entry door. (IFC 505.1)
36: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
37: This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed
description of intended use.
38: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
39: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond -10/06
* *continued on next page **
D07 -347 Printed: 10 -19 -2007
Signature:
J ,
Print Name: cS4 a-vl. K a vi W_D L
doc: Cond -10/06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Date: l o - ! �U 7
D07 -347 Printed: 10 -19 -2007
//��IJo //'� /� �t King Co Assessor's Tax No.: 73t --C O77
Site Address: 16 V C , hr �y `i2.• I61 Suite Number: Floor:
Tenant Name: ko r k1i t .i JPJ'\ P, +a I I YQ.p1-
New Tenant: .... Yes ❑ ..No
Property Owners Name: 5r.cp. r.e. -t'\I 11° E a ?4 J 1 L / `7 o Urn co Pro p&ri- .es -4-1c, .
Mailing Address: 16 Yai ` vi X11,2 -n RD. 5,. IC5 TUk..J [16( wn `7
City State Zip
CONTACT PERSON who;do we contact when your permit is ready to b
Name: 'r I � � 1 2 T PI Day Telephone: 1 -125- 1 -125- 67 l616
Mailing Address: 22( apt�" (i..+ » NaK _,Te oce. (AJ �1�XJ`7 3
City State
Zip
E -Mail Address: 01f n1 � � � , Colt 4.1` n 51 G • c Fax Number: 5 — 77 02.14
GENERAL, CONTRACTOR .INFORMATI
(Contractor Information for Mechanical, (pg 4) for Plumbing and Gas Piping (pg 5)) ; ';:,
Company Name: ' C
Mailing Address:
Contact Person:
E -Mail Address:
Contractor Registration Number:
ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Recor
Company Name: OM VIP It PP ( � ;'ou •
Mailing Address: Z2l G -1` � �/ �-- W ) •2C. » bon - aka 1 , (AP q
City State Zip
Day Telephone: /425— G76 —670
rid f►ti
E -Mail Address: Apr 1 �� c w vi Ut d 0% n •Cowl Fax Number: 425 " 77 S2 (4i
NGINEEROF; RECORD . -Alt plans must be et stamped by Engineer of Recor
Company Name: A) 14
Mailing Address:
State
Contact Person:
Contact Person:
E -Mail Address:
CITY OF TUKWILA'
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.wa.us
Q:1Applications\Forns- Applications On Linel3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
State
Zip
City
Day Telephone:
Fax Number:
Expiration Date:
Zip
City
Day Telephone:
Fax Number:
Page 1 of 6
Valuation of Project (contractor's bid price): $ O l (Ow Existing Building Valuation: $
Scope of Work (please provide detailed information): jJe(,O VQ,r1car
rrAr5
Will there be new rack storage? 0.... Yes
e All °B.uildii 2
seas in S
uarelFootage Belo
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes... No If "yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Sprinklers
Q: Applications\Forms- Applications On Line 3 -2006 - Permit Application.doe
Revised: 9 -2006
bh
Automatic Fire Alarm ❑ None
i I 4 L t .. i. L •A_
'No If yes, a separate permit and plan submittal will be required.
Other (specify)
Will the bd storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes No
If `yes', attach list of materials and storage locations on a separate 8 -1/2 "x 11 " paper including quantities and Material Sa ety ata Sheets.
SEPTIC SYSTEM
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Page 2 of 6
[ TERMIT APPLICATION NOT — Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING O R OR
Signature:
nn
Print Name: t3
AGENT:
Mailing Address: 221az 6 At..e.
Date Application Accepted:
Q:\Applications\Fonns- Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
ouvM
City
Day Tel (-L ephone: "00 Q 1 X
le
State Zip
Date: q /, i /
l
Date Application Expires: 01 tf 1(0.9_
Page 6 of 6
PLUMBING AND GAS P ' .'- G CONTRACTOR INFORMATION
Company Name:
Mailing Address:
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date.
Valuation of Plumbing work ontractor's bid price): $
Valuation of Gas Piping work ( ' t tractor's bid price): $
Scope of Work (please provide de . ' ed information):
Building Use (per Intl Building Code):
Occupancy (per Intl Building Code):
Utility Purveyor: Water:
Indicate type of plumbing fixtures and/or gas piping ou
Fixtur Ty pe:
Bathtub or combination
bath/shower
Bidet
Clothes washer, domestic
Dental unit, cuspidor
Dishwasher, domestic,
with independent drain
Building sewer or trailer
park sewer
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
. ture Type:
Drinking fountain ' water
cooler (per head)
Food -waste _ ' i er,
commercial
Floor drain
Shower, gle head trap
Lavato
Rai ater system — per
d . (inside building)
pair or alteration of water
iping and/or water treating
equipment
Q:\Applications\Forms- Applications On Line\3 -2006 -Permit Application.doc
Revised: 9 -2006
bh
is eing installed and the quantity below:
FixtgotiTyp
Wash fountain
Receptor, indirect
ante
ks
Ur Is
Wate. Closet
Water h
vent
Sewer:
er and/or
Repair or alt tion
of drainage or - nt
piping
tre''Ty
Gas piping outlets
Additional medical gas
inlets/outlets — six or more
Medical gas piping system
serving one to five
inlets/outlets for specific gas
Page 5 of 6
Doc: RECSETS-06
RECEIPT NO: R07 -02292
Initials: JEM
User ID: 1165
Payee: UNICO PROPERTIES LLC
SET TRANSACTIONS:
Set Member Amount
D07 -329 281.16
D07 -346 177.00
D07 -347 211.72
TOTAL: 669.88
ACCOUNT ITEM LIST:
Description
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http. / /www.ci.tukwila.wa.us
BUILDING - NONRES
STATE BUILDING SURCHARGE
SET RECEIPT
SET ID: 1019 SET NAME: CONNELL DESIGN
TRANSACTION LIST:
Type Method Description Amount
Payment Check 6266 669.88
TOTAL: 669.88
Account Code Current Pmts
000/322.100 656.38
000/386.904 13.50
TOTAL: 669.88
Payment Date: 10/19/2007
Total Payment: 669.88
4.22 10/19 9710 )Ai'
Receipt No.: R07 -01937
Initials: JEM
User ID: 1165
Payee: CONNELL DESIGN GROUP, INC.
TRANSACTION LIST:
Type Method Description
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 2523049077 Permit Number: D07 -347
Address: 16000 CHRISTENSEN RD TUKW Status: PENDING
Suite No: Applied Date: 09/11/2007
Applicant: NORTHWEST RESTAURANT Issue Date:
Amount
Payment Check 15100 134.69
Account Code Current Pmts
000/345.830 134.69
Total: $134.69
Payment Amount: $134.69
Payment Date: 09/11/2007 01:44 PM
Balance: $211.72
2643 09/11 9710 TOTAL 134
doc: Receiot -06 Printed: 09 -11 -2007
COMMENTS:
Type of Inn,
31di4-
-.
A dress:
1 (0000 C.list54
Date Called:
ithir t
o. t
Date Wanted:
`Z.i
01
a.r
P.m.
Requester:
ai
s
-6 _ book-- D.uLGS
r
S
(ii—A.6 - 1 tar. 4oatk.
Project:
.•w t'-
Type of Inn,
31di4-
-.
A dress:
1 (0000 C.list54
Date Called:
Special Instructions: V-.6*
•
Date Wanted:
`Z.i
01
a.r
P.m.
Requester:
Phone No:
4
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. 0 Corrections required prior to approval.
'Inspector: p
El $58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
'Receipt No.:
'Date:
Date:
1 243ko-r
Project:
NS, • w Q��°v2R+s.T
Type of Inspection:
5%..) s�. cwt Lt
Ad ress:
I 4, oao c- f"EQ-i gr" ,..1 SG/J
Date Called:
Special Instructions: 1 2 1 5
Date Wanted:
/ D1
i
%p
"gym.
