HomeMy WebLinkAboutOrd 2168 - Fire Alarms Plan Submittals and Electrical Permits (Repealed by Ord 2328) -4.10.
o
f„.
to,
f90e!
City of TuklArila
Washington
Cover page to Ordinance 2168
The full text of the ordinance follows this cover page.
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF TUKWILA,
WASHINGTON AMENDING ORDINANCE NO 2131, AS CODIFIED AT
TMC CHAPTER 16.40, "FIRE ALARMS," TO REFLECT CHANGES IN
REQUIREMENTS FOR PLAN SUBMITTALS AND ELECTRICAL
PERMITS, AND TO CLARIFY FIRE WATCH REQUIREMENTS AND
ASSESSMENT OF REINSPECTION FEES, PROV/DIN G FOR
SEVERABILFTY; AND ESTABLISHING AN EFFECTIVE DATE
Ordinance 2168 was amended or repealed by the
following ordinances.
AMENDED BY: REPEALED BY:
2328
r )O
eft'••
rsos
C ity of u la
Washington
Ordinance No. L
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF TUKWILA,
WASHINGTON AMENDING ORDINANCE NO. 2131, AS CODIFIED AT
TMC CHAPTER 16.40, "FIRE ALARMS," TO REFLECT CHANGES IN
REQUIREMENTS FOR PLAN SUBMITTALS AND ELECTRICAL
PERMITS, AND TO CLARIFY FIRE WATCH REQUIREMENTS AND
ASSESSMENT OF REINSPECTION FEES; PROVIDING FOR
SEVERABILITY; AND ESTABLISHING AN EFFECTIVE DATE.
WHEREAS, the City desires its regulations to reflect the fact that it now manages
its own electrical permitting and inspection processes; and
WHEREAS, the City desires to require additional information for fire alarm system
blueprint submittals; and
WHEREAS, the City desires to further clarify its fire watch requirements for
existing systems that are temporarily non functional; and
WHEREAS, the City wishes to provide clarification to contractors on instances
where re- inspection fees may be assessed;
NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF TUKWILA,
WASHINGTON, DO ORDAIN AS FOLLOWS:
Section 1. Ordinance No. 2131, as codified at TMC Chapter 16.40.040, "Approval
and Design Plans," is hereby amended to read as follows:
16.40.040 Approval and Design Plans
A. At least three complete sets of blueprint drawings with information regarding
the fire alarm system, including detailed specifications, wiring, diagrams, elevation
diagram (showing false ceiling areas) and floor plans, shall be submitted to the Tukwila
Fire Prevention Bureau for approval prior to installation of any equipment or wiring.
(One set of approved plans shall be located at the construction site.)
B. Drawings submitted for approval must include the following:
1. Floor layout showing all rooms and spaces, including a cross section of the
space being protected, with accurate measurements drawn to a scale no smaller than
1/8 -inch scale.
2. Identification of each room or space, i.e. guest rooms, mechanical room,
attic, etc.
3. Location of each system component using the appropriate symbol.
4. Explanatory notes and legend to lend clarity to the plan and identify the
manufacturer and model number of each alarm component used.
C: \Documents and Settings \All Users\ Desktop \Kelly \MSDATA \Ordinances \Fire Alarm Systems 2007.doc
DT:ksn 6/14/2007 Page 1 of 4
5. A wiring schematic clarifying type and size of wiring (must comply with
NFPA 70), and a point -to -point wiring diagram.
6. Zoning, if applicable.
7. A copy of the technical specifications for each component used in the
makeup of the automatic fire alarm system. If the components are not all from the same
manufacturer, UL cross listing compatibility cards are required.
8. The current used by each of the initiating and indication devices and
current rating of the power supply.
9. Battery calculations for compatibility.
10. Building permit number.
11. Total number of devices being installed.
C. After the fire alarm plans have been approved by the Tukwila Fire Prevention
Bureau, a job number will be issued to begin work. The plan review fees are as follows:
Commercial: For 1 -5 heads: Base fee $75.00.
Commercial: For 6 or more heads:
Base fee $150.00 $1.50 per device in excess of 10 devices.
Single Family: $50.00 base fee $1.50 per device in excess of 10 devices.
Section 2. Ordinance No. 2131, as codified at TMC Chapter 16.40.050, "General
Requirements," is hereby amended to read as follows:
16.40.050 General Requirements
A. All companies installing automatic fire alarm systems shall have a State
electrical contractor's license.
B. All persons installing automatic fire alarm systems shall hold a State low
voltage installer's certificate or journeyman electrician certificate per RCW 19.28.041.
An apprentice certificate is acceptable for installers when supervised by a certified
journeyman per RCW 19.28.4.
C. A City of Tukwila electrical permit shall be posted at all automatic fire alarm
system installations per TMC 16.04.020 -8.
D. All equipment, devices, and wiring shall be listed by Underwriters
Laboratories or Factory Mutual and shall be approved for the purpose which they are
intended. No one shall perform any type of modification to any device that would void
its UL/ FM listing.
E. If determined necessary by the authority having jurisdiction, control panels
shall have sufficient auxiliary power outlets for automatic door closures, relay boards
for elevator control, HVAC detectors, air pressurization, and all other auxiliary devices.
They shall also have sufficient power for 4 -wire smoke detectors, remote LED
indicating lights and duct detectors with relays.
F. Remote alarm annunciation/ indication is required at the main entrance if the
control panel is not visible from the main entrance.
G. When the control panel is located inside a room, the outside of the door shall
have a sign in 1 -inch letters that reads "Fire Alarm" or "Fire Alarm Control."