Requester:
l
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
COMMENTS:
Approved per applicable codes. El Corrections required prior to approval.
(Inspector:
DD1 -3l
Date:
_. Z s o
$58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
'Receipt No.:
'Date:
Project: ,
fvo ` // .' & 1
Type of Inspection:
F / /Ir7! /,C, 4
\ '
Address: /
/ (.. 0 6 b I `i ri % Sky
K to alied:
c
Special Instructions:
Date Wanted:
// / /
4( /(- ''')
(a.m
P.m.
Requester:
Phone No'
-?U� -,
/7-
7
3
(/
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)43 -3
'!I
COMMENTS:
Approved per applicable codes. Corrections required prior to approval.
Ej $58.00 REINSPECTI0 FEE RE Prior to inspection, fee rust be
paid at 6300 Southcenter Blvd., Suite 100. Call the schedule reinspection.
(Receipt No.:
!Date:
Project: i v
/VGv7i t / fl ) ? f (,i •--,,,
Type of I pection: I
J pi 1.1.--. 1 vk c
Address:
/ 000 a r;) tamp, Sep, Pi.,
Date Called:
Special Instructions:
Date Wanted:
a.m.
Requester:
Phone /
F2 ' - 'S/ 7Y
INSPECTION RECORD
Retain a copy with permit
0'17 -7
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION 02- 6300 Southcenter Blvd., #100, Tukwila, WA 98188 . (206)431-3670
PERMIT NO.
El Approved per applicable codes. corrections required prior to approval.
COMMENTS:
�./ .v tier 7/ `/ C <1
Inspector:
'Date: // �-•7
$58.00 REINS ION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call the schedule reinspection.
'Receipt No.:
'Date:
COMMENTS:
Type of Inspection:
Address: /6 >o Ghr,. s -
Suite #: /00
Contact Person:
hit ; ,e C.. (.,)he i-eet-
P - : 1G 1' i no- i
Can- 7�l�.,J --ma-t -,
Permits:
Occupancy Type:
rl
; iR
1.
ill 1 a E = 4, ,
Project: At ta. 4cs f-viQi-14 5
Type of Inspection:
Address: /6 >o Ghr,. s -
Suite #: /00
Contact Person:
hit ; ,e C.. (.,)he i-eet-
Special Instructions:
Phone No.:
2d — 7d'4 -- e 3 s ,
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
. NSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
Dal -3
PERMIT NUMBERS
444 Andover Park East, Tukwila, Wa. 98188 206- 575 -4407
Date: 1 2 j 3A 7
Hrs.:
1
Inspector: . 54)/525 --
At $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
%proved per applicable codes.
Word /Inspection Record Form.Doc 1/13/06
ri Corrections required prior to approval.
T.F.D. Form F.P. 113
Project: N. 4.
Sprinklers:
,
Type of Inspection:
&n a_ L AL T / ) Ptmazt&x? .
Address: /!,000
Suite #: iov
Cfrierz=
-- - m-t, - rt./
Contact Person:
M,,zE 1/Vii - — &7 --
Special Instructions:
Phone No.:
2o&- -?g6 - 6385
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
444 Andover Park East, Tukwila, Wa. 98188 206- 575 -4407
-- Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
7 oq -S47-
PERMIT NUMBERS
n Corrections required prior to approval.
COMMENTS:
Gisl�72. L .T P4556D - kt/L' / rr /aP 716e -et 61/-0c11''
Inspector: G-uy6 /2
Date: 11/24107
Hrs.: /
n $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Word /Inspection Record Form.Doc 1/13/06
T.F.D. Form F.P. 113
04 -04 -2008
APRIL FILIPPI
2202 64 AV W
MOUNTLAKE TERRACE WA 98043
RE: Permit No. D07 -347
16000 CHRISTENSEN RD TUKW
Dear Permit Holder:
In reviewing our current records the above noted permit has not received a final inspection by the City of Tukwila Building Division.
Per the International Codes, Uniform Plumbing/Fuel Gas Code and/or the National Electrical Code, every permit issued by the
Building Division under the provisions of the code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit issuance, or if the building or work
authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days.
Based on the above, you are hereby advised to:
Call the City of Tukwila Inspection Request Line at 206 -431 -2451 to schedule for the next or final inspection.
This inspection is intended to determine if substantial work has been accomplished since issuance of the permit or last inspection; or if
the project should be considered abandoned.
If such determination is made, the International Codes, Uniform Plumbing/Fuel Gas Code and/or the National Electrical Code does
allow the Building Official to approve one extension of time for an additional period not exceeding 180 days. Extension requests
must be in writine and provide satisfactory reasons why circumstances beyond the applicants control have prevented action from
being taken.
In the event you do not call for the above inspection and receive an extension prior to 05/31/2008 , your permit will become null and
void and any further work on the project will require a new permit application and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
r Marshall
Pe Technician
xc:
Permit File No. D07 -347
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
ACTIVITY NUMBER: D07 -347 DATE: 09 -11 -07
PROJECT NAME: NORTHWEST RESTAURANT
SITE ADDRESS: 16000 CHRISTENSEN RD, STE 101
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
Bui ing livision
Pt.6311
11-
Complete
Comments:
Documents/routing slip.doc
2 -28-02
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
Fire Prevention
Structural
DETERMINAT ON OF COMPLETENESS: (Tues., Thurs.)
Incomplete
TUES/THURS ROU ING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
DUE DATE: 09-13-07
Not Applicable ❑
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
No further Review Required
DATE:
DUE DATE: 10-11-07
Not Approved (attach comments) n
DATE:
ID4
Planning ivision
Permit Coordinator E
n
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
License Information
License
GATEWCS992C3
Licensee Name
GATEWAY CONSTRUCTION SRVCS INC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602086011
Ind. Ins. Account Id
754100
Business Type
CORPORATION
Address 1
701 DEXTER AVE N SUITE 420
Address 2
City
SEATTLE
County
KING
State
WA
Zip
98109
Phone
2066219111
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
2/26 /2001
Expiration Date
3/4/2008
Suspend Date
Separation Date
Parent Company
Previous License
NIELSC *02708
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
SACCO, RONALD
PRESIDENT
02/26/2001
Bond
Amount
NIELSEN, CRISTIAN
VICE PRESIDENT
02/26/2001
SRS1008614
Bond Information
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
#2
RLI
INSURANCE
CO
SRS1008614
02/26/2002
Until
Cancelled
$12,000.00
03/04/2002
Look Up a Contractor, Electrir an or Plumber License Detail Page 1 of 2
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L&I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= GATEWCS992C3 10/19/2007
GENERAL NOTES
ALL CONSTRUCTION SHALL COMPLY WITH THE CURRENT REGULATORY CODES FOR THE STATE
OF WASHINGTON AND THE LOCAL JURISDICTIONS. SEE PROJECT DATA SECTION FOR CURRENT
APPLICABLE GORES.
CONTRACTOR IS TO VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC., AND
NOTIFY THE DESIGNER OF ANY AND ALL DISCREPANCIES PRIOR TO PROCEEDING WITH THE
WORK.
CONTRACTOR SHALL VERIFY ALL "BUILDING STANDARDS" WITH BUILDING LANDLORD PRIOR
TO BEGINNING ANY WORK. HOWEVER, THERE SHALL BE NO DEVIATIONS WHATSOEVER FROM
THE CONTRACT DOCUMENTS WITHOUT THE DESIGNER'S WRITTEN APPROVAL THEREOF. THE
CONTRACTOR AGREES TO DEFEND, INDEMNIFY AND HOLD THE DESIGNER HARMLESS FROM
ANY CLAIMS ARISING AS A RESULT OF UNAPPROVED CHANGES.
ALL DEBRIS SHALL BE REMOVED FROM THE PREMISES AND ALL AREAS SHALL BE LEFT IN
A CLEAN (BROOM) CONDITION AT ALL TIMES.
APPROVED PLANS SHALL BE KEPT IN A PLAN BOX AND SHALL NOT BE USED BY ANY
WORKMEN. ALL CONSTRUCTION SETS SHALL REFLECT THE SAME INFORMATION AS WELL AS
ALL REVISIONS, ADDENDA AND CHANGE ORDERS. THE CONTRACTOR SHALL ALSO
MAINTAIN IN GOOD CONDITION, ONE COMPLETE SET OF PLANS WITH ALL REVISIONS,
ADDENDA AND CHANGE ORDERS ON THE PREMISES AT ALL TIMES WHICH ARE TO BE UNDER
THE CARE OF THE JOB SUPERINTENDENT.
ALL OPERATIONS CONDUCTED ON THE PREMISES SHALL NOT BE OBJECTIONABLE BEYOND
THE PROPERTY BOUNDARY LINES BY REASON OF NOISE, STEAM, ODOR, FUMES, GASES,
SMOKE, VIBRATION, HAZARD OF OTHER CAUSES. IN ADDITION, THE CONTRACTOR SHALL
MINIMIZE DISRUPTIONS OF ADJACENT TENANTS DUE TO NOISE, ODOR, CORRIDOR FUMES OR
VIBRATION. ALL COMMON LOBBY AND CORRIDOR SPACE SHALL BE KEPT CLEAR OF DUST,
DEBRIS AND CONSTRUCTION MATERIALS AT ALL TIMES.
ALL WORK SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S LATEST
RECOMMENDATIONS OR WRITTEN DIRECTIONS.
ALL DIMENSIONS ARE TO FACE OF GYPSUM WALL BOARD UNLESS OTHERWISE NOTED.
WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK,
THE DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR WORK IN THE SAME BUILDING.
10. WHERE DEVICES OR ITEMS OR PARTS THEREOF ARE REFERRED TO IN SINGULAR, IT IS
INTENDED THAT SUCH SHALL APPLY TO AS MANY SUCH DEVICES, ITEMS OR PARTS AS ARE
REQUIRED TO PROPERLY COMPLETE THE WORK.
II. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES
WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR
SHALL BEAR ALL EXPENSE OF REPAIR OR REPLACEMENT OF UTILITIES OR OTHER
PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE EXECUTION OF HIS
WORK.
12. THE CONTRACTOR WILL VERIFY AND CONFORM TO ALL REQUIREMENTS OF ALL UTILITY
COMPANIES UNLESS OTHERWISE NOTED IN THE PLANS AND SPECIFICATIONS.
10. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF
THE OCCUPANTS AND WORKERS AT ALL TIMES.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE SECURITY OF THE BUILDING
AND SITE WHILE JOB IS IN PROGRESS AND UNTIL THE JOB IS COMPLETED.
15. ALL WORK SHALL BE GUARANTEED FOR A PERIOD OF ONE (I) YEAR AFTER COMPLETION,
UNLESS OTHERWISE SPECIFIED AND SHALL BE SO STATED IN CONTRACTOR'S WRITTEN
PROPOSAL AND AGREEMENT. ALL REPAIRS, CORRECTIONS AND DISCREPANCIES ETC.,
MUST BE MADE WITHOUT ANY ADDITIONAL COST TO THE OWNER, AND WITHIN FIVE (5) DAYS
AFTER NOTICE IS GIVEN.
16. LATHING, PLASTER AND GYPSUM WALL BOARD SYSTEMS SHALL CONFORM TO THE CHAPTER
25 OF THE 2006 I.B.G.
11. ALL EXPOSED GYPSUM BOARD TO HAVE METAL EDGES AT ALL CORNERS AND WALL
INTERSECTIONS.
IS. ALL GLASS AND GLAZING SHALL COMPLY WI "-1 THE 2006 I.B.G.. AND THE
U.S. PRODUCT SAFETY COMMISSIONS: SAFETY STANDARD FOR ARCHITECTURAL GLAZING
MATERIALS.
ICs. ALL REQUIRED FIRE DOORS SHALL BEAR A LABEL FROM A RECOGNIZED AGENCY SHOWING
THE SPECIFIC RATING.
20. EXIT SIGNS AND ILLUMINATION SHALL CONFORM TO THE 2006 I.B.G. CHAPTER 10 AND LOCAL
FIRE MARSHAL REQUIREMENTS.
21. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY
SPECIAL KNOWLEDGE OR EFFORT.
22. FIRE EXTINGUISHERS: VERIFY REQUIREMENTS AND LOCATIONS WITH THE FIRE MARSHAL.
CONTRACTOR TO SUPPLY FIRE EXTINGUISHERS AND CABINETS AS REQUIRED.
23. ELECTRICAL ROUGH -IN AND REFLECTED CEILING PLAN ARE FOR THE GENERAL INFORMATION
OF THE CONTRACTOR. EXACT LOCATIONS SHOULD BE VERIFIED.
24. FLAMMABLE LIQUIDS SHALL NOT BE PLACED, STORED OR DISPENSED IN THIS OCCUPANCY
EXCEPT AS PROVIDED IN N.F.P.A. STANDARD 30 AND THE CURRENT UNIFORM FIRE CODE.
PERMIT MAY BE REQUIRED.
25. ALL DRAPES, HANGINGS, CURTAINS, DROPS AND ALL OTHER DECORATIVE MATERIAL,
INCLUDING CHRISTMAS TREES THAT WOULD crEND TO INCREASE THE FIRE AND PANIC HAZARD
SHALL BE MADE FROM NONFLAMMABLE MATERIAL, OR SHALL BE TREATED AND MAINTAINED
IN A FIRE RETARDANT SOLUTION OR PROCESS APPROVED BY THE COUNTY FIRE MARSHAL.
PROVIDE A CERTIFICATION TO THIS EFFECT.
A. EXIT DOORS, EXIT LIGHTS AND FIRE EXTINGUISHER LOCATIONS SHALL NOT BE
CONCEALED OR OBSTRUCTED BY ANY DECORATIVE MATERIAL.
B. MINIMUM FLAME SPREAD CLASSIFICATION OF INTERIOR FINISHES SHALL BE PER
THE 2003 I.B.G.
26. ALL LAY -IN ACOUSTICAL CEILING GRIDS SHALL BE INSTALLED AND SECURED PER THE
2006 I.B.G. STANDARDS FOR EARTHQUAKE ZONE D, ASME C655, 0636.
21. PROVIDE OR MODIFY AS NEEDED SPRINKLER, ALARM AND SMOKE DETECTION SYSTEM PER
APPLICABLE CODES, INCLUDING IF NECESSARY FIRE HORNS, STROBE LIGHTS, CONTROL
PANEL CONNECTIONS, SMOKE DETECTORS, AUDIO VISUAL ALARMS. SUBMIT SHOP DRAWINGS
TO THE FIRE MARSHAL FOR APPROVAL.
25. TENANT TO PROVIDE AND INSTALL THE TELEPHONE AND DATA COMMUNICATION CABLING.
CONTRACTOR TO COORDINATE SCHEDULING AND OTHER REQUIREMENTS WITH TENANT.
21. MECHANICAL SYSTEM: CONTRACTOR SHALL VERIFY AND PROVIDE A COMPLETE HVAC
SYSTEM WHICH CONFORMS TO THE OWNER'S HVAG SPECIFICATIONS. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL ROOF PENETRATIONS AND PATCHING, ANY SCREENING OF
ROOF - MOUNTED MECHANICAL UNIT REQUIRED BY GOVERNING JURISDICTION.
SO. PROVIDE OR MODIFY AS NEEDED EMERGENCY LIGHTING.