C: \Documents and Settings \AII Users\ Desktop \Kelly \MSDATA \Ordinances \Fire Alarm Systems 2007.doc
DT:ksn 6/14/2007 Page 2 of 4
H. A rechargeable battery backup is required on any automatic fire alarm system
installation. There shall be enough battery capacity at all times to run the alarm system
in standby for 24 hours and after that time, sound all alerting devices for at least five
minutes. At the end of the battery life cycle, batteries shall be replaced.
I. Audible devices shall be placed in buildings and be so located that, with all
intervening doors closed, the alarm device shall be heard at not less than 15 decibels
above the ambient noise levels; sleeping areas shall be a minimum of 75 decibels.
Visible alarms shall be placed throughout the building in all assembly areas; common
use areas, including toilet rooms and bathing facilities; hallways and lobbies; and hotel
guest rooms. Individual offices, mechanical rooms, and small storage rooms are not
included.
J. Whenever possible, the control panel shall be located in a heated main corridor
or a heated main lobby. When the control panel is located inside a room, the room shall
be heated, and kept at an ambient temperature between 40° and 100 °F. The outside of
the door shall have a sign in 1 -inch letters, which reads "Fire Alarm" or "Fire Alarm
Control." AT NO TIME SHALL THE CONTROL PANEL BE LOCATED IN AN
EXTERIOR LOCATION.
K. All new alarm systems shall be addressable. Each device shall have its own
address and shall annunciate individual addresses at a UL central station.
Section 3. Ordinance No. 2131, as codified at TMC Chapter 16.40.120, "Special
Requirements," is hereby amended to read as follows:
16.40.120 Special Requirements
A. The guest room detectors of hotel /motel occupancies shall annunciate at a
panel located at or near the front desk. These detectors will not transmit an alarm to the
UL central station. The alarm panel, located at or near the front desk, shall be monitored
24 hours a day by the hotel /motel staff.
B. Multi family dwellings and lodging houses fully protected by an automatic
sprinkler system shall have detectors installed in accordance with the International
Building Code. Common areas and exit corridors shall be protected by detectors and
manual pull stations, monitored by a UL central station.
C. When monitoring of an existing system is lost for any reason, a fire watch must
be posted during non business hours. The fire watch person shall call the recorded fire
prevention phone line at two -hour intervals confirming the all -clear status of the
building. In the event of a fire emergency, the fire watch shall call 911 immediately to
report the fire emergency.
D. Duct detectors shall send a supervisory signal only and shall not cause an
alarm.
E. Lock boxes shall be provided for an access to alarm panels and sprinkler risers.
F. An exterior horn or bell /strobe shall be installed outside all buildings/ tenant
spaces that have a fire alarm system.
Section 4. Ordinance No. 2051, as codified at TMC Chapter 16.40.130, "Re-
inspection Fees for New Construction, Tenant Improvements, and Spot Inspections," is
hereby amended to read as follows:
16.40.130 Re inspection Fees for New Construction, Tenant Improvements, and
Spot Inspections. When an inspection is requested for new construction, tenant
improvements or spot inspections, and then, upon arrival, the Fire Inspector finds that
the work is not complete, not ready for inspection, or does not comply with fire code
C: \Documents and Settings \AII Users\ Desktop \Kelly \MSDATA \Ordinances \Fire Alarm Systems 2007.doc
DT:ksn 6/14/2007 Page 3 of 4
requirements, a follow -up inspection will be required, and a re- inspection fee of $80 will
be assessed.
Section 5. Severability. If any section, subsection, paragraph, sentence, clause or
phrase of this ordinance or its application to any person or situation should be held to
be invalid or unconstitutional for any reason by a court of competent jurisdiction, such
invalidity or unconstitutionality shall not affect the validity or constitutionality of the
remaining portions of this ordinance or its application to any other person or situation.
Section 6. Effective Date. This ordinance or a summary thereof shall be published
in the official newspaper of the City, and shall take effect and be in full force on July 1,
2007 after passage and publication as provided by law.
PASSED BY THE CITY COUNCIL OF THE CITY OF TUKWILA, WASHINGTON,
at a Regular Meeting thereof this g day of 7 2007.
ATTEST AUTHENTICATED:
tr\n,ra2
��e
Steven M. Mullet, Mayor
J6IE. Cantu, CMC, City Clerk
Filed with the City Clerk: 07
APPROVED AS TO FORM BY: Passed by the City Council: t. ice
Published: L- -1 -C7
Effective Date: 2 7 7
Office of the City Attorney Ordinance Number: g'
C: \Documents and Settings \AII Users\ Desktop \Kelly \MSDATA \Ordinances \Fire Alarm Systems 2007.doc
DT:ksn 6/14/2007 Page 4 of 4
SUMMARY OF ORDINANCE
No. 2168
City of Tukwila, Washington
On June 18, 2007, the City Council of the City of Tukwila, Washington, adopted
Ordinance No. 2168, the main points of which are summarized by its title as follows:
An ordinance of the City Council of the City of Tukwila, Washington, amending
Ordinance No. 2131, as codified at TMC Chapter 16.40, "Fire Alarms to reflect
changes in requirements for plan submittals and electrical permits, and to clarify fire
watch requirements and assessment of reinspection fees; providing for severablilty;
and establishing an effective date.
The full text of this ordinance will be mailed upon request.
Approved by the City Council at a Regular Meeting on June 18, 2007.
C�vt e -A i -6-6.
76ade E. Cantu, CMC, City Clerk
Published Seattle Times: June 21, 2007