51. ALL ITEMS MARKED *N.I.C.* ARE NOT PART OF THIS CONTRACT.
52. ABBREVIATIONS THROUGHOUT THE PLANS ARE ABBREVIATIONS WHICH ARE IN COMMON USE.
THE LIST OF ABBREVIATIONS PROVIDED IS NOT INTENDED TO BE COMPLETE OR
REPRESENTATIVE OF CONDITIONS OR MATERIALS ACTUALLY USED ON THE PROJECT. THE
DESIGNER WILL DEFINE THE INTENT OF ANY IN QUESTION.
33. DO NOT SCALE DRAWINGS. IF A DIMENSION DISCREPENCY IS NOTED, CONTACT DESIGNER.
34. IF BUILDING STANDARDS HAVE NOT BEEN ESTABLISHED OR HAVE BEEN ESTABLISHED OR
HAVE BEEN CHANGED FOR DOORS, RELITES, HARDWARE , DOOR AND RELITE FRAMES OR
OTHER STANDARD DETAILS, THEN CONTRACTOR MUST VERIFY WITH DESIGNER AND OWNER
PRIOR TO CONSTRUCTION.
ABBREVIATIONS
ACCOUS.
ACT.
ADJ.
A.F.F.
APPROX.
ARCH.
BLK.
BD.
BLDG./BLD.
B/S
CAB.
GLG. /CLOG.
CL OR C
CLKG.
COL.
CONT.
CONC.
CONST.
CONTR.
CPT.
G.W.
D.
DEPT.
PET.
PIAG.
DIA.
PIM.
DBL.
DWG.
D.F.
D I FF.
D.N.
E.
EA.
ELEV.
ELEC.
EMER.
EXT.
EQ.
EQPT.
EXIST.
P.I.O
F.A.
F.E.
F.E.G.
FIN.
FIXT.
F.D.
FLR.
F.O.I.C.
FT.
GA.
GALV.
GL.
GJN.B.
GYP.
H.
HGP.
HD.WD.
HD.
HM.
HORZ.
HT.
HR.
H.W.
.B.G.
NOD.
NCL.
NFO.
NTSUL.
NTR.
JAN.
J.B.
JT.
JANITOR
JUNCTION BOX
JOINT
VICINITY MAP
ACOUSTIC /ACOUSTICAL
ACOUSTICAL TILE
ADJUST /ADJUSTABLE
ABOVE FINISHED FLOOR
APPROXIMATELY
ARCHITECTURAL
BLOCK/BLOCKING
BOARD
BUILDING
BUILDING STANDARD
CABINET
CEILING
CENTER LINE
CAULKING
COLUMN
CONTI NUOUS
CONCRETE
CONSTRUCTION
CONTRACTOR
CARPET
COLD WATER
DEEP
DEPARTMENT
DETAIL
DIAGONAL
DIAMETER
DIMENSION
DOUBLE
DRAWING
DRINKING FOUNTAIN
D I FUSSER
DOWN
EAST
EACH
ELEVATION (BLDG)/
ELEVATOR
ELECTRICAL
EMERGENCY
EXTERIOR
EQUAL
EQUIPMENT
EXISTING
FURNISHED 4
INSTALLED BY OTHER
FIRE ALARM
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH
FIXTURE
FLOOR DRAIN
FLOOR
FURNISHED BY OTHER
INSTALLED BY
CONTRACTOR
FOOT OR FEET
GAUGE
GALVANIZED
GLASS /GLAZING /GLAZED
GYPSUM WALL BOARD
GYPSUM
HIGH
HANDY CAP
HARD WOOD
HEAVY DUTY
HOLLOW METAL
HORIZONTAL
HEIGHT
HOUR
HEATING VENTALATING
AIR CONDITIONING
HOT WATER
INTERNATIONAL BUILDING
CODE
INCANDESCENT
INCLUDE
INFORMATION
INSULATE (D)(ING)
INTERIOR
LAM.
LAV.
L.
LTG.
LT.
LG./L...
MAT.
MAX.
MFG.
MECH.
MED.
MIN.
MIN.
MISC.
MTD.
MTL.
MW.
N.
N.I.C.
N.T.S.
NO.
OFF.
O.G.
OFF.
O.F.C.I .
O.F.O.I.
PNL.
PT.
PART.
P.P.L.
PL.
F. LAM.
PLY.
Q.T.
QTY.
R.B.
R.
RAD.
REF.
REQD.
REV.
R.O.
RM.
S.
SECT.
SHT.
SIM.
SPEC.
S.
SST.
STD.
STOR.
STRUC.
SUSP.
SW.
TEL.
TEMP.
TYP.
U.L.
U.P.G.
VOL.
VAR.
V.G.T.
VERT.
V.P.
W.B.
P.
WT.
W/
W.H.
WT.
LAMINATED /LAMINATE
LAVATORY
LENGTH
LIGHTING
LIGHT
LONG
MATERIAL
MAXIMUM
MANUFACTURER
MECHANICAL
MEDIUM
MINIMUM
MINIMUM
MISCELLANEOUS
MOUNTED
METAL
MICROWAVE
NORTH
NOT IN CONTRACT
NOT TO SCALE
NUMBER
OFFICE
ON CENTER
OWNER FURNISHED
CONTRACTOR INSTALLED
OWNER FURNISHED
OWNER INSTALLED
PANEL (I N )
PAINT (ED)
PARTITION
POLISHED PLATE GLASS
PLATE
PLASTIC LAMINATE
PLYWOOD
QUARRY TILE
QUANTITY
RUBBER BASE
RISER RANGE
RADIUS
REFERENCE
REQUIRED
REVISED /REVISION
ROUGH OPENING
ROOM
STAIR
SECTION
SHEET
SIMILAR
SPECIFICATIONS/
SPECIFIED
SOUTH
STEEL
STAINLESS STEEL
STANDARD
STORAGE
STRUCTURAL
SUSPEND /SUSPENDED
SWITCH
TELEPHONE
TEMPERED
TYPICAL
UNDERWRITER'S
LABORATORY
UNIVERSAL PLUMBING
CODE
VOLUME
VARIABLE/VARIES
VINYL COMPOSITION TILE
VERTICAL/VERTICALLY
VENEER PLASTIC
WOOD BASE
WALL COVERING
WOOD
WEIGHT
WIDE
WITH
WATER HEATER
WEIGHT
160oI Chriitensen1Rd,
a14
Seattle _1 18 _c
PROJECT DATA
PROJECT ADDRESS:
GOVERNING CODE:
USE ZONE:
OCCUPANCY:
CONSTRUCTION TYPE:
ENERGY CODE:
ACCESS CODE:
PLUMBING COPE:
CONTRACTOR:
MECHANICAL:
ELECTRICAL:
SPRINKLER:
SUITE 101
TUG
B
3,367 SF
LEGAL DESCRIPTION
SiTE PLAN
16000 CHRISTENSEN RD
BUILDING 02 - SUITE 101
TUKWILA, WA 98188
2006 I.B.G.
(STATE OF WASHINGTON
AMENDMENTS)
CONTRACT THIS BUILDING
CHRISTENSEN ROAD
V -N -FULLY SPRINKLERED
2006 WASHINGTON STATE
ENERGY CODE
ICC /ANSI AI17.1 -2003
2006 U.P.G.
TO BE DETERMINED PRIOR
TO PERMIT ISSUANCE
BIDDER DESIGN
(UNDER SEPARATE PERMIT)
BIDDER DESIGN
(UNDER SEPARATE PERMIT)
BIDDER DESIGN
(UNDER SEPARATE PERMIT)
KING COUNTY PARCEL NUMBER: BALDING I -16040 CHRISTB4SEN AVE. - 252304 403ci AND 252304 -4018
KING COUht1Y PARCEL NUMBER: BUILDING 2 -16000 CHRISTENSEN AVE. - 252304 -
KING COUNTY PARCEL, tlJM1EER: BUILDING 3 - 16300 CHRISTENSEN AVE. - 252304 -4078
LE1A1- 2rgr TiON
PARGi*L. it
That portion of the K.H. Gilliam Donation Land Claim *40 and of the southwest quarter of the southwest cjucr ter . of section 24, Torrehlp 23 North, Range 4 East, W.M., and of Government Lot I In Section 25, Township 23
North, Range 4 East, W.M., In King County, Washington, more particularly described as follows: Commencing at the northwest corner of Parcel 2 of City of TLkwfla Short It *73 -16-55 as retarded under King Gounty
Recording No. 74O605 8; thence south 64° Oe' 52' East, 24.88 feet to a point of curvature; thence easterly 168.00 feet along the arc oP a tangent curve to the left, having a radhn oP 135.00 feet, through a central
angle of 10° 11' 42" to the true point of beginning thence continuing easterly 146.87 feet along the arc of a non- tangent cove to the left, having a radius of g95.O0 feet, the radius point of which bears north 15° 52' 26°
east, through a central angle of Oq° 00' 01' to a point on said curve; thence north 06° 34' 56' east, 66.23 Peet to a point oP curvature thence northeasterly 6.86 feet along the arc oP a non - tangent curve to the right,
having a radius of 62.00 feet, the radars point of retch bears south 22° 09' 30" East, through a central an oP 06° 20' 30° to a point of reverse curvature; thence northeasterly 25.15 feet along the art of a tangent
curve to the left, having a radius of 20.00 feet, through a central angle of 72° 03' 23° to a point of tangency; thence north 02° 13' 31" east, 0.qq feet; thence south lee 46' 23° east, 6.61 feet thence north O2° 13 31°
east, 106.17 feet; thence north 11° 04' 07" east, 51.22 Peet; thence north 48° 35' OO" east, 6021 feet; thence south 841° 47' 00' east, 110.00 feet thence north 48° I9' 41" east, 55.00 feet; thence south 4I° 40' Iq" east,
45.14 feet; thence south 29° 47' 54" east, 4 feet thence south 03° 44' 56' west, 40.46 feet; thence south 24° 03' 53' rest, 4081 feet; thence south Dq° Iq' 22' west, 62.85 feet; thence south 32° 31' 34" reset, 59.80
Peet; thence south 35° 13' 26" rest, 59.19 feet; thence south 341° 40' 01' west, 63.82 feet; thence south 40° 00' 241" west, 66.84 feet thence south 241° 01' 34' west, 35.16 feet; thence south 31° 16' 45" west, 11.29 feet;
thence north 77° 25' 04' west, 105.54 Peet; thence north 12° 34' S6" east, 28.00 feet; thence north 11° 25' 04' west, 3059 feet to a point of curvature; thence southwesterly 52.g6 feet along the arc of a non - tangent
curve to the right, having a radius of 320.0 feet, the radius poinnt of which bears north 641° 42' 541" west, through a central angle of O9° 28' 59" to a point of tangency; then.) south 2'° 46' 00' west, 44.96 Peet; thence
north 60° 14' OO" west, I7.Iq feet; thence south 841° 46' 00" west, 24b1 Peet; thence earth 00° 14' 00" east, 830 feet; thence south 8'° 46' 00" west, 2q50 Peet; thence north 00' 14' 00' west, 14450 feet; thence south
89° 46' 00" west, 29.50 feet; thence north 00° 14' 00' west, 34.00 feet; thence north I6° 05' 55" east, 20.97 feet to a oint of curvature; thence southeasterly q.43 feet along the arc of a non - tangent curve to the
left, having a radius of 96850 feet, the radius point of which bears north 16° 05' 55" east through a central angle of OO p 33' 241" to a point on said curve; thence north 15' 32' 26' east 3350 feet to the true point of
beginning; EXCEPT that portion thereof lying within the 30 foot City of Seattle Pipeline right -of -way as recorded under King County Recording No. 4106155. (ALSO KNOWN AS revised Lot I, City of TUkrlia boundary Tine
adjustment No. 8i- .4Q - -3LA, recorded under King County Recording No. 8112160540; said bouncery line being a revision of City of Tvfcwlla boundary line adjustment No. 81- 1 -8LA, recorded under Ding County Recording No.
31020503aq, which revised City of Tukwila 5,or-t Plat No. 18 -16-55 recorded under King County Recording No. 7 also recorded under Ktng County Recording Nos. 1gO6O500q7 orid 190605OOgq); TOGETHER
WITH a 24 foot ingress, egress, and utilities easement over a portion of Revised Lots 3 oP said City of Tukwila boundary line adjustment No. 81- 40 -3LA, lying 12 feet on each side of the following described centerline,
Commencing at the northwest corner of Parcel 3 of said City of Tukwila Short Plat No. 13- I6 -S5 thence south OO° 14' 00" east, 91.90 feet to the point of bees ning of this centerline description; thence north 841° 46' OO"
east 18450 feet to point "D'; thence continuing north 09° 46' 00" east, 22.00 feet thence north 29° 46' 00° east, 14336 feet to a point of curvature thence northerly 6555 feet alent the are of a tangent curve to the
left, having a radius of 920.00 feet, through a central angle of 11° 44' 10° to the on of this centerline description ALSO TOGETHER WITH a 25 foot ingress, egress, and utilities easement over a portion or Revised Lots
2 and 3, said boundary Ilse adjustment No. 81- 40 -13LA, it 125 feet on each side of the following described centerline; Beglrnrng at Point 'D "; thence north OO° 14' OO" west, 226.00 Peet to the end of this centerline
description; ALSO TOGETHER WITH a 24 foot Ingress, egress and utilities easement, over a portion of revised Lot 2, said boundary line adjustment No. 81- 40 -3LA, lying 12 feet on each side of the following described
centerline; Commencing at the southwest corner of Parcel I of said City of Tukwila Short Plat No. 75- 16-55; thence north 0O° 14' DO° west, 21.47 feet to the point of beginning of the centerline description; thence
a
southesterly 43.10 feet along the are of a non - tangent curve to the right, having a radius of 55.00 feet, the radius point oP which bears south 00° 19' 00" west, t a central angle of 44° 54' OS" to a point of
reverse curvature thence southeasterly 31.09 feet along the arc of a tangent curve to the left, having a radius of 100.00 feet, throu a central angle oP 21° 14' 541" to a point of curvature; thence southeasterly 234.41
feet along the ere of a non - tangent curve to the left, having a radius of 809$2 feet, the radius point of which bears north 29° 58' 01 east through a central angle of 15° 05' 50" to a point of curvature; thence
northeasterly 43.19 feet along the arc of a non - tan curve to the left, having a radius or 80.00 feet, the radius point of which be north 08 52' 06" east though a central angle of 30° 56' 06° to the end of this
centerline description.
PARCEL 2_
That portion of the W.M. Gillian Donation Land Claim No. 40 and of the southwest quarter of the southwest quarter of Section 24, Towrr.:iip 23 North, Rare 4 East, W.M., and of Govermhent Lot I In Section 25 Township
23 North, Range 4 East, KM., in King County, Washington, more partIcuierly described as follows: Beginning at the southwest corner• of' f r'areet I of City of Tukwila Short Plat No. 18 -16-55 as recorded under King County
Recording No. 1 thence north DO' 14' OO" west, 188.41 feet; thence south 841° 41' 00° east, 10.00 feet; thence north 00 °•14' 00" west, 6.52 Peet; thence north 10° 34' 00" west, 17.31 feet thence south 63°
07' 11' east, 88.05 Peet; thence south 42° 04' 00' east, 1022 feet; thence south 51° 51' 21' east, 102.40 feet; thence south 84° 35' 20" east, 121.50 feet; thence north 11° 04' 01" east, 25.00 Peet; thence south 02° 13'
37' west, 106.11 feet; thence north 87° 46' 23" west, 6.61 feet; thence south 02° 13' 31" west, 0.44 Peet to a point of curvature; thence southwesterly 25.15 feet along the are of a tangent curve to the right having a
radius of 20.00 feet, trough a central angle of 72° 03' 23" to a point of reverse curvature; thence southwesterly 6.66 feet along thr are of a tangent curve to the left, having a radius of 62.00 feet, trough a central
angle of 06° 20' 30" to a point an sold curve; thence south 06° 34' 56" west, 66.28 feet to a point of curvature; thence northwesterly 146.67 feet along the arc of a non - tangent curve to the right, having a radius of
435.00 feet, the radius point of which beers north 06° 32' 25" east, through a central angle of Oq° 00' Or to a point an said curve; thence south 15° 32' 26" west, 3350 feet to a point of curvature; thence easterly
feat
south 16° 05'55" the we t, 20.97 feet south 00 4' 00 east, 34.00 feet; 9613.50 feet, the
north 841° 46' radius
00" eas 29.50 feet; thence south 00 6 14' 0 0 ° east, 1 feet; th south 81' 46' 00" w , 64.00 f e u et thence
south 00° 14' 00" east, 6.50 feet; thence south 841° 46' 00" west, 115.50 feet to Point "A'; thence north 00° 14' 00" west, 341.00 feet to the point of beginning. EXCEPT that portion thereof lying within the 30 foot City of
Seattle Pipeline Rye-of-rice as recorded under King County Recording No. 4106155; (ALSO KNOWN AS revised Lot 2, City of Tukwila boundary Ilne adjustment No. 61- 40 -5LA, recorded under King County Recording No.
8112160540 said bovnciary line being a revision of City of Tukwila boundary Iine adjustment No. 81- 1 -15LA recorded under King County Recording No. 6102050389, which Revised City of 'Nkrela Short Plat No. 78- 16-55,
recorded under Keg County Recording No. 1406050Og8, oleo under King County Recording Numbers 7 and 7g060500gq); TOGETHER WITH a 24 foot Ingress, egress, and utilities easement over a portion of
revised Lot 3 of City of Tukwila Hamda y Line Adjustment No. 31- 40 -8LA, lying 12 feet an each side of the following described centerline: Commencing at Point °A" as described above; thence south 00° 14' 00" east,
73.00 feet to the point of beginning of this centerline description; thence north 8q° 46' 00 east, 465.0 feet to Point °s'; thence continuing north Sq° 46' 00" east, 69.00 feet to Point'G°; thence continuing north 841° 46'
00" east, 69.00 feet to Pofnt"D " thence continuing north 69° 46' 00' east, 1250 feet to the end of this centerline description ALSO TOGETHER WITH The following 25 foot ingress, *grate and utilities easements over
portion of revised Lots I and 3 of City of Tukwila boundary line adjustment No. 81- 40-BLA lying 125 feet on each side of the following descrbed centerline; Beginning at Point ', thence north 00° 14' 00" west, 73.00
feet to the end of this centerline description; Beginning at Point "C ", thence north 00° 14' 00" west, 88.50 feet to the end of this centerline description; Beeinntng at Polnt"D", thence north 00° 14' 00" west, 226.00 feet
to the end oP this centerline description.
PARCEL 31
That portion of eoverrrnent Lot I in Section 25, Township 23 North, Range 4 East, W.M., in King County, Washington, more particularly described as follows= Beginning at the Southwest corner of Parcel 4 of GIN of Tukwila
Short Plat No. 1S -16- as recorded under King County Recording No. 106000 thence north 00' 14' 00" west, 210.00 Peet to a point of curvature; thence northerly 104.72 fret along the arc of a non- tangent
curve to the left, having a radius of 4000 feet, the radius point of which bears north 00° 14' 00' west through a central angle of 150° 00' 00' to a point of reverse curvature; thence northerly 4155 feet along the arc
of a tangent curve to the right, having a radius of 40.00 feet, through a central angle of 60° 00' 00' to a point of tangency; thence north 00' 14' 00' west 121.31 feet; thence north 841° 46' 00" east 115.40 feet; thence
north 00° 14' 00' west 850 feet; thence north 8 46' 00" east 96.50 Feet; thence north 00° 14' 00" west 850 feet; thence north 841° 46' 00" east 24.61 Feet; thence south 60° 14' 00' east 17.19 feet to Point "E ";
thence north 2q° 46' 00" east 44.36 feet to a point of curvature; thence northerly 52.q6 feet along the a-c of a tangent curve to the left, having a radius of 320.00 feet, through a central angle of 041° 28' Sq' to a
point on said curve; thence south 11° 25' 04' east 30.5' feet; thence south 12° 34' 56' west 28.00 feet; thence south TT' 25' 04" east 10534 feet; thence south 31° 16' 45° west Ii.Oq feet; thence south 34° 31' 52' west
6054 feet; thence south 30° 51' 21" west 61.18 Peet; thence south 13° 16' 05' west 53.94 feet; thence south 15° 57' 27" most 51.32 feet; tinence south 13° 48' 40" rest 5433 feet; thence south 00° 38' 22" east 6234 feet;
thence south 00° 18' 55' west 41.21 feet; thence south 07° 59' 16' east 53.17 feet; thence south 18° 27' 46' east 5637 feet; thence south 27° 57' 17" east 3.24 feet; thence north 31° 41' 00" west 345.34 feet to the
point of beginning. (BEING KNOWN AS revised Lot 3, of City of Tukrrlla boundary Ilene adjustment No. 81- 40-13LA as recorded under King County Recording No. 8112160540, being a revision of boundary line adjustment No.
81- 1 -3L.A as recorded under King County Retarding No. 81020505aq, retch revised City of Tukwila Short Plat No. 78- 16-55, recorded under King county Recording No. 7906050098, also recorded under King county
Recording Nos. 190605009/ and 1906050099); TOGETHER WITH a 24 foot ingress, egress, and utility easement over a portion of revised Lot I of it of Tukwila fovndary Line Adjustment No. 81- 40 -BLA, lying 12 feet
on each side of the following described centerline: Commencing at Polnt'E' as described above: thence north 241° 46' 00' East 4936 feet to a point of curvature thence northerly 65.55 feet along the arc of a tangent
curve to the left, having a radars of 320.00 feet, through a central angle of II° 44' 10' to a point on Said cure; thence south 11° 25' 04" East 30.00 feet to the end of this centerline description.
SEPARATE PERMIT
REQUIRED FOR:
echaniral
Electrical
_I tumbing
G as Piping
City of Tukwila
IM BUil,DING DIVISION
F
1111111
0 IIIIII ►IIIIIIIII�
IIiIIIIIIIIIIillllllll
/IIIIIIIIIIIIIIIIILIIIIIII IJIr
IiIIIIIIIIIIIIIIIIIIiIIIIIII L.
� IIIIIIIIIIIIIIIIIIIIIIIIIIIIIr
u IIIIIIIIIIIIIIIIIIIIIIIIIIIIII L
111111 III111111IIIII
DRAWING INDEX
TI.O COVER SHEET
TI.I. FIRST FLOOR EXITING PLAN
AI.O FIRST FLOOR PARTITION /ELECTRICAL/
PHONE /DATA 4 REFLECTED CEILING PLANS
BUILDING 2 - FIRST FLOOR EXITING
Ilr
review approval is sub :act to errors en i omissi
Approval of cons &cticn c' :_�:" c'_
the
violation cf c:-.7 : • i cV c; c authorize
of approved F :1 :' C: ; (7'. , _ T� Receipt vicdgeck
Permit No.
By
1111II11IIIIIIIfIIIIIIIIIIIIIIIIIIr
J 111111I IIIIIrunIIII IIIIIriIIIIIIL
1111111111111111111IF
IIIIIiIIIIIIIIIIIIIL
1111111111111111
r it ? i ';f irr
AREA OF CONTRACT
ME Eft
• trl
My of Tukwila
ING DIVISION
REVISIONS �
•
to cha nges Shall be rior le
apr
of wcric wnthou�ldin9 Di�I
T u�tiala
n 'T : revisions will require a ne
and ,nay include a��it►nnai SIR
err
the scope
r oval of
; ion.
v plan submitt'
rke
C o
planning interiors architecture
DESIG
22002 - 64th Avenue W., Suite 2C
Mountlake Terrace, WA 98043
T: 425 -670 -6706 F: 425- 774 -8219
REGISTRATION
4676
N
PROJECT NAME
STATE OF WASHINGTON
Northwest Restaurant
RIVERVIEW PLAZA
TENANT IMPROVEMENT
BUILDING 2 - FLOOR 1
16000 CHRISTENSEN ROAD STE 101
TUKWILA, WASHINGTON
DESIGN TEAM
PROJECT NO.:
07.172
PRINCIPAL:
VSS
DRAWN BY:
EC
CHECKED BY:
VSS
sormirminmenm
ISSUED /REVISIONS
9 -11 -07 ISSUED FOR PERMIT
PROJECT CONSULTANTS
SHEET TITLE
COVERSHEET
SHEET NO.
NELL
RECEIVED
CITY OF TUKWILA
SEP 1 1 ' /
rat um! I c F
FIRST LOOR EXITNG PLAN
SGALE:3/S2 I'-0"
boT3in
CO NELL
planning interiors architecture
DESIG
22002 - 64th Avenue W., Suite 2C
Mountlake Terrace, WA 98043
T: 425 - 670 -6706 F: 425 - 774 -8219
REGISTRATION
PROJECT NAME
Northwest Restaurants
RIVERVIEW PLAZA
TENANT IMPROVEMENT
BUILDING 2 - FLOOR 1
16000 CHRISTENSEN ROAD STE 101
TUKWILA, WASHINGTON
DESIGN TEAM
PROJECT NO.:
07.172
PRINCIPAL:
VSS
DRAWN BY:
EC
CHECKED BY:
VSS
PROJECT CONSULTANTS
SHEET TITLE
SHEET NO.
ISSUED /REVISIONS
9 -11 -07 ISSUED FOR PERMIT
RECEIVED
CITY OF TUKWILA
SEP 1 1 Y •J
umi\I i ER
FIRST FLOOR EXITING
PLAN
Till
DOOR SCHEDULE
DOOR #
RATED
WIDTH
HEIGHT
TYPE
FRAME
MAT.
FRAME
FINISH
HARDWARE
REMARKS
116
-
3' -0'
B/5
A
B/5
13/5
HW-1
111
-
3' -0'
135
A
13/5
B/5
HW-1
DOOR TYPES
HARDWARE TYPES - VERIFY WITH OWNER
13/5 SOLID
DOOR
CORE
HN-I - TENANT INTEFJORR, LATCHING
NOTES:
I. ALL DOOR AND DOORWAYS SHALL GPMLY WITH EGG /ANSI A111.I -2003 GOOFS, SECTION 404
2. MAN/F. = BUILDING STANDARD
3. CONTRACTOR TO REUSE AND RELOCATE EXISTING DOORS AND HARDWARE WHERE POSSIBLE.
4. ALL DOOM TO EE EQIUIFFED WITH LEVER -TYPE LATCHING HARDWARE OR OTHER
APPROVED HANDICAP AGGE55IBL.E CONFIGURATION PER ICG /ANSI 40426
5. ALL DOORS TO BE OPE NABLE FROM THE INSIDE WITHOUT A KEY OR ANY SPECIAL
KNOWLEDGE OR EFFORT.
6. EXISTING DOORS TO REFRAIN.
r
I
O
PARTITION NOTES
PARTITION /ELECTRICAL/
PHONE /DATA PLAN
SCALE :1 /8 "= r -O"
CONTRACTOR TO VERIFY ALL DIMENSIONS. ALL DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE ARCHITECT FOR DIRECTION.
ALL PARTITIONS, UNLESS OTHERWISE NOTED, SHALL BE CONSTRUCTED WITH METAL STUDS AT 24" O.G. WITH
5/8" TYPE 'X' GYPSUM WALLBOARD EACH SIDE.
THERE SHALL BE NO EXPOSED PIPE, CONDUIT, DUCTS, VENTS, ETC. ALL SUCH LINES SHALL BE CONGEALED
OR FURRED AND FINISHED, UNLESS OTHERWISE NOTED AS EXPOSED CONSTRUCTION ON DRAWINGS.
OFFSET STUDS, WHERE REQUIRED, SO THAT FINISHED PARTITION SURFACE WILL BE FLUSH, UNL2S
OTHEWNISE NOTED. PROVIDE FURRING AT EXISTING PARTITIONS AS REQUIRED TO INSTALL ELECTRICAL
ITE=MS AS INDICATED ON THE DRAWINGS.
DOOR AND CASED OPENINGS WITHOUT LOCATION DIMENSIONS ARE TO BE SIX INCHES FROM FACE AT HINGE
SIDE OF DOOR TO ADJACENT PARTITIONS.
ALL EXIT DOORS SHALL BE OPERABLE FROM THE INSIDE WITHOUT USE OF KEY OR ANY SPECIAL
KNOWLEDGE OR EFFORT.
PROVIDE SHEET METAL REINFORCING (S' HORIZONTALLY MOUNTED STRIP OF 20 GA. GALVANIZED SHEET
METAL) IN PARTITIONS FOR INSTALLATION OF WALL HUNG CABINET WORK AND PANELING WHERE INDICATE
ON DRAWINGS INCLUDING ALL OWNER PROVIDED ITEMS.
CONTRACTOR TO VERIFY DIMENSIONS FOR ALL PLUMING PARTITIONS.
CONTRACTOR TO PROVIDE SHOP DRAWING5 FOR DESIGNER AND TENANT APPROVAL PRIOR TO
MM./FACTURE OF ANY CABINET WORK, MILLWORK, AND ANY OTHER SPECIAL ITEMS REQUIRING CUSTOM
SHOP FABRICATED WORK.
MIN. 25 GA MTL. STUD TOP TRACK,
BRAGS TO STRUCTURE WITH EITHER
*12 GA. 6LAV. STL. SUSPENSION HANGER
WIRE SET OR 25 GA. METAL STUDS 0 8'
O.G. OR 2 PER WALL SECTION
MINIMUM, ANCHOR TO TOP
TRACK PER MFG. REQUIREMENTS
CANT. 25 GA. GALV. STEEL
RUNNER CHANNEL ANCHORED
TO FLOOR WITH POWDER
ACTIVATED FASTENING
SYSTEM 0 24' O.G.
EXIST EXIST EXIST
RECEPTION CONFERENCE OFFICE
L 102 1
V
,:;151111111111111111:: .: :i111111111111111111C3_�
O
25 GA. STUDS OR
IRE HANGERS
MAT
EXIST.
CONT. 'L' METAL
TRIM WITH PAPER WING
25 GA. GALV. 3-1/2'
STUDS @ 24' O.G.
5/8" TYPE 'X' G.W.B.
EXIST FFI
L10_4
EXIST
OFFICE
I AS 1
SECTION - BUILDING STANDARD PARTITION
NOT TO SCALE=
NOTE:
I. WALLS LESS THAN 8' -0' IN LENGTH DO NOT REQUIRE BRACING MIST ATTACHED TO ANOTHER WALL.
FIST
1 105 1
I
EXIST
OFFICE
I 118 1
KEY NOTES
0a
D
1 108 IC E
I. ALIGN FINISHED SURFACES.
2. PROVIDE NEW CARPET THROUGHOUT, VERIFY SPED. WITH TENANT.
DIST
WOW ROOM
1105 l
r
1 114 1
EXIST. I
+44'
' 44'
444'
+44 GFI
444'
113
DICE
EXISTING I CE
111
PARTITION LEGEND
EXISTING PARTITION TO REMAIN.
B/5 TENANT PARTITION - B/5 METAL 51U05 24 "O.G. WITH 5/8" TYPE 'X 6413 ON BOTH SIDES FROM
FLOOR TO UNDERSIDE OF HAMS CEILING, SEE DETAIL 11 1 THIS SHEET.
O B/5 3' -0" x DILL HEIGHT SAFETY GLASS RECITE IN 135 FRAME, MATCH EXISTING
STORAXE
CLOSET 00
SCALE:1 /S "= I' -O"
EXIST EXIST EXIST
RECEPTION CO I CE OFFICE
EXIST
6
z
1 103 1
1104
DICE
1 II9
REFLECTED CEILING PLAN
b
EXIST I
6
ELECTRICAL NOTES - VERIFY FINAL LOCATIONS WITH
TENANT
ALL WALL MOUNTED TELEPHONE AND ELECTRICAL OUTLETS TO BE INSTALLED IS' ABOVE FLOOR UNLU
OTHERWISE NOTED.
ALL/ANY CORE DRILL LOCATIONS SHALL BE VERIFIED WITH DESIGNER PRIOR TO DRILLING. ALL LIMIJBED CORE
DRILLS SHALL BE PLUGGED AND CAPPED AS REQUIRED TO MAINTAIN FLOOR FIRE RATING.
ALL. TE.EPHONE AND COMFUTER WIRES SHALL BE PULLED BY TENANTS CONTRACTOR UNLE55 OTHERWISE
NOTED. ELECTRICAL CONTRACTOR SHALL PROVIDE PULL WIRES AND 130) E55 AT EACH LOCATION.
ELECTRICAL LEGEND
N
WALL MOUNTED DUPLEX RECEPTICAL OUTLET
WALL MOUNTED QUADRAPLEX RECEPTACLE OUTLET
WALL MOUNTED COMBINATION TELEPHONE AND DATA OUTLET
WALL MOUNTED Q)ADRAPLEX RECEPTACLE OUTLET - DEDICATED I2OV, 20A
WALL MOUNTED DUPLEX RECEPTACLE OUTLET - DEDICATED I20V, 20A
NEW
NOTE: CONTRACTOR TO REUSE AND / OR RE=LOCATE EXISTING ELECTRICAL / TELEPHONE OUTLETS
WHERE POSSIBLE.
ALL EXISTING ELECTRICAL / TELEPHONE OUTLETS NOT SHOWN ARE TO REMAIN.
USE BUILDING, STANDARD ELECTRICAL FIXTURES 71-1ROU6HO(r UNLESS OTHERWISE NOTED.
EX LI
115 1
0
ki
OFFICE
IC
B
B/5 SINGLE SWITCH
EXIST
6 I
EXIST.
115
LIGHTING NOTES
LIGHTING LEGEND
E
EXISTING TO REMAIN
N NEW
R RELOCATE EXISTING FIXTURE
LIGHTING CALCULATIONS
6
6 1
OFFICE AREA = 3561 S.F.X 1.0 WATTS/S.F= 3561 WATTS ALLOWED
2 x 4 FLUORESCENT - 35 F.A. 0 88 WATTS = 3,344
TOTAL WATTS USED = 3,344 WATTS
WORK ROOM
1109
6
6 1
114
II LE II
6 1
EXIST.
EX ST.
OFFICE
PROVIDE FIRE DAMPERS AT ALL SUPPLY AND RETURN AIR OUTLETS, INLETS, OR DUCTS PENETRATING FIRE
RATED ASSEMBLIES, ENCLOSURES, WALLS, FLOORS, OR SURFACES, AND AS REQUIRED BY FIRE
DEPART NT, IF APPLICABLE.
CONTRACTOR SHALL OBTAIN APPROVAL FROM DESIGNER OF ALL THERMOSTAT LOCATIONS.
ALL REWIRED EXIT SIGNS SHALL HAVE LETTE SIX INCHES HIGH MINIMJM AND SHALL CONFORM WITH ALL
APPLICABLE CODES.
CEILING HEIGHTS ARE FROM SLAB TO FINISHED CEILING.
LIGHT SWITCHES SHALL BE INSTALLED AT +48' A.F.F. MULTIPLE SWITCHES SHOULD BE GANGED TOGETHER
UNLESS OTHERWISE 5PEGIFIED.
CONTRACTOR SHALL PROVIDE EMERGENCY LIGHTING, STROBE LIGHTS, AUDIO VISUAL ALARMS, TO MEET
ALL APPLICABLE CODES.
CONTRACTOR TO VERIFY ALL SWITCH LOCATIONS WITH TENANT PRIOR TO INSTALLATION. NUMBER OF
SWITCHES FOR OPEN AREA 15 BIDDER DESIGN. SWITCHES INDICATED ON DRAWING FOR OPEN AREA ARE
FOR REFERENCE ONLY.
CONTRACTOR SHALL PROVIDE SEISMIC BRACING 0 ALL RELOCATED LIGHT FIXTURES.
I I OFFI
1
EXISTING LIGHT FIXTURES' PLACEMENT. UPGRADE ALL LAMPS TO B/S AVANTE SPECIFICATION
(T5 — 56 WATTS)
NS M 13/5 2 x 4 FLUORESCENT LIGHT FIXTURE - AVANTE - T5 (56 WATTS)
RELOCATE LAMP TO TNIS LOCATION IF POSSIBLE
INDICATES 24 HOUR FIXTURE, WITH EMERGENCY BATTERY BACKUP
PROVIDE NEW 2x4 CEILING TILES, SECOND -LOOK, EXISTING CEILING GRID TO REMAIN
ILLUr1INAT13D CEILING MOUNTED EXIT 5IGN VV/ URGENCY LIGHTS, VERIFY IF REQUIRED -
DIREGTION OF ARROW, LITHONIA LQM S W 6 120 / 211 EL N WHITE THROMOPLAS11G LED EXIT,
SINGLE STENCIL FACE W/ EXTRA FACE PLATE, GREEN LETTERS, W/ NICAP BATTERY BACKUP.,
NO. 5S8087
CONTRACTOR TO REUSE AND / OR RELOCATE EXISTING LIGHT FIXTURES AND SWITCHES MERE
POSSIBLE.
CONTRACTOR TO RE5WITCH / RECIRCUIT LIGHT SWITCHES AND LIGHT FIXTURES AS NEPED.
ALL EXISTING LIGHT FIXTURES / SWITCHES NOT SHOWN ARE TO REMAIN.
"007 39 7
planning interiors architecture
DESIG
22002 - 64th Avenue W., Suite 2C
Mountlake Terrace, WA 98043
T: 425 - 670 -6706 F: 425 - 774 -8219
REGISTRATION
4670
PROJECT NAME
Northwest Restaurants
RIVE PLAZA
TENANT IMPROVEMENT
BUILDING 2 - FLOOR 1
16000 CHRISTENSEN ROAD STE 101
TUKWILA, WASHINGTON
DESIGN TEAM
PROJECT NO.:
07.172
PRINCIPAL:
VSS
DRAWN BY:
EC
CHECKED BY:
VSS
SHEET TITLE
SHEET NO.
CO'' NELL
PALL A
STATE AF WA9tRiTON
lommolommommomeol
ISSUED /REVISIONS
9 -11 -07 ISSUED FOR PERMIT
PROJECT CONSULTANTS
RECEIVED
CITY OF TUKWILA
SEP 1 1 ' r 11
VtN rifR
PARTITION /ELECTRICAL/
PHONE /DATA/REFLECTED
CEILING PLAN